REHVA Journal – December 2011

KarelKabele
Professor
Czech Technical University in Prague
Department of Microenvironmental and Building Services Engineering
kabele@fsv.cvut.cz

 

Pavla Dvořáková
Assistant Professor
Czech Technical University in Prague
Department of Microenvironmental and Building Services Engineering
pavla.dvorakova@fsv.cvut.cz

 

Introduction

There are several aspects that emphasises the application of radiant heatig/cooling systems in form of embeded capillary mats (Figure 1) to be an up-to-date topic in Central Europe. Desired reduction of energy consumption including primary energy, a recently formed demand for active cooling systems in this region and general expectations of high indoor environmental quality open a wide area for integrated radiant systems. Hand in hand with more and more common applications of these systems various questions arise. This paper has ambitions to answer often asked questions about radiant heating/cooling applications.

 

Figure 1 Integrated heating/cooling ceiling system with capillary mats before covering with the plaster.

Buildings in Central Europe

The typical need for climate conditions of Central Europe (Czech Republic) is space heating during heating period (approx 230 days a year). Up till recent days there were no active cooling systems considered for a traditional building. Due to low internal gains, high thermal inertia and optimised glazing ratio such a building could be operated without any active cooling. For up-to-date buildings (especially office buildings) with high internal gains, high galzing ratio, low mass and well-insulated walls (U value less than 0.3 W/m²K ) and windows (U value less than 1.8 W/m²K ) an active cooling system seems to be essential whenever we want to follow the comfort requirements during summer period. Numerous of these buildings demonstrate the cooling load to be higher or much more higher than the heating load.

Traditional approach to the technical solution of a heating /cooling system is to design two independent systems - radiator heating and split units cooling. One of the latest technical solutions, which could be considered as a sustainable one, is an integrated radiant heating/cooling system.

Radiant heating/cooling systems

Heat transmition to a room equipped with this system is mainly by radiation and convection. Final assesment of the room thermal comfort should not be based just on dry bulb temperature but it is adequate to asses it according to the room resultant temperature – numerical values of these two paramenters might differ significantely during both the winter and the summer period. This fact means that by using this system it is possible to reach lower air temperature in winter and higher air temperature in summer to get the same perception of indoor climate.

Radiant systems are used as ceiling, wall or floor systems.

Comparing to a traditional system, this technical solution integrates two systems into one and it may reduce air change rate to hygienic minimum. The strong point of this solution is a significant reduction of used material or better to say reduction of embodied energy in a heating, cooling and ventilating system (Roulet et al. 1999).

There are several limits for application of these systems. During the heating period the ceiling system output is limited by a hygienic limit reducing highest intensity of radiation on the skull-cap up to 200 W/m². For underfloor heating there is a limit for floor surface temparature – it should not exceed 29°C. In case of wall heating system the surface temperature should be within 35–50°C, based on the room operation. During the cooling period the surface temperature should not drop below the dew point temperature to avoid condensation.

The whole system solution must not cause any local discomfort like asymmetric thermal radiation, large vertical temperature gradient or draught.

Capillary mats

Furthermore paper deals with the radiant heating/cooling system in form of capillary mats.

Capillary mats, embedded in the gypsum plaster layer of the ceiling structure (Figure 2), are supplied by both the heating and the cooling water (four-pipe system) (Figure 3). Ceiling surface transmits energy into the heated/cooled room via radiation and convection heat transfer modes. As the output of radiant system is limited by acceptable surface temperature, often asked question is whenever is this system suitable to use.

Let´s list the elements that might infuense the applicability of integrated radiant systems. These factors come from the limits mentioned above taking into account the type of building and its operation.

Figure 2 Integrated heating/cooling ceiling system with capillary mats.

Figure 3 Four pipe system – connection circuits.

Factors with crucial impact to the system applicability (Figure 4)

·         Indoor sensitive heat load

·         Indoor latent heat load

·         Fresh air volume for ventilation

·         Total air volume for ventilation

·         Indoor humidity control

·         Glazing ratio

·         Glazing quality – U-value, g-value

·         Active shading

·         Room geometry

·         Building orientation

·         Heating setpoint

·         Cooling setpoint

·         Activity and clothing level of building inhabitants

·         Climate

Figure 4 Factors influencing indoor environment in the rooms with radiant heating /cooling.

All of these listed parameters affect the design and operation of HVAC systems. Forgetting these parameters may result in undesirable state of indoor environment. The system does not cover all the demands (heating/cooling) or surface condensation appears.

Modelling and energy performance simulation

One of the ways how to investigate the performance of a radiant heating/cooling system is the use of computer modelling and simulation. By a virtual model with various cases of application it is possible to reach the knowledge about the system operation under different boundary conditions. Several methods and approaches to the building energy performance modelling and simulation are available. However, the issue is very complex, full of bonds between different factors with the basic impact to indoor environment and final applicability of the system. Therefore it is necessary to use simulation tools that can cover all of these effects. Regarding energy performance, control algorithm and whole year IEQ assessment it seems that tools based on method of dynamic heat balance are the best to fulfil our expectation. We can find program ESP-r in this category. It provides time dependent energy flow patterns, temperature and humidity levels in processed parts of the building and some other important values for overall analysis.

If we are looking for a detailed description of temperature and velocity airflow patterns in defined closed space, tools based on the CFD (Computational Fluid Dynamics) method seems to be the best choice e.g. Fluent or Flovent.

Capillary mats modelling

It is possible to find several studies aimed to the applicability of the system with capillary mats in Czech climate conditions. Modelling and simulation of energy performance is effective for complex systems, but it is very sensitive to the way of the task and boundary conditions definition.

To build a model of a room fitted with a heating/cooling ceiling system it is necessary to specify dimensions, building envelope characteristics, environment behind the envelope and orientation of the building. Furthermore it is necessary to set ventilation, lighting, inner loads, activity and presence of users with relevant timing and loads. For the heating/cooling part it is necessary to define maximum output and control loops. Thus defined, the model is loaded with effects of climate conditions of the site, which are again defined by the time dependence of air temperature, relative humidity, wind direction and speed and intensity of solar radiation. Length of the simulated period is chosen depending on which parameters we are interested in. For either only heating or only cooling focused models a characteristic winter or summer week usually provides enough information. A whole year period is preferable for integrated systems. This will also affect the transition period and can alert the otherwise hardly identifiable marginal stages.

Following case study is an example of using the ESP-r simulation tool to analyse energy performance of a room equipped with integrated heating/cooling ceiling system.

Problem description

The main purpose of the study is to investigate integrated heating/cooling system performance during typical Central Europe climate conditions with office operation load profile. This task arose from common practice, when several problems with system application occured despite following all the common recommendations (Kabele et al. 2002).

The issue appeared with following questions. Is the integrated ceiling heating/cooling system able to secure compliance with comfort requirements during the whole year operation in a modelled case? Are the current design recommendations in terms of maximum heating/cooling output of the ceiling applicable particularly in climate conditions of Central Europe? (Figure 5)

C:\Users\Cynthia\Documents\_REHVA_\revha\04_REHVA_journal\REHVA journal 2011\Journal issue 6-2011\articles\fig5.jpg

Figure 5 Annual ambient air temperatures in the Czech Republic.

Research method

Problem analysis followed by computer simulation of an annual building energy performance was used on a case study to analyse selected parameters, that may have any influence on the possibility of system application. ESP-r, an energy system performance simulation tool, was used for this purpose (ESRU 2004).

Modelling and simulation

Model Description

A five - zone modelwas created (Figure 6). The model contains four equal zones with following dimensions 5 m x 9 m x 3 m, each facing different cardinal point, and a corridor in the centre with following dimensions 4 m x 4 m x 3 m. Each of the zones has a window 5 m x 1.6 m in a longer exterior wall. Medium-heavy constructions were considered with the value of overall coefficient of heat transmission according to Czech building regulations (ČSN 730540 2005). For an external wall U = 0.239 W/m²K, for an internal wall U = 1.561 W/m²K and for a window it is 1.198 W/m²K.

No heat flux through ceilings and floors was assumed.

C:\Users\Cynthia\Documents\_REHVA_\revha\04_REHVA_journal\REHVA journal 2011\Journal issue 6-2011\articles\fig6.jpg

Figure 6 ESP-r model of the building.

Heating and cooling system is radiant low temperature heating/high temperature cooling system with capillary mats placed inside the layer of gypsum plaster on ceiling construction and defined by heating capacity controlled according to established practice in a range of 0-130 W/m², cooling capacity 0–80 W/m² in each of the rooms (Jeong et al. 2004). This technical solution is carried out in the model by placing a cooling and heating capacity to the axis of gypsum plaster layer. (R.K. Strand and K.T. Baumgartner 2005) The active ceiling construction contains layers according to Figure 7.

C:\Users\Cynthia\Documents\_REHVA_\revha\04_REHVA_journal\REHVA journal 2011\Journal issue 6-2011\articles\fig7.jpg

Figure 7. Active Ceiling/Floor construction: 1 Flooring, 2 Polyurethane foam board, 3 Heavy mix concrete, 4 Gypsum plaster with capillary mats.

The control of the system is running as basic heat and cool controller according to sensors, located in each of the rooms sensing dry bulb temperature. Set point for heating is 22°C; for cooling 26°C. There is no humidity control considered.

Ventilation. Mechanical ventilation 0.7 h-1 and infiltration 0.3 h-1 is considered. Supply air temperature is 20°C.

Occupation and casual gains. Sensitive and latent heat load by persons is 7.8 W/m² during working hours (weekdays 7:00-18:00), sensitive heat load by equipment is 15 W/m²and by lights 25 W/m²during the whole day.

Simulation

The whole year period was studied using Prague (Czech Republic) ASHRAE IWEC climate files. An integrated building simulation was used, with time step of 1 hour and initial period of 11 days. The discussion of the results was focused on heating/cooling energy consumption. PMV and PPD parameters were used to evaluate thermal comfort (Yang 1997, ČSN EN ISO 7730 2005). The third thing to follow was the possibility of condensation on the ceiling surface during the cooling period.

Simulation results and discussion

In following tables and diagrams there are selected simulation results from ESP-r.

Energy

From the point of annual energy consumption the results show a significant impact of the internal heat loads which decrease energy demand for heating and increase cooling demand comparing to unoccupied space. The effect of building orientation for both the heating and the cooling energy demand is also significant (Table 1)

Table 1. Annual energy h/c consumption.

Zone

En. for Heating

Operating time

En. for Cooling

Operating time

 

[kWh]

[h]

[kWh]

[h]

room1

283

264

-12211

4455

room2

436

392

-11049

4146

room3

253

282

-11415

4247

room4

328

301

-13007

4633

Total

1301

 

-47682

 

Thermal comfort – resultant temperature

The temperature curve confirmed the ability of the heating/cooling system capacity to guarantee set temperatures inside all of the zones almost during the whole year. Set point for cooling was exceeded only in several hot days during summer with maximum value 31.5°C (Table 2)

Table 2. Resultant temperature extremes.

zone

Maximum [°C]

Minimum [°C]

Mean value [°C]

Standard deviation

room1

29.7

22.5

25.3

1.2079

room2

28.5

22.5

25.1

1.1186

room3

27.8

22.5

25.1

1.0106

room4

31.5

22.5

25.4

1.3316

corridor

27.5

23.9

25.7

0.85953

Thermal comfort – PMV, PPD

Thermal comfort evaluation is based on PMV (Predicted Mean Vote) and PPD (Predicted Percentage of Dissatisfied) classification of heated/cooled spaces. PMV is defined by six thermal variables for indoor-air and human condition. It is air temperature, air humidity, air velocity, mean radiant temperature, clothing insulation and human activity. The value of PMV index has range from −3 to +3 which corresponds to human sensation from cold to hot. The null value of PMV index means neutral. It is desirable to maintain the PMV at level 0 with a tolerance of ±0.5 to ensure a comfortable indoor climate. Comfort evaluation is based on activity level 1.2 met with clothing level equal to 0.7 clo (ASHRAE 2005, CSN EN ISO 7730) in this case study.

The results show PMV index to be from 0.0 to 2.0. Index PPD in 48% of the time is up to 10% which means that during this time the number of dissatisfied occupants will not exceed 10%. Index PPD during 99% of the time is up to 50%.

From the point of heating there is no problem with thermal comfort in all of the examined cases; minimum value for PMV during heating period is 0.0, which means neutral.

On the other hand several problems with thermal comfort during cooling period were detected. In this case the maximum PMV index reached 2.0, which means warm (Figure 8).

C:\Users\Cynthia\Documents\_REHVA_\revha\04_REHVA_journal\REHVA journal 2011\Journal issue 6-2011\articles\fig8.jpg

Figure 8 Annual distribution of PMV and PPD index (ESP-r).

Active ceiling surface temperatures and surface condensation

The active ceiling surface temperatures coming out from the simulation are in figures. Figure 9shows temperature difference between active ceiling surface temperature and the dew point temperature during the year. Critical period (the value is below zero) is marked with circle. Detailed analysis of critical time is on the Figure 10.

The possibility of surface condensation occurred in a range of one or two hours during one critical day of the year in summer when the exterior relative humidity was very high.

C:\Users\Cynthia\Documents\_REHVA_\revha\04_REHVA_journal\REHVA journal 2011\Journal issue 6-2011\articles\fig9.jpg

Figure 9 Temperature difference between active ceiling surface temperature and the dew point temperature.

C:\Users\Cynthia\Documents\_REHVA_\revha\04_REHVA_journal\REHVA journal 2011\Journal issue 6-2011\articles\fig10.jpg

Figure 10 Integrated look at energy and environmental performance during critical days. OccCasG - internal heat gains, CoolInj-cooling system injection, AmbientRH-ambient air relative humidity, dbT- zone dry bulb temperature, Ambient dbTmp- ambient dry bulb temperature, room1RH- zone relative humidity, Surf-5:room1Dsur-dpT difference between cooling surface temperature and dew point. Critical hours marked with circle.

Conclusion

Is it possible to use an integrated heating/cooling ceiling system in a modern building, built according to valid Czech standards with respect to energy efficiency in Czech climate conditions? The question has been analysed. The purpose of created case study was to predict thermal behaviour of the room heated/cooled with this system and to describe thermal comfort behaviour in time during a whole year operation. ESP-r, a modelling tool was applied.

Based on the simulation results no problems with the heating were detected anywhere. The system can reliably guarantee the required temperature during the whole year. At the same time the simulation shows that common designed heating/cooling capacities (130 and 80 W/m²) of the ceiling surface are appropriate. Several problems appeared with the cooling. The designed capacity was not able to cover the temperature requirements and occasionally a short-term condensation appeared. This means that the application of this integrated system is limited by its capacity. Especially in the buildings with higher internal gains this application is arguable. Following the effect of building orientation individual control of the zones is recommended.

The results from above and the conclusions made from them are valid for the conditions of the simulation.

 

Acknowledgments

This paper was supported by Research Plan CEZ MSM 6840770003.

References

1.   ASHRAE. Fundamentals, 2005. Atlanta, USA

2.   Claude-Alain Roulet, Jean-Pierre Rossy and Yves Roulet. 1999 Using large radiant panels for indoor climate conditioning, Energy and Buildings, Volume 30, Issue 2, June 1999, Pages 121-126.

3.   ČSN 730540 Thermal protection of buildings – Part 2: Requirements. 2005. Czech Standardization Institute 2005.

4.   ČSN EN ISO 7730 2005. Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria.

5.   ESRU 2004. ESP-r A Building Energy Simulation Environment; User Guide Version 10 Series, ESRU Manual University of Strathclyde, Energy Systems Research Unit, Glasgow.

6.   HenzeGregor P., Felsmann Clemens, Kalz Doreen E. and Herkel Sebastian. 2007. Primary energy and comfort performance of ventilation assisted thermo-active building systems in continental climates, Energy and Buildings, In Press, Corrected Proof, Available online 2 February 2007.

7.   Jeong Jae-Weon and Mumma Stanley A. 2004. Simplified cooling capacity estimation model for top insulated metal ceiling radiant cooling panels, Applied Thermal Engineering, Volume 24, Issues 14-15, October 2004, Pages 2055-2072.

8.   Kabele, K., Vávra, P., Veverková, Z., Centnerová, L. 2002. Optimisation of panel radiant systems for heating and cooling in buildings (in Czech) Proceedings of 10th international conference Heating 2002 pp.188-193, 13.-15.3 2002 Podbanské, Slovak Republic, SSTP 0216 ISBN 80-967479-1-6.

9.   Kabele, K.,Dvořáková, P. 2006. Indoor Air Quality in Sustainable Architecture, Proceedings of Healthy Buildings 2006, Lisboa 4-8 June 2006, vol. 3, pp 1-4. ISBN 989-95067-1-0.

10.Koschenz, M. and Dorer, V. 1999. Interaction of an air system with concrete core conditioning. Energy and Buildings. 30(2): 139.

11.LaouadiAbdelaziz. 2004. Development of a radiant heating and cooling model for building energy simulation software, Building and Environment, Volume 39, Issue 4, April 2004, Pages 421-431.

12.Petráš, D. Low – temperature combined heating for sustainable low-energy buildings, SSTP 2001., 4th.international conference Indoor climate of buildings 2001.

13.Strand R.K. and Baumgartner K.T. 2005. Modeling radiant heating and cooling systems: integration with a whole-building simulation program, Energy and Buildings, Volume 37, Issue 4, April 2005, Pages 389-397.

14.K. H. Yang and C. H. Su. 1997. An approach to building energy savings using the PMV index, Building and Environment, Volume 32, Issue 1, January 1997, Pages 25-30.

15.Kabele, K., Dvořáková, P.: Integrated HVAC systems in Central Europe climate, In: Clima 2007 WellBeing Indoors Proceedings CD ROM [CD-ROM]. Brussels, REHVA, 2007, ISBN 978-952-99898-3-6.

Karel Kabele, Pavla DvorákováPage