Zhang Lin
Building Energy & Environmental Technology Research Unit
City University of Hong Kong
bsjzl@cityu.edu.hk

 

The goal of decreasing carbon emission and increasing energy conservation is a continuous process. There is no single method for achieving this goal. Should we aim to increase the amount of equipment in order to offset the negative byproducts of our existing systems? In contrast, we can try to decrease the amount of equipment we use. As long as we satisfy the performance requirements, the result will be a decrease in economic and environmental costs. Only with ongoing research and development are we able to make progress towards the correct path. This paper looks at the field of HVAC with regards to the increasing pressure from climate change. It proposes the use of a new type of air distribution system: stratum ventilation, which takes advantage of the allowance for higher indoor air velocities to offset the elevated temperatures.

Keywords: ventilation, air distribution, air jets, stratum ventilation, thermal comfort

Current Situation

With the looming presence of worldwide climate change (Pachauri 2007), there is constant pressure to make changes to improve the situation. As a result of numerous global conferences and discussions, there is an international consensus to reduce CO2 emission. The EU has established policies to achieve nearly zero energy buildings by 2020 (Directive 2010/31/EU 2010). A byproduct of these types of buildings, however, is the extreme insulation and airtightness they are constructed with in order to withstand the harsh climates. The result is reduced indoor air quality and thermal comfort in the summer due to the restricted evacuation of heat gains. Therefore, the role of mechanical ventilation is increased in these buildings to compensate for the increase in sanitary and cooling requirements. Alternatively, minimizing the energy consumption used by air-conditioning systems would decrease the amount of CO2 emission. With this in mind, while revising EN ISO 7730 (Olesen n.d.), Fountain and Aren’s theory was used. The theory stated that higher air speed was required to offset increased indoor temperature (Fountain and Arens 1993).

In East Asia, the governments of the various judiciaries have recently issued guidelines and made changes in setting the indoor air temperature during the summer:

·  The Hong Kong Electrical and Mechanical Services Department (EMSD) established guidelines to set the room temperature of an air-conditioned space to 25.5°C in the summer months (Electrical and Mechanical Services Department (EMSD), Government of Hong Kong S.A.R. n.d.).

·  The National Development and Reform Commission of the Chinese State Council established guidelines to set the indoor temperature to 26°C in the cooling season (National Development and Reform Commission (NDRC), The State Council of China n.d.).

·  Room temperature in the “Presidential Office” in Taipei has been set to 27°C after Dr. Ma Ying-jeou’s inauguration in May 2008 (NOW news 2008).

·  The Ministry of Knowledge and Economy of Korea recommends room temperatures ranging from 26°C to 28°C in summer (Ministry of Knowledge and Economy 2008).

·  The Ministry of Environment (MoE) of the Japanese Cabinet has encouraged its citizens to set the temperature of offices to 28°C in summer months (Ministry of the Environment (MoE) 2005).

Although these guidelines are correct from a political and environmental point of view, they are not widely implemented for two reasons. Firstly, the setting of indoor temperature is guided by the thermal comfort of the occupants and not by government regulations. Secondly, even if the room temperature is set to 26°C, only a small percentage of energy savings is obtained using conventional air distribution with a non-reheat air treatment. If a reheat air treatment is applied, even more energy would be consumed. With this in mind, it would be ideal if thermal comfort was obtainable at elevated temperatures while also achieving notable energy savings.

Allowance for increased air velocity

Air velocity is one of the major factors influencing thermal comfort along with air temperature, relative humidity, mean radiant temperature, metabolic rate, and clothing insulation. One of the implications of ASHRAE 55-2004 was that the air velocity should not be perceived by the occupants (v < 0.35 m/s). The introduction of ASHRAE 55-2010 allowed for elevated air movement to broadly offset the need to cool the air in warm conditions (ASHRAE 2010). This recent change allows for new opportunities to manage increased room temperatures.

Identifying suitable air distribution systems for elevated temperatures

In order to take advantage of a higher air velocity allowance, a criterion must be established to identify suitable air distribution systems for elevated temperatures. These systems should operate with temperatures and air movements comparably higher but within the range defined by ASHRAE 55-2010. There should be horizontal airflow targeting the head, neck, and chest of the occupants from the frontal or lateral directions. This criterion was based on studies that for light activities, to remove metabolic heat from the brain, cooling should be focused upon an area superficial to the carotid arteries and jugular vein (Williams and Chambers 1971, Brown and Williams 1982, Nunneley et al. 1982, Cohen et al. 1989, Nakamura et al. 2008). Studies also showed that occupants were less sensitive to air movement from the front (Mayer 1992) and sides (Toftum, Zhou and Melikov 1997). Using this criterion, an assessment was made to determine how conventional air distribution systems match up.

Mixing ventilation is the most common air distribution system. With its ceiling-mounted air inlets and outlets, horizontal air movement is not available. Mixing ventilation would have high fan energy consumption if the required air movement in the occupied zone is realized because of the distances between the diffusers and the occupants. It is also not applicable for heating due to the short circuiting of the warm airflows.

Displacement ventilation is thermally driven with air movement flowing upwards from the floor level. It generally provides higher air quality and better ventilation efficiency than mixing ventilation with the same airflow (Awbi 1991). Using horizontal air movement would be contradictory to the concept of displacement ventilation as it would disrupt the thermal plume around the occupants. Displacement ventilation also tends to cause overcooling of the lower zone, causing discomfort at the leg area of occupants (Wyon and Sandberg 1990). Similar to mixing ventilation, using displacement ventilation for heating would cause short circuiting of the airflow because the warm supply air is buoyant.

Using personalized/task ventilation would satisfy the established criterion. This type of air distribution supplies occupants with air from nozzles located nearby plus a background general air distribution. It uses nozzles near the occupants to distribute fresh air, providing horizontal air flow. It is very effective at providing adequate indoor air quality with good energy efficiency. However, it is often difficult and expensive to connect ducts and equip nozzles to various indoor spaces. It would also be difficult to manage in cases where the occupants require any sort of mobility and repositioning.

Stratum ventilation for small-medium rooms

The rationale behind stratum ventilation is that the indoor air quality and thermal comfort are unimportant beyond the occupied zone. In addition, the indoor air quality below the breathing zone is not important. Stratum ventilation uses air inlets and outlets mounted on the wall(s) as shown in Figures 1 and 2. The air is supplied directly into the breathing zone, forming a young air layer as shown in Figure 3.

m in m out 3副本.JPG

Figure 1. Conceptual design of stratum ventilation.

P1015353

Figure 2. Application of stratum ventilation in a classroom.

6ach21-1

Figure 3. Demonstration of the air supply stratum with smoke.

The occupants get the benefit of good IAQ by staying within the air supply streams and gaining more exposure to the fresh air. The age of air is younger and the CO2 concentration is lower compared with conventional air distributions (Lin et al. 2012, Tian et al. 2010 and 2011). Unlike with mixing ventilation and displacement ventilation, the return air inlets mounted in the occupied zone allow for the possibility of heating, where the stratum effect is maintained.

This setup creates a modest, reverse temperature gradient (Figure 4) in the occupied zone, preventing the lower zone from being over-cooled. The thermal sensation of stratum ventilation was explored alongside mixing ventilation and displacement ventilation with an experimental study involving human subjects. The same subjects were subjected to varying room temperatures in a thermal sensation analysis. Using the thermal sensation votes, it was determined that mixing ventilation, displacement ventilation, and stratum ventilation had a neutral temperature of 24.6°C, 25.1°C, and 27.1°C respectively as shown in Figure 5 (Fong et al. 2011).

 

Figure 4. Vertical temperature profile of stratum ventilation.

 

This shows that stratum ventilation is more suitable at operating in elevated temperatures than conventional ventilation systems. A larger database comprising of the aforementioned data and data also for varying supply airflow rates and air diffuser types reveals that stratum ventilation can provide a uniform thermal environment (Cheng et al. 2014).

 

Figure 5. Thermal sensation votes of subjects.

Energy savings with stratum ventilation

There are eight factors which contribute to the energy savings of stratum ventilation in comparison to conventional systems.

1.   The neutral temperature of 27°C yields a higher humidity ratio for same relative humidity, lowering the latent load.

2.   The higher neutral temperature means there is a smaller temperature difference between the indoor and outdoor space, resulting in smaller transmission loads.

3.   The smaller enthalpy difference between the indoor air and outdoor air means there is a lower ventilation load.

4.   There is a longer free cooling period because of the higher enthalpy of the indoor air.

5.   The higher ventilation effectiveness means a lower ventilation load.

6.   The reverse temperature gradient in the occupied zone means there is no over-cooling of the lower zone.

7.   The elevated supply air temperature allows the associate chiller to have a higher evaporative temperature.

8.   The lower cooling capacity permits the use of smaller pumps and fans.

 

A simulation of the year-round electric energy consumption of a typical office, a typical retail shop and a typical classroom in Hong Kong shows that stratum ventilation provides a significant amount of energy savings as seen in Table 1 (Lin et al. 2011, Lee et al. 2013). The electrical energy consumption includes the entire air conditioning system, namely chiller and AHU (fans are inclusive), but excludes lighting, appliances in the rooms and other non-air-conditioning equipment in the rooms.

Table 1. Comparison of the year-round energy consumption between different ventilation systems.

Air Distribution System

Electric Energy Consumption (kWh/netto-m2)

Mixing

794

Displacement

592

Stratum

472

 

Energy Savings

Mixing to Displacement

25.40%

Displacement to Stratum

20.15%

Mixing to Stratum

40.43%

 

Overall, stratum ventilation is novel in that it is an innovative air distribution design concept while being old technology that requires only existing components, minimizing the risk of failure. The smaller capacity of stratum ventilation leads to smaller mechanical plants and ductwork, smaller air conditioning systems that take up less space, and substantially lower year-round energy consumption. These aspects yield lower initial costs, operational costs, and a smaller life-cycle carbon footprint.

Conclusion

With the presence of worldwide climate change and the corresponding governmental responses, improvements must be made upon conventional air distribution systems. With the introduction of ASHRAE 55-2010, there are new provisions for changes to conventional systems to meet the demands of elevated temperatures. Stratum ventilation has shown the potential to be a significant improvement upon conventional systems. Its use of increased air velocity allows for thermal comfort at temperatures 2.5°C higher while providing yearly energy savings of at least 20% over conventional systems.

Acknowledgment

The work described in this paper is supported by a General Research Grant from the National Natural Science Foundation of China (Project No. 51178407).

References

ASHRAE. ANSI/ASHRAE Standard 55-2010 Thermal Environmental Conditions for Human Occupancy. Atlanta: American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc, 2010.

Awbi, H.B. Ventilation of Buildings. London: E&FN Spon, 1991.

Brown G.A. Williams G.M. (1982) The effect of head cooling on deep body temperature and thermal comfort in man. Aviation Space and Environmental Medicine 53(6): 583-586.

Cheng Y, Fong ML, Yao T, Lin Z, Fong KF, 2014. Uniformity of stratum ventilated thermal environment. Indoor Air, in press.

Cohen J.B. Allan J.R. Sowood P.J. (1989). Effect of head or neck cooling used with a liquid-conditioned vest during simulated aircraft sorties. Aviation Space and Environmental Medicine 60(4): 315-320.

Directive 2010/31/EU of the European Parliament and of the Councuilof 19 May 2010on the energy performance of buildings.

Electrical and Mechanical Services Department (EMSD), Government of Hong Kong S.A.R. Energy conservation charter 2006-suitable room temperature. n.d. http://www.energyland.emsd.gov.hk/blue_sky/eng/index.htm.

Fong ML, Lin Z, Fong KF, Chow TT, Yao T. Evaluation of thermal comfort conditions in a classroom with three ventilation methods. Indoor Air2011; 21(3): 231-39.

Fountain, ME, and EA Arens. "Air movement and thermal comfort." ASHRAE Journal, August 1993: 26-30.

Lee CK, Fong KF, Lin Z, Chow TT, 2013. Year-round energy saving potential of stratum ventilated classrooms with temperature and humidity control. HVAC&R Research, 19(8): 986-991.

Lin Z, Lee CK, Fong KF, Chow TT, Yao T, Chan ALS, 2011. Comparison of annual energy performances with different ventilation methods for cooling. Energy and Buildings, 43: 130–136.

Lin Z, Wang J, Yao T, Chow TT. Investigation into anti-airborne infection performance of stratum ventilation. Building and Environment, 2012; 54: 29-38.

Mayer, E. "New measurements of the convective heat transfer coefficients: influences of turbulence, mean air velocity and geometry of human body." ROOMVENT. Lyngby: Danish Association of HVAC Engineers (DANVAK), 1992. 263-76.

Ministry of the Environment (MoE). National campaign to fight global warming. April 28, 2005. http://www.env.go.jp/en/press/2005/0428b.html.

Ministry of Knowledge and Economy, the Republic of Korea. The standard of energy management, December 29, 2008. http://www.mke.go.kr/info/law/gosiView.jsp? (Item No. 2008-219).

Nakamura M. Yoda T. Crawshaw L.I. Yasuhara S. Saito Y. Kasuga M. Nagashima K. Kanosue K. (2008) Regional differences in temperature sensation and thermal comfort in humans,  Journal of Applied Physiology 105(6): 1897-1906.

National Development and Reform Commission (NDRC), The State Council of China. Citizen’s pact for deed of thrift. n.d. http://www.ndrc.gov.cn/gzdt/t20051223_54462.htm.

NOW news. Campaign in office of president for saving energy and reducing carbon emissions. May 24, 2008. http://www.nownews.com/2008/05/24/10844-2279584.htm.

Nunneley S.A. Reader D.C. Maldonado R.J. Head-temperature effects on physiology, comfort, and performance during hyperthermia. Aviation Space and Environmental Medicine 53(7): 623-628.

Olesen, BW. "Introduction to the new revised draft of EN ISO 7730." Norderstedt, n.d.

Pachauri, RK. The IPCC fourth assessment working group reports: key findings. United Nations Headquarters, New York City: IPCC, 2007.

TianL, Lin Z, Wang Q. Comparison of gaseous contaminant diffusion under stratum ventilation and under displacement ventilation. Building and Environment, 2010; 45(9):2035-2046.

Tian L, Lin Z, Wang Q. Experimental investigation of thermal and ventilation performances of stratum ventilation. Building and Environment, 2011; 46(6): 1309-1320.

Toftum, J, G Zhou, and A.K. Melikov. "Effect of airflow direction on human perception of draught." CLIMA 2000. Brussels, 1997. 366.

Williams B.A. and Chambers A.B. (1971) Effect of neck warming and cooling on thermal comfort, NASA Special Publications SP-302: 289-294.

Wyon, DP, and MG Sandberg. "Thermal manikin prediction of discomfort due to displacement ventilation." ASHRAE Transactions, 1990: 96.

Zhang LinPages 40 - 43

Stay Informed

Follow us on social media accounts to stay up to date with REHVA actualities

0

0 product in cart.products in cart.