Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Besides the standard, a Technical Report 16798-2 is also being developed to support and explain the standard in more details. The standard is now written in normative language and should be clearer as all the informative text will be included in the technical report. The standard does include default criteria in 3-4 categories (Table 1) for the indoor environmental parameters, as described in this paper. It is however in a series of tables in an informative annex B. Individual countries can decide if they want to use these default values, only use one category, or use quite different values, which will be included in a normative national annex A with similar structure as annex B.
Table 1. Description of the applicability of the categories used.
Category | Explanation |
I | High level of expectation and also recommended for spaces occupied by very sensitive and fragile persons with special requirements like some disabilities, sick, very young children and elderly persons, to increase accessibility. |
II | Normal level of expectation |
III | An acceptable, moderate level of expectation |
IV | Low level of expectation. This category should only be accepted for a limited part of the year |
It is important to emphasis that the requirements and default criteria are based on the influence on the occupants and the standard do not set direct criteria depending on the type of system (mechanical or non-mechanical) used for conditioning the space.
The draft technical report TR16798-2 will include guidance to the standard in similar sections as the standard. The TR includes also some additional sections and annexes with more voluntary concepts and methods as described in this paper.
In parallel two similar documents ISO-CD17772 and ISO-DTR17772 are being developed as almost identical documents. At a later stage it may be possible to combine these standards to one EN-ISO standard. The entire mentioned document will be available for comments during the first couple of months in 2015.
In the following section some of the highlights and especially what is new will be described.
The sections for thermal environment are almost identical to the existing standard. Criteria for both mechanical and non-mechanical heated, cooled and ventilated buildings are included. An addition is the criteria for local thermal discomfort based on EN ISO 7730 including draught, vertical air temperature differences, and radiant thermal asymmetry and floor surface temperatures. These criteria do not influence the calculation of energy performance; but will influence the design of the building and heating, cooling, and ventilation systems.
In the standard personalized systems have been introduced as a new part; but without any default criteria. However an annex in the TR gives some examples on how criteria for personalized systems could be expressed (see Table 2).
Table 2. Example criteria for personalized systems.
Aspect | Requirement |
‘Temperature’ control winter | At workstation level, the (operative/equivalent) temperature is adjustable with a response speed of at least 0,5 K / minute within a range of 5 K, from 18 to 23 °C. |
‘Temperature’ control summer | At workstation level, the (equivalent) temperature is adjustable (with a response speed of at least 0,5 K / minute within a range of 5 K, from 22 to 27 °C. |
Fresh air supply control | Local fresh air supply (per workstation) is adjustable from around 0 to at least 7 l/s. |
Delivered air quality | For requirements related to air cleaning technology: see Annex K. |
Installation noise | Noise level - with the personalized system in the highest setting - should not be higher than 35 dB(A). |
The standard does include some new aspects related to indoor air quality. Like in the existing standard the requirements to indoor air quality is mainly expressed as a required minimum ventilation rate. The general requirements for the designer regarding the indoor air quality is the same for residential and non-residential buildings.
Design parameters for indoor air quality shall be
derived using one or more of the following methods:
·
Method based on perceived air quality
·
Method using criteria for pollutant
concentration
·
Method based on pre-defined ventilation
air flow rates
Within each method, the designer shall
choose between different categories of indoor air quality and define which
building category is to be used. The method used shall be documented and it
must be explained why the selected method is appropriate.
The total
ventilation rate for the breathing zone is found by combining the ventilation
for people and building calculated from the following formula.
qtot = n · qp + AR · qB Eq (1)
Where
qtot = total
ventilation rate for the breathing zone, l/s
n = design value for the number of the persons in
the room, –
qp = ventilation
rate for occupancy per person, l/s·per person
AR = floor area, m²
qB = ventilation rate for emissions from building, l/s
per m²
The basic tables with default values are Table 3 and Table 4. The perceived air quality levels are set for non-adapted persons. If in special cases the design will include adapted persons see TR16798-2. A new criteria is that the total ventilation rate must never be lower than 4 l/s per person.
Table 3. Design ventilation rates for non-adapted persons for diluting emissions (bioeffluents) from people for different categories.
Category | Expected Percentage
Dissatisfied | Airflow per non-adapted
person |
I | 15 | 10 |
II | 20 | 7 |
III | 30 | 4 |
IV | 40 | 2,5* |
* Category IV is intended for the evaluation of IAQ in existing buildings where the space for installations are limited.
Table 4. Design ventilation rates for diluting emissions from different type of buildings.
Category | Very low polluting
building, | Low polluting building, | Non low-polluting
building, |
I | 0,5 | 1,0 | 2,0 |
II | 0,35 | 0,7 | 1,4 |
III | 0,2 | 0,4 | 0,8 |
IV | 0,15 | 0,3 | 0,6 |
Minimum
total ventilation rate for health | 4 l/s per person | 4 l/s per person | 4 l/s per person |
A building is by default a low-polluting building unless prior activity has resulted in pollution of the building (e.g. smoking). In this case, the building shall be regarded as non-low polluting. The category very low-polluting requires that the majority of building materials used for finishing the interior surfaces meet the national or international criteria of very low-polluting materials. An example of how to define very low-polluting building materials is given in Annex B3 of the standard.
The technical report will show tables with default values based on the two tables above and an assumed density of occupants. An example is given here in Table 5.
As mentioned above the technical report is
also discussing a possible design for adapted persons i.e. persons that have
occupied the space for more than 15 minutes and then adapted to the odour level
of bioeffluent from the occupants. This may be relevant for spaces like
conference rooms and auditorium, where people enter at the same time. The odour
level will increase (perceived air quality decrease); but at the same time the
occupants adapt to the odour level in the space and the lower ventilation and
level of perceived air quality acceptable. This is as example the basis for the
minimum ventilation rates given in ASHRAE standard 62.1. In the present
standard prEN16798-1 the criteria of a total ventilation of minimum 4 l/s
person must be fulfilled. It can be seen in Table 5 that
only in a few cases the criteria of 4 l/s person will be used and only for
category 4. On the other hand if the ventilation rate is designed for adapted
occupants the criteria of minimum 4 l/s person is used in all cases except
for Category I.
The values in italics indicate situations where the calculated ventilation rate
is lower than the minimum value of 4 l/s per person required for health.
Table 5. Non-adapted persons.
Examples of recommended ventilation rates for non-residential buildings with
default occupant density for three categories of pollution from the building.
Type of building
or space | Category | Floor area m² per person | qp | qp | qB | qtot | qB | qtot | qB | qtot | ||||
minimum ventilation rate | ||||||||||||||
l/s per m² | l/s per person | l/s per m² | l/s per m² | l/s per person | l/s per m² | l/s per m² | l/s per person | l/s per m² | l/s per m² | l/s per person |
| |||
for occupancy only | for very low-polluted building | for low-polluted building | for non-low polluted building | |||||||||||
Single office | I | 10 | 1 | 10 | 0,5 | 1,5 | 15 | 1 | 2,0 | 20,0 | 2 | 3,0 | 30 | |
II | 10 | 0,7 | 7 | 0,35 | 1,1 | 11 | 0,7 | 1,4 | 14,0 | 1,4 | 2,1 | 21 | ||
III | 10 | 0,4 | 4 | 0,2 | 0,6 | 6 | 0,4 | 0,8 | 8,0 | 0,8 | 1,2 | 12 | ||
IV | 10 | 0,25 | 2,5 | 0,15 | 0,4 | 4 | 0,3 | 0,6 | 5,5 | 0,6 | 0,9 | 9 | ||
Landscaped
office | I | 15 | 0,7 | 10 | 0,5 | 1,2 | 18 | 1 | 1,7 | 25,0 | 2 | 2,7 | 40 | |
II | 15 | 0,5 | 7 | 0,35 | 0,8 | 12 | 0,7 | 1,2 | 17,5 | 1,4 | 1,9 | 28 | ||
III | 15 | 0,3 | 4 | 0,2 | 0,5 | 7 | 0,4 | 0,7 | 10,0 | 0,8 | 1,1 | 16 | ||
IV | 15 | 0,2 | 2,5 | 0,15 | 0,3 | 5 | 0,3 | 0,5 | 7,0 | 0,6 | 0,8 | 12 | ||
Conference room | I | 2 | 5 | 10 | 0,5 | 5,5 | 11 | 1 | 6,0 | 12,0 | 2 | 7,0 | 14 | |
II | 2 | 3,5 | 7 | 0,35 | 3,9 | 8 | 0,7 | 4,2 | 8,4 | 1,4 | 4,9 | 10 | ||
III | 2 | 2 | 4 | 0,2 | 2,2 | 4 | 0,4 | 2,4 | 4,8 | 0,8 | 2,8 | 6 | ||
IV | 2 | 1,25 | 2,5 | 0,15 | (1,4) 1,8 | (3) 4 | 0,3 | (1,6) 2 | (3,1) 4 | 0,6 | 1,9 | 4 | ||
Auditorium | I | 0,75 | 13,3 | 10 | 0,5 | 13,8 | 10 | 1 | 14,3 | 10,8 | 2 | 15,3 | 12 | |
II | 0,75 | 9,3 | 7 | 0,35 | 9,7 | 7 | 0,7 | 10,0 | 7,5 | 1,4 | 10,7 | 8 | ||
III | 0,75 | 5,3 | 4 | 0,2 | 5,5 | 4 | 0,4 | 5,7 | 4,3 | 0,8 | 6,1 | 5 | ||
IV | 0,75 | 3,3 | 2,5 | 0,15 | (3,5) 4.7 | (3) 4 | 0,3 | (3,6) 5,3 | (2,7) 4 | 0,6 | (3,9) 4,7 | (3) 4 |
Table 6. Adapted persons. Examples of recommended ventilation rates for non-residential buildings with default occupant density for three categories of pollution from building itself.
Type of building
or space | Category | Floor area m² per person | qp | qB | qtot | qB | qtot | qB | qtot | ||||
Adapted qp
according to table B1 | |||||||||||||
l/s per m² | l/s per person | l/s per m² | l/s per m² | l/s per person | l/s per m² | l/s per m² | l/s per person | l/s per m² | l/s per m² | l/s per person | |||
For occupancy | for very low-polluted building | for low-polluted building | for non-low polluted building | ||||||||||
Conference room | I | 2 | 1,75 | 3,5 | 0,5 | 2,25 | 4,5 | 1 | 2,75 | 5,5 | 2 | 3,75 | 7,5 |
II | 2 | 1,25 | 2,5 | 0,35 | 1,60 | (3,2)4 | 0,7 | 1,95 | (3,9)4 | 1,4 | 2,65 | 5,3 | |
III | 2 | 0,75 | 1,5 | 0,3 | 1,05 | (2,1)4 | 0,4 | 1,15 | (2,3)4 | 0,8 | 1,55 | (3,1)4 | |
IV | 2 | 0,50 | 1 | 0,25 | 0,75 | (1,5)4 | 0,3 | 0,80 | (1,6)4 | 0,6 | 1,10 | (2,2)4 | |
Auditorium | I | 0,75 | 4,67 | 3,5 | 0,5 | 5,17 | (3,9)4 | 1 | 5,67 | 4,3 | 2 | 6,67 | 5,0 |
II | 0,75 | 3,33 | 2,5 | 0,35 | 3,68 | (2,8)4 | 0,7 | 4,03 | (3,0)4 | 1,4 | 4,73 | (3,6)4 | |
III | 0,75 | 2,00 | 1,5 | 0,3 | 2,30 | (1,7)4 | 0,4 | 2,40 | (1,8)4 | 0,8 | 2,80 | (2,1)4 | |
IV | 0,75 | 1,33 | 1 | 0,25 | 1,58 | (1,2)4 | 0,3 | 1,63 | (1,2)4 | 0,6 | 1,93 | (1,5)4 |
The ventilation rate required to dilute a pollutant shall be calculated
by this equation:
Eq (2)
Where:
Qh =the
ventilation rate required for dilution, in litre per second;
Gh =the
pollution load of a pollutant, in micrograms per second;
Ch,i =the guideline
value of a pollutant, see Annex B6 , in micrograms per m³;
Ch,o =the
supply concentration of pollutants at the air intake, in micrograms per m³;
ev =the ventilation effectiveness
NOTE. Ch,i and Ch,o may also be expressed in
ppm (vol/vol). In this case the pollution load Gh has to be expressed in l/s.
To calculate the design ventilation air flow rate from
Eq. (2), the most critical or relevant pollutant (or groups of pollutant) shall
be identified and the pollution load in the space shall be estimated. When this
method is used it is required that CO2 representing the pollutant emission from people (bio effluents) shall be
used as one of the gases. Values depending on the category of indoor air are
defined for CO2 in Annex
B2 of the standard. Threshold values, based on WHO, for other sources are
listed in Annex B6. Emission rates and outdoor concentrations for the gases
considered shall be defined based on material testing or certification (see
Annex B3 of the standard) and local ambient air quality values.
This is a method to determine certain pre-defined
minimum ventilation air flow rate estimated to meet requirement for both
perceived air quality and health in the occupied zone.
The pre-defined ventilation air flow rates shall be
expressed by one or more of the following parameters:
·
total design ventilation for people and
building components (qtot);
·
design ventilation per unit floor area (qm²); design ventilation per
person (qp);
·
design air change rates (ach); design
opening areas (Atot).
Default values are presented in Annex B2 of the
standard.
Pre-defined ventilation air flow rates can be given on
national level based on one or more of the following criteria: total air change
rate for the dwelling, supply air flows for specific rooms, exhaust air flows
from specific rooms. In Annex B2 of the standard the default values for the
three criteria is shown (see Table 7). It is assumed that air is supplied in
living rooms and extracted from wet rooms. Both the total air flow rate for the
entire dwelling and the exhaust air flow rate from wet rooms shall be
calculated. The higher of the two shall be used. In the technical report
several examples on default ventilation rates in residential buildings are
presented.
The standard is also describing concepts for natural
ventilated building, where the criteria based on CO2 could be used. In annex B2 a methodology for defining default design
opening areas for natural ventilation systems in dwelling is presented (see Table 8). The opening areas must be provided as supply/extract grilles, stack
ducts, window grilles, or similar system.
Table 7. Default criteria based on pre-defined ventilation air flow rates: Total ventilation (1), Supply air flow (2) and (3) supplemented by exhaust air flow.
Category | Total ventilation including air infiltration | Supply air flow per. person | Supply air flow based on perceived IAQ for adapted persons | Supply air flow for bedrooms | Exhaust air flow Peak or boost flow for high demand l/s | ||||
(1) | (2) | (3) | (4) | ||||||
l/s per m² | ach | l/s per person | qp l/s per person | qB l/s per m² | l/s per person | Kitchen (3a) | Bath-rooms (3b) | Toilets (3c) | |
I | 0,49 | 0,7 | 10 | 3,5 | 0,25 | 10 | 28 | 20 | 14 |
II | 0,42 | 0,6 | 7 | 2,5 | 0,15 | 8 | 20 | 15 | 10 |
III | 0,35 | 0,5 | 4 | 1,5 | 0,1 | 4 | 14 | 10 | 7 |
IV* | 0,23 | 0,4 | 2,5* | 10 | 6 | 4 | |||
Column 3 and 4: The ventilation air flow rates must be available when the rooms are occupied. The design can take into account that not all bedrooms are occupied at the same time, e.g. during daytime. The number of persons in bedroom depends on the size according to design criteria and building regulations. * Category IV is intended for the evaluation of IAQ in existing buildings where the space for installations are limited. Supply air flow for method 3 is based on eq (1). |
Table 8. Default design opening areas for dwellings. Values for bedrooms and living rooms may be given per m² floor area or as fixed values per room.
Extract Kitchen, bathrooms and toilets (cm²) | Supply Bedrooms and living rooms (cm²) | |
Default design opening area | 100 per room | 60 per room |
The standard is also setting up some requirements regarding the use of filtration and air cleaning. The influence of position of outdoor air intakes, filtration and air cleaning shall be considered according to prEN 16798-3 (revised EN13779) and the draft technical report TR 16798-2. If filtration and air cleaning is used the following points shall be considered:
· Reducing the amount of airborne pollutants (pollens, molds, spores, particles, dust) from the outdoor air intake by circulating the air through a filter.
· Circulating secondary air through a filter or other air cleaning technology to reduce the amount of pollutants in the air
· Reduce the concentration of odours and gaseous contaminants by circulating the secondary air or recirculating the return air (gas phase air cleaning)
Design guidelines on air cleaning and filtration are given in prEN16798-3 and ISO DIS 16814. How to partially substitute outside air by air cleaning is described in draft TR16798-2.
To enable people to perform visual tasks efficiently and accurately, appropriate lighting shall be provided. The degree of visibility and comfort is wide ranging governed by activity type and duration of required lighting criteria for work places as specified in EN12464-1 and for sports lighting in EN 12193. For some visual tasks in buildings and spaces the required lighting default criteria are presented in Annex B4 to the standard. The design illuminance levels shall be obtained by means of daylight, electric light or a combination of both. For reasons of comfort and energy in most cases the use of daylight is preferred. This depends on factors like standard occupancy hours, autonomy (portion of occupancy time during which there is enough daylight), location of the building (latitude), amount of daylight hours during summer and winter, etcetera.
A new thing is the inclusion of a table with default values for daylighting as shown in Table 9.
Table 9. Daylight availability classification as a function of the daylight factor DCa,j of the raw building envelop opening and DSNA EN15193.
Vertical Facades Daylight factor DCa,j | Roof lights Daylight factor DSNA | Classification of
daylight availability |
DCa,j ≥ 6% | 7% < DSNAa | Strong |
6% > DCa,j ≥ 4% | 7% > DSNA ≥ 4% | Medium |
4% > DCa,j ≥ 2% | 4% > DSNA ≥ 2% | Low |
DCa,j < 2% | 2% > DSNA ≥ 0% | None |
a Values of DSNA > 10% should be avoided due to danger of overheating |
Guidance for evaluation of noise at the design stage is found in EN 12354-part 5. The noise from building service systems may disturb the occupants and prevent the intended use of the space or building. The noise in a space shall be evaluated using A-weighted equivalent sound pressure level, normalized with respect to reverberation time to take into account the sound absorption of the room. Default values for three categories are then listed in the informative annex to the standard.
For energy calculations the result will depend very much on how the occupant schedules will be assumed. In this way it may be very difficult to compare same type of building if different occupant schedules have been used. Therefore the standard prEN16798-1 list several recommended occupant schedules for different type of spaces like residential, offices, schools, restaurant, meeting room, department store, etc. The schedules include criteria for the indoor environment based on the default values, time and level of occupancy and internal loads from other equipment. The criteria used for room temperatures, ventilation, and humidity are based on Category II and very low-polluted building. The internal loads from appliances are based on recent values from a study by REHVA.
The following sections from the existing standard have all been moved to the technical report with only a few changes.
· Evaluation of the indoor environment and long term indicators
· Inspections and measurement of the indoor environment in existing buildings
· Classification and certification of the indoor environment.
With this revision a more concise standard will be available together with guidance in a technical report.
All criteria listed given as categories in an informative annex are default values. Individual countries may select other values or one category following the concept of the way the default values are expressed.
The inclusion of default occupant schedules will make the calculated energy performance more comparative between buildings.
[1] CEN/TC156/WG19/N84: prEN16798-1 Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics.
[2] CEN/TC156/WG19/N89: draft prCEN/TR 16798-2 WD :Guideline for using indoor environmental input parameters for the design and assessment of energy performance of buildings.
[3] prEN16798-3: Energy performance of buildings - Part 3: Ventilation for non-residential buildings - Performance requirements for ventilation and room-conditioning systems; see also article Claus Händel.
Follow us on social media accounts to stay up to date with REHVA actualities
0