Keywords: Bedroom Ventilation; Indoor Air Quality; Sleep Quality; Carbon Dioxide; Standards; Engineering Solutions

Xiaojun Fan¹
Mizuho Akimoto²
Lan Li³
Pawel Wargocki⁴*
1 Berkeley Education Alliance for Research in Singapore (BEARS), Singapore. xiaojun.fan@bears-berkeley.sg
2 Department of Architecture, School of Creative Science and Engineering, Waseda University, Japan mizuho.akimoto@aoni.waseda.jp
3 Department of Architecture, School of Design, Shanghai Jiao Tong University, China. lanli2006@sjtu.edu.cn
4* International Centre for Indoor Environment and Energy (ICIEE), Department of Environmental and Resource Engineering (DTU Sustain), Technical University of Denmark (DTU), Denmark. pawar@dtu.dk (*corresponding author); REHVA Fellow

 

Despite sleeping daily, we seldom speak about bedroom environmental quality, usually focusing on bedding. Recent studies consistently show that inadequate bedroom ventilation can impair sleep, suggesting that current ventilation requirements may need revision. This article discusses evidence linking bedroom ventilation to sleep quality and advocates updating residential standards to safeguard healthy sleep.

Why bedroom ventilation matters: Sleep is essential to human health, neurocognitive performance, and well-being. While sleep can be affected by many factors, including sleep hygiene, health conditions, and stress, it has recently been shown that bedroom ventilation can also play a critical role in supporting sleep health. Yet, bedroom ventilation generally remains understudied and inadequately addressed in standards and guidelines compared with what is prescribed for other occupied environments in commercial and residential buildings.

Bedrooms constitute a unique indoor environment characterized by long, stationary occupancy (often as long as 7 to 9 hours), passive and unconscious exposure to pollutants generated indoors and outdoors, and generally low outdoor air change rates (Sekhar et al., 2020). During sleep, occupants cannot actively regulate bedroom ventilation unless they wake up. The majority of current ventilation standards, building guidelines, and indoor air quality codes specify whole-dwelling ventilation requirements but basically do not provide line-item, room-specific ventilation requirements for bedrooms (Akimoto et al., 2025); some of these requirements are presented in Table 1. The problem is amplified by the fact that air quality is invisible and often imperceptible, leaving occupants unaware of potential risks. Furthermore, inadequate ventilation is particularly relevant to residential buildings without mechanical ventilation. In such residences, the occupants may routinely sleep with bedroom doors and windows closed, primarily to create private, undisturbed environments with no concern about ventilation. Windows and doors are also often closed to reduce noise and prevent heat loss. This will restrict the infiltration of outdoor air into the already airtight spaces and may subsequently affect sleep quality.

Table 1. Summary of selected ventilation standards and guidelines for residential buildings in European countries.

Countries/Regions

Reference

Notes

Requirements

L/s or m³/h

h-1

CO₂ (ppm)

Austria

ÖNORM H 6038 (2020)

Bedroom

25 m³/h per person

-

Approx. 1,000 (design target)

The Netherlands

Besluit bouwwerken leefomgeving

Sleeping room / habitable room

0.7 L/s per m², min. 7 L/s

-

-

 

Programma van Eisen Gezonde Woningen (2022)

Voluntary guideline, Classes A/B/C

60/40/25 m³/h per person

-

+300/+450/+750 *

Denmark

BR18 (2018)

-

0.3 L/s per m²

-

-

 

DS 447 (2021)

Cat II as in EN16798

0.42 L/s per m²

-

-

Finland

FINVAC (2019)

New buildings

6 L/s per person

-

-

 

 

New buildings

0.35 L/s per m²

-

-

 

 

New buildings

12 L/s for the largest or only bedroom; 8 L/s for other bedrooms

-

-

 

 

Minimum for existing buildings

4 L/s per person

-

-

 

 

Recommendation for existing buildings

6 L/s per person

-

-

France

Arrêté du 24 mars 1982

General dwelling ventilation; total minimum extract depending on the number of principal rooms

35–135 m³/h

-

-

 

ANSES (2013)

Recommendation, not a residential bedroom regulation

-

-

1,000

Norway

TEK (2017)

Occupied

1.2 m³/h per m²

-

-

 

 

Unoccupied

0.7 m³/h per m²

-

-

 

 

Bedroom

26 m³/h per planned bed

-

-

Sweden

FoHMFS 2014:18

Occupied

0.35 L/s per m², 4 L/s per person

0.5

-

 

 

Unoccupied

0.1 L/s per m²

-

-

Switzerland

SIA 180

Sleeping person, CO₂-based estimate

20 m³/h per person

-

1,000

 

 

Sleeping person, odour-based estimate

25 m³/h per person

-

-

 

SIA 2024

Housing/hotel rooms, nighttime value

15 m³/h per person

-

-

 

 

Housing/hotel rooms, daytime value

29 m³/h per person

-

-

Europe

EN 16798-1 (2019)

Bedroom - Cat I

0.49 L/s per m², 10 L/s per person

-

+380*

 

 

Bedroom - Cat II

0.42 L/s per m², 7 L/s per person

-

+550*

 

 

Bedroom - Cat III & IV

0.35 L/s per m², 4 L/s per person

-

+950*

*Above background CO₂ concentration

 

How to measure sleep: The gold-standard method for measuring sleep is polysomnography (PSG), which uses electroencephalography (EEG), electrooculography (EOG), and electromyography (EMG) to quantify sleep quality. The measurements are typically performed in laboratories due to the high cost and complexity involved; the wide-field application of PSG is impractical. With advancements in sensing technologies, many wearables that use actigraphy are available on the market, providing non-invasive sleep-quality measurements; however, they are not as accurate as PSG, particularly for assessing sleep architecture. Standardized questionnaires, such as the Pittsburgh Sleep Quality Index (PSQI) and Groningen Sleep Quality Scale (GSQS), can also be used to assess subjective sleep quality; they have been developed by sleep researchers and are considered standard tools (Buysse, 2014).

How to characterize bedroom ventilation: Metabolically generated CO₂ by sleeping occupants is typically measured and used as a proxy for bedroom ventilation and air quality. The advantage is that the generation rate is relatively stable, and bedroom conditions also generally remain fairly stable during sleep. Knowing the human metabolic CO₂ generation rate allows estimation of bedroom ventilation rates using a mass-balance model, subject to specific assumptions about air distribution and mixing. Still, measuring CO₂ alone will not be sufficient to demonstrate the presence of other pollutants in bedrooms, especially those that infiltrate from outdoors, such as particulate matter (PM).

Figure 1. Sleep quality measured objectively as a function of the measured CO₂ concentration; filled markers indicate the levels at which negative effects on sleep quality were observed. Note that the CO₂ concentrations here are the absolute levels. Adapted from (Akimoto et al., 2025), where details can be found.

Bedroom ventilation recommendations: The recent ASHRAE 1837-RP project, “The effects of ventilation in sleeping environments,” conducted numerous cross-sectional, field intervention, and controlled laboratory studies to investigate the effects of bedroom ventilation on sleep.  Based on their results, supplemented by other studies as summarised in Figure 1, the requirements for bedroom ventilation rates were proposed (Akimoto et al., 2025).

The results presented in Figure 1 can be interpreted as follows: maintaining CO₂ concentrations in bedrooms below 1,000 ppm would minimize sleep disturbance, but it is preferable to keep them below 800 ppm. CO₂ concentration must be below 1,000 ppm because Kang et al. (2024) showed that sleep was disturbed at 1,000 ppm (Kang et al., 2024). 800 ppm is preferred to provide a margin of protection, given that no effects were generally observed below this level. Also, it aligns relatively well with the 19th-century proposal, which recommended setting bedroom ventilation rates to keep CO₂ below 700 ppm (Pettenkofer, 1858).

Figure 2. Estimated minimum outdoor air supply rate per person during sleep as a function of indoor CO₂ concentration at different CO₂ emission rates. Data for children from Klausen et al. (2023). Data for adults from Fan et al. (2021) and Xiang et al. (2026). Data for the elderly (seniors) from Yan et al. (2023).

Recent studies have reported average CO₂ generation rates during sleep of 9-11 L/h per person (Fan et al., 2021; Klausen et al., 2023; Yan et al., 2023; Xiang et al., 2026), as shown in Figure 2. Using these emission rates, the minimum outdoor air change rate was estimated to be >5.3 L/s per person, which would keep CO₂ levels <1,000 ppm, but preferably it should be ≥8 L/s per person, which would keep CO₂ levels ≤800 ppm and consequently ensure that sleep is not disturbed (Figure 2). It should be noted that these rates may need to be higher when emissions from other indoor sources besides humans, such as building materials, are elevated. In many countries, achieving these targets will require outdoor air supply rates in bedrooms to be higher than those in current residential codes, as illustrated in the examples below (Tables 1 and 2). However, as also shown in the examples below (Tables 1 and 2), meeting the above recommendation does not necessarily mean increasing total whole-dwelling ventilation rates; it may require optimizing the efficiency of ventilation allocation to safeguard sleep.

Role of CO₂: Whether pure CO₂ affects sleep is inadequately explored. Only two studies examined this question, and the findings remain inconclusive. More effort is indeed needed to clarify this relationship, especially since ambient CO₂ levels are increasing and because indoor CO₂ levels are also used as inputs for demand-controlled ventilation (DCV) systems. Today, CO₂ is primarily measured to indicate exposure to a complex mixture of human bioeffluents and other indoor pollutants caused by poor ventilation. Unless evidence disproves this, it should be used as such.

Effectiveness of airing behaviours: While it may not be a common practice, airing by opening windows or doors can be considered the primary means of increasing ventilation in bedrooms. However, as shown in the example below (Table 2), its effectiveness in improving bedroom ventilation could be limited; this is also confirmed in studies reviewed by Sekhar et al. (2020). Some studies have shown that opening exterior windows/doors can reliably increase air changes with outdoor air, thus benefiting sleep (Fan et al., 2022); however, in areas with high outdoor air pollution, the positive impacts of increased ventilation could be offset by the penetration of outdoor air pollutants (Yan et al., 2024), as can occur when opening interior doors (Fan et al., 2022), where pollutants from adjacent indoor spaces might be transported into bedrooms without providing true dilution, such as cooking-related pollutants originating in kitchens. So, the quality of the outdoor air used for airing is also important.

Engineering solutions for HVAC practice: To reconcile the competing demands of high outdoor air supply, energy efficiency and outdoor pollution filtration, HVAC systems for sleeping environments will require a dedicated technical approach. Deploying low-noise ventilation with energy recovery and real-time CO₂-based DCV systems enables maintaining CO₂ levels below the target while continuously minimizing energy consumption. Such solutions should be considered the standard for new dwellings and when retrofitting the existing ones. Yet they may not be feasible in many existing bedrooms. Noise from the ventilation system is critical for sleep and should be minimized (Lan et al., 2021). For existing bedrooms, it may be considered to develop personalized ventilation systems that deliver conditioned, filtered outdoor air directly to the breathing zone of sleeping persons, as such systems are effective and affordable (Lan et al., 2013). However, the design and installation could be challenging. Complementary high-efficiency filtration, either stand-alone or in-duct HEPA, could be another option in the case of high PM pollution (e.g., wildfire events) (Lamport et al., 2023). Other solutions, in the case the ventilation system is in place, may include redirecting the air first to bedrooms during the night by rebalancing the systems or supplying all ventilation air only through bedrooms in the form of cascade ventilation; as shown in the examples below (Table 2), such a solution may leave the total prescribed ventilation in the standards for residential environments unchanged but will secure that it is used more effectively for sleep.

Illustrative examples: Table 2 presents a few examples illustrating how the recommended bedroom ventilation target (≥ 8 L/s per person, CO₂ ≤ 800 ppm) can be operationalized and achieved.

Table 2. Examples of how to achieve recommended ventilation targets for existing and newly built buildings.

Example 1

Consider a typical 2+1-person European dwelling (85 m², height of 2.5 m) comprising a main bedroom for 2 adults (15 m²) and a child’s bedroom (10 m²). Under the Danish building code (BR 18), according to Table 1, an area-specific ventilation rate of 0.3 L/s per m² yields only 2.3 L/s per person in the main bedroom and 1.5 L/s per person in the child’s bedroom, substantially lower than the recommended 8 L/s per person. However, the total dwelling ventilation rate is 25.5 L/s. Directing this air through the bedrooms via cascade ventilation or after nocturnal airflow rebalancing delivers 8.5 L/s per person in bedrooms, meeting the target under nominal occupancy. If evaluated instead under EN 16798-1 Category II (0.42 L/s per m²), the total dwelling air supply rate increases to 35.7 L/s. Supplying it through bedrooms or after nocturnal airflow rebalancing provides 11.9 L/s per person.

Example 2

Consider a 2+2-person European dwelling (110 m², height of 2.5 m) with a 15 m² bedroom (2 adults) and two 10 m² children’s bedrooms. Applying the EUROVEN whole-dwelling recommendation of 0.5 h-1 (Wargocki et al., 2002) provides a total outdoor air supply rate of 9.5 L/s per person. If the supply is through bedrooms, the rates recommended in the present article can be met. However, applying 0.5 h-1 directly to bedrooms will yield only 5.2 L/s per person in the main bedroom and 1.7 L/s per person in the children’s bedroom, which is significantly lower than the recommended levels, despite meeting the overall EUROVEN guideline value.

Example 3

EN 16798-1 specifies requirements for indoor CO₂ concentrations above outdoor levels across four categories: 380 ppm (Category I), 550 ppm (Category II), 950 ppm (Category III) and above 950 ppm (Category IV). Assuming a typical nocturnal outdoor baseline of 430 ppm, only Category I will (nearly) meet the recommended 800 ppm level, ensuring that sleep disturbance can be avoided. Integrating thus real-time CO₂-based DCV into ventilation systems, using a Category I CO₂ level of 380 ppm above the outdoors, can be considered a good engineering solution for bedrooms.

Example 4

Assuming the dwelling in Example 1 is naturally ventilated and using the empirical field data collected in Danish bedrooms, sleeping with closed bedroom windows and doors yields a median air change rate of 0.32 h-1 (infiltration only), corresponding to 1.7 L/s per person in the main bedroom and 2.2 L/s per person in the child’s bedroom. Opening windows can increase the median air change rate to 0.82 h-¹, which could increase the ventilation rate to 4.3 L/s per person in the main bedroom and to 5.7 L/s per person in the child’s bedroom, still below the recommended 8 L/s per person. Although under favourable conditions, these rates can be higher, natural ventilation depends on many factors, including weather variations, and is often constrained by cold drafts, summer overheating, traffic noise, privacy concerns, and the infiltration of outdoor pollutants.

 

The examples shown in Table 2 demonstrate that achieving the recommended bedroom ventilation rates for healthy sleep does not necessarily require increasing whole-dwelling ventilation rates. In buildings with mechanical ventilation, simple rebalancing of airflow distribution or the implementation of CO₂-based DCV would be sufficient. For new buildings, supplying outdoor air primarily through bedrooms, especially during sleeping periods, by using cascade ventilation or intelligent control strategies might be considered a standard in dwellings. In naturally ventilated buildings, window openings may substantially improve bedroom ventilation. Still, the resulting rates are variable and cannot be guaranteed due to weather dependence, occupant behaviour, outdoor pollutant levels, acoustic noise, and thermal comfort boundaries.

In summary, the scientific evidence suggests that the engineering challenge is not to increase total overall ventilation, but to provide it where and when it is needed. Bedroom-focused ventilation strategies can deliver the specific airflow required for healthy sleep without escalating total building ventilation energy demand.

Moving forward: To move bedroom IAQ management from basic documentation to standard engineering execution, the building industry and HVAC researchers must focus on three core technical challenges: (1) revise standards for bedroom-specific ventilation requirements for healthy rest; (2) focus on climate-resilient design to combine low-energy mechanical cooling with efficient ventilation during hot nights or wildfire smoke events in a warming world; (3) develop closed-loop responsive control that integrates low-cost sensors with advanced sleep trackers to enable next-generation smart home HVAC controllers. Challenge 1 is particularly urgent as it will impact the design of new buildings, renovations and ventilation solutions.

An important issue, of course, is overheating. The evidence shows considerable effects of elevated temperatures on sleep quality. This issue will be described in a separate article.

References

Akimoto, M. et al. (2025) “New research on bedroom ventilation and sleep quality suggests that building standards should be revisited (ASHRAE 1837-RP),” Science and Technology for the Built Environment, 31(8), pp. 905–916. Available at: https://doi.org/10.1080/23744731.2025.2531317

Buysse, D.J. (2014) “Sleep Health: Can We Define It? Does It Matter?,” Sleep, 37(1), pp. 9–17. Available at: https://doi.org/10.5665/sleep.3298

Fan, X. et al.(2021) “Emission rate of carbon dioxide while sleeping,” Indoor Air, 31(6), pp. 2142–2157. Available at: https://doi.org/10.1111/ina.12911

Fan, X. et al.(2022) “A field intervention study of the effects of window and door opening on bedroom IAQ, sleep quality, and next-day cognitive performance,” Building and Environment, 225(July), p. 109630. Available at: https://doi.org/10.1016/j.buildenv.2022.109630

Kang, M. et al.(2024) “Ventilation causing an average CO₂ concentration of 1,000 ppm negatively affects sleep: A field-lab study on healthy young people,” Building and Environment, 249, p. 111118. Available at: https://doi.org/10.1016/j.buildenv.2023.111118

Klausen, F.B. et al. (2023) “The effect of air quality on sleep quality and cognitive performance in school children aged 10-12 years: a double-blinded, placebo-controlled, crossover trial,” International Journal of Occupational Medicine and Environmental Health, In press(2), pp. 1–15. Available at: https://doi.org/10.13075/ijomeh.1896.02032

Lamport, D.J. et al.(2023) “Can air purification improve sleep quality? A 2‐week randomised‐controlled crossover pilot study in healthy adults,” Journal of Sleep Research, 32(3), pp. 1–9. Available at: https://doi.org/10.1111/jsr.13782

Lan, L. et al.(2013) “Pilot study on the application of bedside personalized ventilation to sleeping people,” Building and Environment, 67, pp. 160–166. Available at: https://doi.org/10.1016/j.buildenv.2013.05.018

Lan, L. et al.(2021) “Pilot study of the effects of ventilation and ventilation noise on sleep quality in the young and elderly,” Indoor Air, 31(6), pp. 2226–2238. Available at: https://doi.org/10.1111/ina.12861

Pettenkofer, M. (1858) Über den Luftwechsel in Wohngebäuden.

Sekhar, C. et al. (2020) “Bedroom ventilation: Review of existing evidence and current standards,” Building and Environment, 184(August), p. 107229. Available at: https://doi.org/10.1016/j.buildenv.2020.107229

Wargocki, P. et al.(2002) “Ventilation and health in non-industrial indoor environments: report from a European Multidisciplinary Scientific Consensus Meeting (EUROVEN),” Indoor Air, 12(2), pp. 113–128. Available at: https://doi.org/10.1034/j.1600-0668.2002.01145.x

Xiang, D. et al.(2026) “Carbon dioxide emission rates during sleep under different bedroom ventilation conditions,” Energy and Built Environment [Preprint]. Available at: https://doi.org/10.1016/j.enbenv.2026.05.007

Yan, Y. et al.(2023) “Emission rate of carbon dioxide by older adults while sleeping,” Building and Environment.

Yan, Y. et al. (2024) “Does window/door opening behaviour during summer affect the bedroom environment and sleep quality in a high-density sub-tropical city,” Building and Environment, 247, p. 111024. Available at: https://doi.org/10.1016/j.buildenv.2023.111024

Xiaojun Fan, Mizuho Akimoto, Lan Li, Pawel WargockiPages 13 - 18