Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
ArtūrsBrahmanisLafiventsLTDRiga, Latvia | EgīlsDzelzītisInstitute of HeatGas and Water technologyFaculty of Civil EngineeringRiga Technical University | ArtursLešinskisInstitute of HeatGas and Water technologyFaculty of Civil EngineeringRiga Technical University |
A plenty
of studies are devoted to estimation methods of seasonal energy consumption of
cooling equipment. Several computing instrument give the ability to calculate or
simulate chiller’s electricity consumption at
variable conditions. Using European Seasonal energy efficiency ratio (ESEER),
provided by equipment suppliers, engineers and project developers can make fast
and rather rough calculations on annual cost in order to determine the economic
feasibility for choosing the particular type of cooling equipment. And the
question is, how precise those calculations could be
for temperate and northern climates?
As a
part of the research on evaporative cooling appliance in temperate climate of
Baltic States, conducted in Latvia in 2011–2014 [1], an analytical research
made in recently restored 19th century historical building, The Art Museum Riga
Bourse.
Figure
1. The Riga Bourse building in 19th century and nowadays after
reconstruction. |
Restoration
of old buildings is a complex construction process, in which engineers and
architects need to solve many atypical tasks concerning not only the structural
stability of the building, but also the recovery of cultural—historical
appearance of the building. Necessity of harmonious integration of modern HVAC
devices in the historical interior also enforces limits to the equipment
selection. The successful solving these and construction tasks results in a
balanced and sustainable restoration of the building.
The
analytical research overtakes the results of water cooling system operation for
one year cooling period. The data of electricity and water consumption, chiller
operation modes and cooling system temperature data were logged with one-minute
interval. The duration of analysis period was chosen, based on the building
cooling demand. The data obtained were converted to average hour values after
the analysis of errors. The calculated cooling output depending on the outdoor air
(OA) temperature is displayed on Figure 2 below.
Figure 2.The calculated cooling output depending on the
outdoor air (OA) temperature.
The
information on equipment efficiency that is necessary for seasonal energy
consumption calculations is limited. Usually, energy efficiency ratio and the
seasonal efficiency of the device are available. The industry has implemented
ESEER (European Seasonal Efficiency Ratio), recently published regulations or
those in the process of being published talk about seasonal coefficient of
performance (SCOP) in heating mode, and its equivalents SEER and SEPR in
cooling mode. Seasonal energy efficiency, in accordance with EN14511:3 – 2013
and [2] is calculated according to the Equation explained below:
ESEER = A ´ EERA + B ´ EERB + C ´ EERC + D ´ EERD, (1)
Where
EER = ratio of the total cooling capacity to the effective power input of the
unit, Watt/Watt.
Table 1.ESEER components description.
Conditions | Load
ratio, % | Weighing
coefficient | Air
temperature at condenser inlet (air cooled chillers) | Water
temperature at condenser inlet (water cooled chillers) |
A | 100 | 0.03 | 35 | 30 |
B | 75 | 0.33 | 30 | 26 |
C | 50 | 0.41 | 25 | 22 |
D | 25 | 0.23 | 20 | 18 |
In
authors’ opinion ESEER introduction to the market was a great achievement
within the equipment assessment principles, which is likely to reflect
accurately the effectiveness of Central Europe or the Mediterranean part of
Europe. On the other hand, when in Latvian climate conditions the building
cooling load is traditionally calculated using an outdoor air temperature of
+27°C (Riga), ESEER test parameters are quite distant
from the real situation. Practice shows that the cooling demand in many objects
occurs at much lower outdoor temperatures such as +15°C or even +10°C. Such
objects may include: office premises with large amount of office equipment,
facilities with high human density, retail spaces with great light intensity,
and rooms with large windows surfaces and no shadows. The location of
ventilation diffusers does not always provide cooling in the most comfortable
way such as displacements ventilation, for people in the premises. In those
cases the air cooling is carried out with chillers and the room terminal units
like chilled beams or fan-coils. Sonderegger (1998),
based on a number of energy efficiency project analysis pointed to a large
inaccuracies in heating / cooling system energy savings estimates, if they are
performed only based on the weather data [3].
The
values of cooling energy produced at a certain temperature ranges with a step
of 2.0°C are presented in Figure 3. The vast majority or about
67% of cooling energy during the cooling period was produced when the outside
temperature was in the range from 10 to 20°C. According to the generally
accepted practice, the cooling is required when ϑOA is higher than 18–19°C, (which is also
generally accepted base temperature for cooling degree-hour calculation).
Within the particular building non-weather dependent cooling accounts for more
than half of the total annual cooling energy. This characterizes the objects
with high heat gains, and / or high microclimate requirements.
Figure 3. Cooling energy produced at outdoor air temperature diapasons.
ESEER
impact factors at the same outdoor (condenser inlet) temperature distribution
for comparison are shown in Figure 4 below.
Figure 4.ESEER impact factors at the same outdoor (condenser
inlet) temperature distribution for comparison.
The
acquired data in art museum showed cooling system showed significant difference
on cooling energy produced on site and ESEER weighing methodology. Due to that,
the more precise coefficient distribution method is offered. The calculation
principle can be expressed as follows:
(1)
Where:
Qel.seas. = electricity consumption during cooling season, kWh
= outdoor air temperature interval
Qc.nom. = nominal cooling load of the device in standard conditions, kW
EER = energy efficiency ratio at a given interval
CL = cooling load at a given temperature interval, % or part of 1, from nominal device capacity
GS = the number of cooling degree hours at a given temperature interval, h
Qel.st. = standby electricity consumption, kWh
Using
the proportional distribution method, seasonal energy consumption calculations
are performed for combined compression cycle - evaporative chiller (KKCD). For
comparison, one calculation is done for close to the ESEER temperature / load
intervals. Cooling degree hours (CDH) was taken, using Latvian Typical
Meteorological year data in temperature diapason ±2°C. We can see that it
overtakes outdoor air temperatures from 18 to 37°C and the total electric
energy consumed is 24 128 kWh for the chiller with maximum cooling
capacity 320 kW (Table 2):
Table 2.Seasonal energy calculation using ESEER values and summarized
CDH.
Condition | ϑOA interval, °C | CDH | Load
ratio, % | KKCD
EER | Yearly
electrical energy consumption, kWh |
A | 33 – 37 | 2 | 100% | 3,6 | 178 |
B | 28 – 32 | 24 | 75% | 4,2 | 1 371 |
C | 23 – 27 | 288 | 50% | 5,1 | 9 035 |
D | 18 – 22 | 965 | 25% | 5,7 | 13 544 |
Total | 24 128 |
However,
the actual yearly electricity consumption of the chiller, logged by electricity
meters is 62 000 kWh. Using the above mentioned formula (2),
proportional method calculation has been performed for 7 outdoor temperature /
load intervals. EER data which was out of ESEER conditions was executed from
laboratory experiments on the similar chiller. The portion of cooling energy at
ϑOA less than 10°C, which was produced at the investigated site during the
cooling season accounted for 5.9% of the total energy produced. This part of
the calculation is added to the calculation due to the equipment operating
efficiency drawbacks within this range (Table 3).
Table 3.
Seasonal energy calculation using 7 intervals with summarized CDH.
ϑ OA interval, °C | CDH | Load
ratio, % | KKCD
EER | Yearly
electrical energy consumption, kWh |
27 – 33 | 49 | 90% | 4,2 | 3 360 |
24 – 26 | 150 | 75% | 5,1 | 7 059 |
20 – 23 | 580 | 50% | 5,7 | 16 281 |
17 – 19 | 804 | 30% | 6,0 | 12 864 |
14 – 16 | 964 | 15% | 6,3 | 7 345 |
10 – 13 | 1 276 | 10% | 7,0 | 5 833 |
0 – 10 | 5,9%
of the overall kWh consumed | 3 112 | ||
Total | 55 853 |
The
results showed much higher precision when using 7 interval proportional methods
for the investigated building. It could be proposed to extend the ESEER part
load test methods to wider TOA and cooling load ranges. Surely, further
investigations on real cooling load should be made in different types of
buildings to increase the amount of trustable data. These factors could help to
increase the accuracy of economic and energy consumption calculations, taking
into consideration peculiarities of various object types and conditions of
northern climate.
[1] Brahmanis A.,
Indirect evaporative cooling in air conditioning systems. Doctoral Thesis, Riga
Technical University, Riga, 2014. – 119 p.
[2] Marinhas S., Eurovent chiller certification key stones and future
challenges. REHVA Journal – March 2013. – p. 31–33.
[3] Sonderegger R.
C., A Baseline Model for Utility Bill Analysis Using Both Weather and
Non-Weather Related Variables. ASHRAE Summer Meeting, Toronto, Canada, June
18-25, 1998. – 10 p.
[4] Zariņš M.
Latvian climate data processing for air-conditioning systems optimization.
Master Thesis. Latvian University of Agriculture, Jelgava,
2002. – 115 lpp.
[5] Stankevica G., Varavs V., Kreslins A. Trends in
Cooling Degree Days for Building Energy Estimation in Latvia. Construction
Science 14, 2013. p. 89–94.
Follow us on social media accounts to stay up to date with REHVA actualities
0