Key words: Air ionization, ultrafine particles, PM₁, hospitals, patient room, mixing ventilation
|
|
|
Simo Kilpeläinen | Minzhou Chen | Risto Kosonen |
Aalto University, School of Engineering, Department of Civil Engineering, Espoo, Finlandsimo.kilpelainen@aalto.fi | Aalto University, School of Engineering, Department of Civil Engineering, Espoo, Finland | Aalto University, School of Engineering, Department of Civil Engineering, Espoo, Finland |
Particulate matter (PM) is one of the most dangerous pollutant types in indoor air. Specifically, ultrafine particles (PM₁) may cause considerable health issues to space users as they can linger in the air for long periods of time [1] and travel deep into the lungs when they get into the respiratory tract [2]. One way to remove PM₁ particles from indoor air is to use an ionizer. Lee et al. [3] showed that an ionizer based on the corona discharge principle can effectively be used to control PM₁ and PM².5 concentration in indoor air if the ion density is large enough (105–106 ions/cm³). Kolarž et al. [4] noticed in their research that the ionizer is especially efficient for particles sized between 100 and 1,000 nm. Furthermore, it has been shown that an ionizer is also capable of deactivating bacteria and viruses [5,6]. In this study, an ionizer based on the corona discharge principle was installed into a laboratory test room that was furnished as a two-occupant hospital patient room (full mock-up of a two-occupant patient room at a Finnish university hospital). The objectives were to assess how well the ionizer can be used to control the PM₁ concentration in the room and to find out how the combined effect of the ionizer and ventilation can be maximized.
The measurements were performed at the test room of the Aalto University HVAC laboratory. The room is airtight, thermally insulated, and measures at 5.5 × 3.8 × 3.6 m (L × W × H). The back wall of the room has a simulation window consisting of four radiant panels (Itula Itugraf) which was used to simulate solar load.
A photo of the test room can be found in Figure 1. There was a curtain that acted as a vision blocker between the beds with a gap of 30 cm above and 20 cm below it. The door-side bed had a chair for the visitor next to it.
Mixing ventilation realized with a multi-nozzle diffuser (Halton JSC) in the ceiling at the center of the room was used for air distribution in all the measurements. The air was supplied at 40 ℓ/s (1.9 ℓ/s/m²). There were two exhaust locations: one (10 ℓ/s) at the ceiling level between the two beds, and another (30 ℓ/s) at two-meter height on the opposite side of the room simulating a toilet exhaust. The indoor air temperature was kept at 24 ±0.5°C and the total heat gain in the room was 390 W (18.5 W/m²).
The infected person was simulated with a thermal model which had a nozzle at the mouth connected to a coughing/breathing machine (CH Technologies). The machine was used in constant exhalation mode to release a test aerosol containing PM₁ particles (10% NaCl solution) produced with a Blaustein nebulizer. A breathing thermal manikin (PT Teknik) was used to model the exposed person. PM₁ concentration was measured from the breathing zone of the manikin 15 cm away from its nose with TSI P-Trak 8525 capable of detecting particles in the size range of 0.02 – 1 µm. A patient lying in the other bed was realized with another thermal model.
The ionizer (Figure 1) used in the measurements was a prototype device based on the corona discharge principle and produced negative ions. The device could be used to produce a cone-like ion stream where the local negative ion concentration varied between 20,000 – 500,000 ions/cm³. In this study, the ionizer was attached to an adjustable holder and installed so that the ion-generating tip of the device was approximately 90 cm from the exposed person’s nose and directed towards it at a 45-degree (vertical) angle.

Figure 1. Measurement arrangement with two patients lying on beds and a visitor seated next to one of the beds (left) and the ionizer attached to a holder (right).
Two different infection sources (lying patient, seated visitor) were considered in the study. As all the measurements were done both with the ionizer off and on, the total number of cases (Table 1) was four. The cases were measured with the exponential decay method. Test aerosol was released into the room until the concentration in the exposed person’s breathing zone rose high enough. After that, the aerosol supply was turned off and the concentration decay measured over time. These measurements were repeated three times both with and without the ionizer.
Table 1. Test cases.
Name | Infector | Ionizer state |
P-OFF | Patient | OFF |
P-ON | Patient | ON |
V-OFF | Visitor | OFF |
V-ON | Visitor | ON |
The results can be found in Figures 2 (infected patient) and 3 (infected visitor). As can be seen from the figures, the time for the concentration to settle to background level (~400 particles/cm³) is roughly twice as long when the visitor is the infector compared to when the patient is. Another observation is that the ionizer has a clear effect in reducing the concentration in both cases.
Figure 2. PM₁ concentration decay as a function of time
when the patient is infected.

Figure 3. PM₁ concentration decay as a function of time when the visitor is infected.
The PM₁ concentration half-lifes for both infector locations are shown in Figure 4. When the patient was the infector, the half-life could be reduced by about 2.3 minutes by using the ionizer. In the visitor case, the reduction was roughly 4.5 minutes. In percentages this amounted to a 25% reduction in both cases, showing that the ionizer was equally effective regardless of infector location.

Figure 4. PM₁ concentration half-lives for the infected patient (left) and infected visitor (right) cases.
In this study, the combined effect of the ventilation system and an ionizer on the PM₁ concentration in a hospital patient room setting was assessed. Two infector locations (lying patient, seated visitor) were investigated. The research was conducted as a laboratory measurement where 10% NaCl solution combined with air was used as test aerosol. Aerosol concentration was monitored from the breathing zone of a thermal manikin simulating an exposed person in the room with a particle counter. The results showed that the half-life of the PM₁ concentration was ~25 % lower with the ionizer than without it. These results were achieved by placing the ionizer tip 90 cm away from the exposed person’s nose and directing the device towards their face at a 45-degree vertical angle.
The study was funded by the Halton Foundation. The authors would also like to thank Mr. Petteri Kivivuori for the technical support with the experiments.
[1] Fierro M. 2000. Particulate Matter. Air Info Now, 1-11.
[2] Bae H., et al. 2022. Adverse effects of air pollution-derived fine particulate matter on cardiovascular homeostasis and disease. Trends Cardiovasc. Med, 32, 487–498.
[3] Lee UK., Yermakov M. and Grinshpun S. 2004. Removal of fine and ultrafine particles from indoor air environments by the unipolar ion emission. Atmos. Environ., 38, 4815-4823.
[4] Kolarž P., et al. 2023. Estimating aerosol particle removal in indoor air by ion-enhanced deposition. J. Aeros. Sci., 173, 106199.
[5] Fletcher L., et al. 2007. Bactericidal action of positive and negative ions in air. BMC Microbiol., 7, 32.
[6] Hagbom M., et al. 2015. Ionizing air affects influenza virus infectivity and prevents airborne transmission. Sci. Rep., 5, 11431.