Interview with Vladimir Zmrhal and Froukje van Dijken by Lada Hensen Centnerová
Vladimír Zmrhal is an associate professor in the Faculty of Mechanical Engineering at the Czech Technical University in Prague, where he heads the Department of Environmental Engineering. His professional specialism is ventilation and air conditioning systems, with a focus on the indoor environment of buildings. He is a member of the Czech Society for Environmental Engineering and serves as editor-in-chief of its VVI journal, which has been indexed in the Scopus database since 2014. He chairs the Technical Standardisation Committee for Ventilation Equipment and the Testing Committee for Building Environment Technology at the Czech Chamber of Authorised Engineers and Technicians (ČKAIT).
Vladimír Zmrhal is the author or co-author of over 250 professional publications, including journal articles, technical books, textbooks, conference papers, patent-protected works, industrial publications and implemented projects. He is a principal investigator on numerous research projects. He contributes to the development of national standards and codes of practice in the field of building ventilation. He wrote the document “Ventilation Concept” and the “Methodological Guidelines for the Design of School Ventilation”. In 2017, he wrote the book “School Ventilation in Context” (in czech), in which he analyses the state of school ventilation in the Czech Republic. https://fs.cvut.cz/school-ventilation-in-context

Froukje van Dijken is a healthy building specialist at bba binnenmilieu in the Netherlands. She holds a Master’s degree in Building Physics from Eindhoven University of Technology. With her more than 20 years of experience on practical research on the indoor environment in schools, she is one of the main experts in this field in the Netherlands. Froukje provided several hundreds of schools with advice on how to reduce the IEQ complaints and to improve the indoor environmental quality. She is also often asked by municipalities, school boards and public health agencies to advise them on a healthy indoor environment in schools. She is the main author of the Dutch guidelines for IEQ in schools (PvE Frisse Scholen) and author and co-author of many articles related to indoor environment. Two of them were also published in REHVA Journal.
VZ: As we all know, ventilation affects well-being, health and productivity, which are the main reasons why ventilation is important. All these aspects are particularly important in schools because children are more vulnerable to poor indoor environmental conditions than adults. Providing healthy indoor air for our children should not be viewed as an option or a luxury, but as a fundamental requirement of every school building.
FvD: I fully agree. The three key reasons are health, learning performance, and comfort or general well-being of children.
FvD: In the Netherlands, most school buildings constructed until the 1980s relied on natural ventilation through operable windows and ventilation shafts. In practice, however, windows were kept closed during cold or windy weather. Over time, building modifications often reduced ventilation performance.
From the late 1980s onwards, mechanical ventilation systems became more common. First, mechanical exhaust in combination with natural supply. Although these systems represented a step forward, ventilation rates were frequently insufficient due to several reasons: 1) Systems were inadequately designed, for example exhaust was provided only in corridor and toilets without sufficient transfer of air between classrooms and exhaust points. 2) A lack of maintenance. 3) Occupants (here teachers) continued to close air inlets and windows to avoid perceived draughts and heat losses.
VZ: There are many problems in the education sector, and ensuring proper ventilation in classrooms is often overlooked. In the past, the building envelope was relatively leaky, allowing at least a certain amount of natural air exchange. Moreover, children used to spend their breaks outside the classroom, for example in the schoolyard or walking in the hallway, allowing the air in the classroom to refresh before the next lesson started. Today, energy-efficiency measures have led to much more airtight buildings when most classrooms are equipped with airtight windows with limited ventilation possibilities. At the same time, children usually remain in the classroom during breaks, and the windows are kept closed for safety, noise or thermal comfort reasons. This could highlight a lack of awareness among those responsible, but also a financial issue, because a permanently functional ventilation system requires substantial investment. Since school buildings are typically owned and managed by municipalities or regional authorities, such projects often depend on dedicated public funding.
VZ: In the Czech Republic, many school buildings are of historic significance and are more than 100 years old, so renovating their ventilation systems is technically challenging and costly. While many buildings have been renovated, this has typically focused on façade insulation and window replacement rather than ventilation improvements. Thus, the vast majority of school buildings in the Czech Republic - I would estimate around 90% - are still ventilated naturally, with teachers responsible for managing ventilation during and between lessons (Figure 1).

Figure 1. Natural ventilation in practice.
In newly constructed school buildings, a central mechanical ventilation system with heat recovery is mostly used. These systems are usually equipped with variable air volume controllers (VAV) and CO₂ sensor located in each classroom. The outdoor airflow rate is then regulated based on occupancy and IAQ needs. Local ventilation units usually cause unwanted noise and are only used when a central system cannot be installed. However, many school operators underestimate the importance of regular maintenance, such as filter replacement and periodic system inspections. As a result, even well-designed systems may fail to deliver their intended performance over time.
FvD: After 2 000 balanced mechanical ventilation systems (mechanical supply and exhaust) with heat recovery have become increasingly common in Dutch schools. In renovations, mechanical systems are installed. Both central and local.
FvD: In the Netherlands, school buildings are typically designed in accordance with the PvE Frisse Scholen [1] (Fresh Schools Program of Requirements, Figure 2). This guideline covers not only indoor air quality and ventilation, but also energy performance, thermal comfort, lighting and acoustics.

Figure 2. PvE Frisse Scholen i.e. “Fresh Schools Program of Requirements”.
Similar to other EU IEQ frameworks, the program defines three performance levels: Class C (sufficient), Class B (good) and Class A (excellent). This allows school owners and designers to select an ambition level that matches their objectives and budget while ensuring a healthy learning environment.
A little history: At the beginning of 2000s we saw that saving energy seemed often more important in schools than a good IEQ, particularly ventilation. Finally, in 2007 we were asked by a governmental organization to develop guidelines for schools to address both energy efficiency and the quality of the indoor environment in schools. This initiative proved highly successful. Nowadays all schools in the Netherlands are built according to these guidelines.
VZ: In the Czech Republic, ventilation requirements for schools are defined in the legally binding document Ministry of Health’s Decree No. 160/2024 Coll. [2] which specifies a minimum outdoor airflow rate of 20 m³/h per student in classrooms and allows mechanical and also natural ventilation by opening windows. Given that a typical primary school classroom usually has a capacity of around 30 pupils, this corresponds to a required airflow rate of approximately 600 m³/h per classroom. This regulation also specifies exhaust airflow rates from sanitary facilities and other auxiliary rooms.
In addition to ventilation, the regulation addresses several other aspects of the indoor environment. The operative temperature in classrooms must not exceed 28 °C, the airflow velocity should be between 0.1 and 0.2 m/s, and the relative humidity of the indoor air should be between 30% and 65%.
However, there is also another legal regulation which says that the maximum average CO₂ concentration in occupied rooms, including classrooms, should not exceed 1 200 ppm during occupancy.
Unfortunately, I must note that, under our current conditions, the binding regulation is merely a ‘piece of paper’, and state administrative authorities lack the means to monitor or enforce these values.
FvD: In the Dutch Building code are specified requirements for ventilation per person.
For school buildings constructed since 2012, the required minimum ventilation rate is 8,5 dm³/s (30,6 m³/h) per person. This corresponds to a required airflow rate of approximately 950 m³/h per classroom.
For existing buildings, the minimum requirement is 3,44 dm³/s (12,4 m³/h) per person.
However, this doesn’t mean there is a big gap between buildings designed before and after 2012. Between 1995 and 2012 the minimum ventilation rate in new buildings was 3,5 dm³/m2 (which corresponds to approximately 6 dm³/s (21,6 m³/h) per person under typical classroom occupancy). For these buildings this minimum is still valid.
VZ: In the Czech Republic, neither continuous monitoring of indoor air quality nor Post Occupancy Evaluation is mandatory for school buildings. As a result, systematic feedback on the actual performance of school environments is limited. In most cases, once a building is completed, there is little follow-up to verify whether the intended indoor environmental conditions are being achieved in everyday operation (Figure 3).

Figure 3. Typical CO₂ concentration trends in naturally ventilated classroom.
FvD: In the Netherlands, CO₂ monitoring in classrooms has been mandatory since 2025. POE is not mandatory, although there are municipalities where a check of the design and the situation upon completion is mandatory. My experience is that POE can be extremely valuable.
FvD: The pandemic prompted the government to introduce subsidy programs aimed at improving ventilation in existing school buildings. These programs focused particularly on schools that did not meet the ventilation requirements for new buildings. As a result, ventilation received much greater attention from school boards, municipalities and policy-makers than it had before COVID-19. The fundamental requirements did not change.
VZ: Interestingly, the COVID-19 pandemic itself did not result in major changes to school ventilation regulations in CZ. The more significant regulatory changes came later, following the energy crisis triggered by the war in Ukraine and the resulting concerns about energy consumption in public buildings.
Before these changes, higher ventilation rates were required in schools, ranging from 20 to 30 m³/h per student in classrooms and up to 90 m³/h per student in gymnasiums, depending on the space and occupancy. The current regulation has simplified and reduced these requirements to 20 m³/h per student (Figure 4).

Figure 4. a) An example of a modern school. b) The classrooms are ventilated by local units located in the hallway. (Source: Líbeznice Elementary School; design: Projektil architekti)
FvD: One of the most important challenges is ensuring resilience to overheating.
This summer several European countries, including the Netherlands, experienced record temperatures. In our country, many schools shortened the school day because classrooms became too hot for effective learning.
Research has shown [3] that elevated temperatures lead to a decrease in school performance.
Ventilation can play an important role in mitigating overheating, but we need more to keep schools cool. We should start with passive measures like sun shading and ventilative cooling. We already have seen promising results from low energy solutions such as ceiling fans in schools. However, due to climate change and continuous rising of temperatures, mechanical cooling systems are no longer going to be a luxury in Dutch schools.
VZ: In the Czech Republic, one of the greatest challenges will be the renovation of existing school buildings. Many schools were constructed decades ago and were never designed to accommodate modern ventilation systems. Improving energy performance while maintaining healthy indoor air quality will often require the installation of mechanical ventilation with heat recovery. In practice, however, such upgrades can be technically challenging due to limited space for equipment and ductwork, as well as the need for structural modifications.
An equally important challenge is awareness and operation. Ventilation remains largely invisible when it works well, which means it often receives little attention from decision-makers and building users. Many school owners, administrators and even public authorities still underestimate the importance of indoor air quality or are unfamiliar with the technical requirements needed to achieve it.
Looking ahead, classroom ventilation should become as automatic and reliable as heating or lighting. Teachers should not have to manage indoor air quality by opening windows or monitoring ventilation equipment during lessons. Their role is to teach. It is the responsibility of designers, engineers and facility managers to provide a building that automatically maintains healthy indoor conditions. Creating such robust, energy-efficient and user-friendly systems will be one of the key challenges for the school sector in the years ahead.
[1] “Programma van Eisen Frisse Scholen 2025,” 2025. [Online]. https://www.rvo.nl/sites/default/files/2025-11/RVO - Frisse scholen 2025.pdf
[2] “VYHLÁŠKA 160/2024 Sb.,” 2024. [Online]. https://archiv.msmt.gov.cz/uploads/legislativa/160_2024_1.1.2026.pdf
[3] P. Wargocki and D. Wyon, “The Effects of Moderately Raised Classroom Temperatures and Classroom Ventilation Rate on the Performance of Schoolwork by Children (RP-1257),” HVAC&R Res., vol. 13, pp. 193–220, 2011, https://www.doi.org/10.1080/10789669.2007.10390951