Ask most engineers what a museum needs from its HVAC system, and the answer is usually: a very stable number. Eighteen to twenty degrees, fifty percent relative humidity, plus or minus five, all year round. Ask most policymakers what a building needs today, and the answer is: less energy, fewer emissions, faster. For years, cultural institutions have sat awkwardly between the two, as if protecting a manuscript and decarbonising a building were simply incompatible jobs.
REHVA’s first webinar in the SIMIACCI series set out to test that assumption directly, gathering a conservator, a manufacturer and an academic researcher — alongside brief policy and innovation framing from the SIMIACCI project itself — for a roundtable. What emerged was less a debate than a surprisingly quick convergence, and a set of implications that matter well beyond the museum sector.
· GLAM (Galleries, Libraries, Archives and Museums) specialist: Anaïs Ortiz, Archives Nationales de France, Head of the Preventive Conservation Department
· Market representative: Werner Adler, Head of Marketing, Communication & Public Affairs, Condair Switzerland and Condair Italy
· IAQ expert: Manuel Carlos Gameiro da Silva, Full Professor, University of Coimbra
· Policy Expert: Francesco Robimarga, Senior Policy and Advocacy Officer, REHVA
· Project Coordinator: Moisés Pinto, Full Professor, Instituto Superior Técnico of the University of Lisbon
The moderator, REHVA’s Pablo Carnero, opened with the question hanging over the whole project: is preserving cultural heritage incompatible with creating healthy, energy-efficient indoor environments? Anaïs Ortiz, who heads preventive conservation at the French National Archives, didn’t hesitate sacrificing human health or the planet’s future to preserve an object, she said, is “completely irrational” — any tension between the two is a legacy of poor understanding, not a real trade-off.
Werner Adler, representing the manufacturer side of the industry, went further, framing the two goals as compatible only if the sector abandons the idea of a single ideal climate for every room. His argument: treat this as risk management, not climate perfection. Monitor the building, the collection and the people continuously, understand where the real risks actually sit, and apply technology precisely where it’s needed — nowhere else. “The goal should not be perfect climate control,” he said, “but sufficient control for the lowest possible energy.”
Manuel Gameiro da Silva, a long-time IEQ researcher, agreed almost immediately, adding a useful piece of institutional history: the very tight temperature and humidity bands still quoted in some specifications trace back, in at least one documented case, to a single designer’s arbitrary decision decades ago — a number that then got copied from spec to spec with no scientific grounding behind it. It became convention simply because nobody questioned it.

Where the conversation really sharpened was on what “compatible” looks like in practice. Ortiz described how the French National Archives has already moved decisively away from the old, fixed set point. Her workplace now floats between 16 and 24°C and 40 to 58% relative humidity — a much wider band than conservation orthodoxy would have allowed a generation ago. The catch, and the part practitioners should pay close attention to, is that the width of the band isn’t the whole story: what her institution actually controls for is the rate of change — no more than roughly 1°C and 2% RH per day, and 2°C and 5% RH per week. It’s a strategy built around stability of trend, not stability of value, and the building’s energy model projects savings of around 60% as a result.
Adler confirmed why that distinction matters so much on the equipment side. A fixed set point — say, 50% RH held constant all year — forces a system to constantly add moisture, then strip it back out again, cycling equipment and burning energy for no real gain. Give the same system a wider, well-managed range instead, and it simply runs less. Gameiro da Silva added the number that makes over-cautious design so costly in practice: double the ventilation rate “just to be safe,” and you don’t double energy consumption — you multiply it by roughly eight. In a sector that has historically erred toward more ventilation and tighter control as the “safe” choice, that single figure reframes a lot of design decisions.
There was a genuinely interesting aside here too. Gameiro da Silva pointed to research on people living for long periods in stable-temperature environments — including a study of homeless populations sheltering in the Moscow metro — who lost some of their body’s own thermal regulation capacity after prolonged exposure to constant conditions. A smooth, gently varying climate that follows daily and seasonal rhythms, without sudden shocks, isn’t just more efficient. It may genuinely be healthier for occupants than the rigid stability conservation once demanded.
The roundtable wasn’t just consensus. Ortiz pushed back gently on the idea that conservation specifications are simply misunderstood by engineers, pointing to a real gap between climate specifications written to allow a wide, adaptive range and the equipment actually installed on site — which, in her own institution’s experience, is often locked to fixed set points that can’t exploit the flexibility the specification allows. The result: buildings that are contractually permitted to save energy but mechanically unable to.
She also raised a problem the panel hadn’t anticipated: sometimes the source of airborne pollutants isn’t the occupants or the outdoor air, as HVAC design conventionally assumes, but the artefacts themselves — objects and storage materials that off-gas compounds threatening both other items in the collection and the people working alongside them for hours at a time. Adler’s response was blunt: if the source is the object or its packaging, ventilation and filtration can only fight the symptom, not the cause. The real fix has to happen at the level of materials and storage, not air handling — a reminder that HVAC engineers can’t solve every indoor air quality problem from inside the plant room.
And when Carnero pushed on whether cultural institutions are actually ready to relax their traditional set points given better monitoring, Ortiz’s answer had an important caveat. On temperature and humidity, yes — many conservation professionals are already comfortable with wider bands, and instrumentation exists to track and alarm on both. On pollutants, the sector is still working largely on smell — literally: undetectable compounds go unmonitored until the damage is visible, and by the time something is noticeable to the human nose, “it’s usually too late.”
Perhaps the most striking moment came when Ortiz named a constraint that has nothing to do with engineering at all: loan contracts between institutions. Insurance policies attached to art and archival loans routinely dictate strict, fixed climatic conditions, regardless of what an institution’s own systems or building science can support. Even a conservation department that has fully embraced adaptive ranges can be forced back into rigid set points the moment a loaned object arrives — because the contractual and insurance frameworks around the sector haven’t caught up with the practice. Nobody on the panel had a ready answer; Carnero flagged it as a stakeholder group — insurers and loan negotiators — that future SIMIACCI events need to bring into the room.
Adler closed with a warning aimed squarely at anyone specifying a monitoring system for a heritage building: monitoring is not, by itself, a substitute for responsibility. Data without minimum performance requirements, meaningful alarms and a defined response process is just data collection. Combined with Ortiz’s closing point — that conservation teams are ready to modernise but are held back by budgets and understaffing rather than reluctance — the panel’s overall message to the value chain was less about new technology and more about follow-through: fund the monitoring, act on what it shows, and negotiate the contracts to match.

Adler’s own closing summary works as a fair distillation of where HVAC practice in cultural buildings needs to head: move from an ideal fixed set point to an acceptable risk range; stop assuming every room needs the same climate; treat ventilation as an air quality system rather than an air-volume system; use technology to understand the environment better rather than simply control it harder; and aim for sufficient control at the lowest possible energy demand, not perfection.
None of that requires waiting for new legislation or new materials — it requires better dialogue between the people who specify systems and the people who live with the consequences of those systems every day. As this first SIMIACCI webinar showed, that conversation is more productive, and the common ground wider, than the “conservation versus efficiency” framing usually suggests. Further sessions in the series will follow the project’s pilot sites as the technology moves from prototype to building.
Follow the latest SIMIACCI updates and opportunities through our communication channels. Subscribe to the newsletter for project news and insights and stay tuned for upcoming webinars. Recordings will be available on the project’s YouTube channel.
Youtube: https://www.youtube.com/@SIMIACCI
LinkedIn: https://www.linkedin.com/company/simiacci/
Newsletter: https://simiacci.eu/#newsletter
Website: https://simiacci.eu/
Funded by the European Union. Views and opinions expressed are however those of the author(s) only and do not necessarily reflect those of the European Union or the European Research Executive Agency (REA). Neither the European Union nor the granting authority can be held responsible for them.
![]()
Follow us on social media accounts to stay up to date with REHVA actualities
0