Keywords: Cybersecurity, Energy Communities, Building Management Systems, Cyber Resilience, Artificial Intelligence, Data Privacy
|
|
|
|
Mohammad Reza Habibi | Göran Hultmark | Kasper Lynge Jensen | Alireza Afshari |
Department of the Built Environment, Aalborg University, Denmarkmre@build.aau.dk | Department of the Built Environment, Aalborg University, Denmarkngh@build.aau.dk | Department of the Built Environment, Aalborg University, Denmarkklje@build.aau.dk | Department of the Built Environment, Aalborg University, Denmarkaaf@build.aau.dk |
Energy communities can involve several buildings with coordinated energy management, including the generation, use, and storage of energy, and they can take various forms, such as clusters of microgrids, or districts. A building energy system can include various technologies, such as photovoltaic systems to generate electricity, heating, cooling, and ventilation systems that consume energy, and batteries that store and release energy. Therefore, buildings can now actively participate in energy markets, not only as consumers but also as prosumers.
Building-level information, such as occupant presence and energy use patterns, can help higher-level energy systems operate more efficiently. However, falsified measurements or signals from compromised buildings can influence community-level decisions and optimization outcomes, such as energy prices. Coordinating many different building energy systems therefore remains both a complex operational challenge and a cybersecurity issue.
One of the challenges in incorporating building-level information is gaining access to it. To address this challenge, building management systems (BMSs) can be integrated with building services to monitor and control them while also connecting to the higher-level energy system. This integration can facilitate information exchange between the building and the higher-level system. Figure 1 illustrates this information exchange in a centralized manner.

Figure 1. Energy communities with a centralized energy management system that exchanges information with building management systems (BMSs).
A BMS plays an important role in building services, as it enables monitoring and control of building systems. A BMS is not limited to energy systems such as heating, cooling, and ventilation. It can also monitor and control water systems and other systems related to occupant comfort. Therefore, a BMS can access real-time data from connected building services, such as energy use, as well as occupant-related data.
Although a BMS can facilitate the efficient operation of building services, it can also increase the attack surface for cyber-attackers and, as a result, expose building services to cyber-attacks. These vulnerabilities may create various risks, such as manipulation of building system operations or unauthorized access to occupants’ private information.
For example, if a cyber-attacker gains access to building controls, the attacker could shut down the cooling system during a heatwave or turn off the heating system on a very cold night. The consequences depend on the type of building: they may range from occupant discomfort in homes and offices to overheating, equipment shutdown, or loss of service in critical facilities such as hospitals, laboratories, and data centres.
For example, if a cyber-attacker manipulates the electricity price received by a BMS, it can mislead the BMS. If the price is shown as low when it is actually high and as high when it is actually low, a BMS designed for economically building energy operation may increase energy use during actual high-price periods and decrease energy use when the actual price is low. Therefore, this type of cyber-attack can lead to the uneconomical operation of building services and impose an additional economic burden on building operations.
Data privacy is another important concern. BMS data can directly or indirectly reveal whether a building is occupied, indicate occupancy times, and expose occupancy routines over time. Energy use and water consumption patterns can also indirectly reveal activities, while indoor temperature data may indicate occupants’ comfort preferences. Protecting BMS data is therefore vital not only for reliable building operation but also for occupant privacy. Thus, while a BMS can improve the operation of building services, it can also create cybersecurity risks affecting comfort, energy costs, and privacy. Understanding common attack types is a useful first step toward addressing cybersecurity challenge in BMSs. Figure 2 highlights potential attack surfaces associated with BMS-related information flows.

Figure 2. Potential Cyber-attack surfaces related to a BMS.
Cyber-attackers may seek to disrupt building services, impose additional operational costs, or violate data privacy by gaining access to occupant information. Figure 3 summarizes several attack types. In this manuscript, three examples particularly relevant to BMSs are discussed: denial-of-service (DoS) attacks, false data injection attacks (FDIAs), and controller hijacking.
In the case of a DoS cyber-attack, a cyber-attacker can make a communication link connected to a BMS unavailable. For example, this may be the link between the BMS and a local controller or actuator in the building, such as a damper in a ventilation system duct. In this case, commands or information required to open or close the damper may not be delivered by the BMS. An FDIA manipulates BMS measurements by injecting false data. In the ventilation example, a falsified damper position signal may cause incorrect control calculations and, consequently, improper operation of the ventilation system. Controller hijacking is another potential BMS attack. It can be modelled by replacing a controller input with a fixed false value. If this value differs from the setpoint, the controller’s output may continuously command a damper to open or close even after the damper reaches its limit, potentially causing mechanical damage if protective limits are absent.

Figure 3. Several types of cyber-attacks worth studying in relation to building management systems (BMSs).
Artificial intelligence (AI) has shown potential for detecting cyber-attacks in different types of energy systems, as demonstrated in [1], [2], as well as for improving their cyber resilience through attack mitigation [3]. Therefore, AI can be considered a potential solution to address the previously discussed issue: the vulnerability of BMSs to cyber-attacks.
An AI-based model can extract hidden patterns or relationships from BMS signals by being trained on BMS datasets. This capability may contribute to improving BMS cybersecurity or, more broadly, enhancing its cyber resilience. For example, if a damper is reported as being a certain percentage open while the monitored airflow is inconsistent with this position, the discrepancy could indicate, among other causes, a faulty sensor or a cyber-attack on the BMS.
Therefore, by improving BMS capabilities, an advanced BMS can be developed that may detect suspicious measurements and replace them with more reliable values, such as validated AI-based estimations, until the compromised signal is identified and the cyber-attack is mitigated. For building professionals, cybersecurity should be considered an important requirement and an essential feature of future BMSs. Its absence may affect building operation and even system-level decisions and operations when a BMS is connected to a higher-level energy system. Thus, cybersecurity can be regarded as a primary design requirement for future BMSs.
A BMS may provide a valuable opportunity to facilitate the operation of building systems and enable the required information flow between a building and higher-level systems, such as energy communities, for coordinated operation. However, this information flow and the digitalization associated with BMSs can introduce new cyber-attack paths. To address this challenge, AI-based security layers could be added to future BMSs to learn relationships among BMS signals, identify suspicious conditions, and initiate appropriate mitigation actions when necessary. Improving the cybersecurity of BMSs is therefore important not only for individual buildings but also for the reliable and efficient system-level operation and energy management of energy communities.
More broadly, as buildings become increasingly digital and part of an expanding ecosystem of connected systems, cybersecurity is becoming an essential part of building performance and resilience. Building Management Systems are no longer isolated technical systems; they exchange data with energy networks, cloud platforms, smart city infrastructure, and other digital services, creating new opportunities for efficient and flexible operation, but also new vulnerabilities. Cybersecurity should therefore be considered alongside energy efficiency, indoor environmental quality, and operational reliability as a fundamental requirement for future buildings. Research combining building engineering, digital technologies, and artificial intelligence can play an important role in developing solutions that enable the benefits of digitalization while ensuring secure, reliable, and resilient building operation.
[1] Habibi, M.R., Guerrero, J.M. & Vasquez, J.C. Artificial intelligence for cybersecurity monitoring of cyber-physical power electronic converters: a DC/DC power converter case study. Sci Rep 14, 22072 (2024). https://doi.org/10.1038/s41598-024-72286-2
[2] M. R. Habibi, H. R. Baghaee, T. Dragičević and F. Blaabjerg, “Detection of False Data Injection Cyber-Attacks in DC Microgrids Based on Recurrent Neural Networks,” in IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 9, no. 5, pp. 5294-5310, Oct. 2021, https://doi.org/10.1109/JESTPE.2020.2968243
[3] M. R. Habibi, H. R. Baghaee, T. Dragičević and F. Blaabjerg, “False Data Injection Cyber-Attacks Mitigation in Parallel DC/DC Converters Based on Artificial Neural Networks,” in IEEE Transactions on Circuits and Systems II: Express Briefs, vol. 68, no. 2, pp. 717-721, Feb. 2021, https://doi.org/10.1109/TCSII.2020.3011324