Zohreh Kiani1,2,3
Kátia Cordeiro Mendonça3,4
Ali Nour Eddine5
Marc Abadie2,3
1Eurovent Certita Certification – Paris, France.
Corresponding author: zohreh.kiani@univ-lr.fr
 
2LaSIE UMR CNRS 7356, La Rochelle Université, La Rochelle, France
 
3RUPEE Lab, La Rochelle, France
 
Tipee Plateforme Technologique du Bâtiment Durable – RUPEE Lab, Lagord, France
 
5Eurovent Middle East, Dubai, United Arab Emirates

 

Introduction

Indoor Air Quality (IAQ) has become one of the most pressing public-health and building-performance challenges of our time. While outdoor air pollution has declined across much of Europe, air pollution remains the continent’s leading environmental health risk. What is often overlooked is that pollution is not limited to the outdoors – poor IAQ significantly contributes to respiratory and cardiovascular diseases, as well as long-term health impacts.

Although organisations such as ISO, CEN and ASHRAE have developed standards and guidelines for indoor air and ventilation, their impact remains limited due to their non-binding nature. In many European countries, legislation still lacks enforceable requirements for ventilation performance, filtration efficiency, air infiltration, system maintenance, and the control of indoor pollutants such as CO₂, formaldehyde and particulate matter. As a result, building occupants are often unaware of the actual quality of the air they breathe and lack tools to make informed decisions.

To address these gaps, Eurovent Certita Certification, launched the IAQ Project. It started with the development of a certification programme covering Indoor Air Quality and Energy Efficiency of Ventilation Systems (IAQVS) for individual houses (Phase I) and has expanded to a comprehensive methodology applicable to residential and commercial buildings (Phase II). The project was created to move beyond static standards and instead provide a performance‑based, scenario‑driven evaluation of ventilation systems, which takes into account both IAQ and energy performance. Using advanced numerical simulation tools, the IAQ project assesses how ventilation units and system configurations behave in real operating conditions, considering climate, wind profiles, airtightness, occupancy habits, pollution sources, dwelling layout, and building type.

Evaluating Single-Flow and Balanced Ventilation systems in multifamily residential buildings

The following case study explores the method developed by the IAQ Project for calculating IAQ performance in Phase II. The study is conducted on a two-story multifamily residential building representative of European housing stock. The building is assumed to be in an urban environment in Strasbourg. In addition, two levels of building envelop airtightness are considered: a tight envelope, representative of modern constructions, and a permeable envelope, representative of older or less airtight dwellings. Outdoor particulate pollution is introduced through two boundary conditions for PM2.5 concentration: a low pollution level (annual mean 10 µg/m³) and a high pollution level (annual mean >20 µg/m³) (See Table 1).

To evaluate the performance of the ventilation system, simulations are performed with HEAVENLY (Holistic Evaluation tool for Air VENtiLation sYstems) based on a TRNSYS-CONTAM dynamic computations of heat, moisture, and pollutants as described in Kiani et al. [1] (See Figure 1).

Table 1. Boundary Conditions. [20]

Case

Outdoor Environment

Building

Number

Wind Intensity

PM2.5Levels

Tightness

1

Strong

<10

Tight

2

Strong

<10

Permeable

3

Strong

>20

Tight

4

Strong

>20

Permeable

 

A screenshot of a house

Description automatically generated

A screen shot of a house

Description automatically generated

a)

b)

Figure 1. Representation of the 1st floor (a) and 2nd floor (b).[20]

Indicators

IAQ assessment is based on IAQ indicators for CO₂, used as a proxy for occupancy-related pollution and ventilation effectiveness; Formaldehyde (HCHO), representative of indoor chemical emissions from building materials and furnishings; PM2.5, representative of fine particulate matter influenced by outdoor pollution and filtration. Each pollutant assessed on a five-level scale.Based on [2] CO₂ concentration (ppm) is room related, so the IAQ for this room is calculated at each time step in each room and are compared directly with the limit values indicated in Table 2.For PM2.5 and formaldehyde, it is the average exposure of each occupant over 24 hours for PM2.5 and 30 minutes for formaldehyde, which must be compared to the reference value in Table 3.

Table 2. 5-level scale for CO₂.[19][20]

IAQ levels

ΔCO₂1

Acceptable deviation

Living Room

Bedrooms

 

Excellent

<950 ppm

<780 ppm

AD < 3%

Good

<1200 ppm

<950 ppm

AD < 3%

Acceptable

<1750 ppm

<1350 ppm

AD < 3%

Bad

<1750 ppm

<1350 ppm

AD < 5%

Very Bad

<1750 ppm

<1350 ppm

AD > 5%

1Concentration above outdoor concentration (400 ppm).

 

Table 3. 5-level scale for PM2.5and Formaldehyde. [19], [20]

IAQ levels

PM2.5(µg/m³)

HCHO (µg/m³)

Acceptable deviation

Long term

Short term

Long term

Short term

Excellent

Cm,a < 5 

Cm,24h < 10 

Cm,a < 30 

Cm, 30 min < 80 

Not permissible

Good

Cm,a < 5 

Cm,24h < 15 

Cm,a < 30 

Cm, 30 min < 100 

Not permissible

Acceptable

Cm,a < 5 

Cm,24h < 15 

Cm,a < 30 

Cm, 30 min < 100 

AD < 3%

Bad

Cm,a > 5

Cm,24h < 15 

Cm,a < 30 

Cm, 30 min < 100 

AD < 5%

Very Bad

Cm,a > 5

Cm,24h < 15 

Cm,a < 30 

Cm, 30 min < 100 

AD > 5%

 

Results

Figure 2 presents the IAQ indicator levels on a five-level scale (1 = Very Bad … 5 = Excellent) for CO₂, PM2.5 and HCHO, comparing Single-Flow (SF) and Balanced Ventilation (BV) for different boundary conditions. Across all boundary conditions, CO₂and HCHO remain consistently at “Good–Excellent” levels for both systems, whereas PM2.5 is the limiting pollutant and drives most of the differences between SF and BV.

For CO₂, both systems achieve values around 4.5–4.7, corresponding to Good to near-Excellent ventilation effectiveness for occupancy-related pollution. CO₂ is essentially unchanged across boundary conditions and between systems (SF: 4.5–4.6; BV: 4.6–4.7). For HCHO, both systems also remain in the Good range (≈4.1–4.4), with only minor variations between SF and BV, meaning that formaldehyde exposure stays well controlled in all tested cases.

In contrast, PM2.5 shows clear and systematic improvement with BV. Under low outdoor PM2.5 conditions (Figure 2.a, b), SF PM2.5 levels are Bad-to-Acceptable (2.2 and 2.5), while BV increases them to Acceptable-to-Good (3.6 and 3.7). Under high outdoor PM2.5 conditions (Figure 2.c, d, PM2.5 >20), SF reaches Very Bad particle performance (1.0 in both cases), whereas BV PM2.5 is Bad-to-Acceptable (2.6 and 2.7). This confirms that the BV system provides more robust particle-related IAQ, especially when outdoor PM2.5 is elevated.

A global IAQ index was computed as the average of the three pollutant indicator levels (CO₂, PM2.5, HCHO), and the standard deviation (SD) across pollutants describes how balanced performance is across contaminants. For SF, the global IAQ ranges from 3.3 to 3.8, corresponding overall to Acceptable–Good, but systematically downgraded by the PM2.5 indicator. For BV, the global IAQ ranges from 3.8 to 4.2, corresponding overall to Good performance, with smaller imbalance between pollutants. Specifically (mean ±SD across pollutants), global IAQ increases from 3.8 ±0.9 to 4.1 ±0.4 in Case 1, 3.7 ±1 to 4.2 ±0.5 in Case 2, 3.3 ±1.6 to 3.8 ±0.8 in Case 3, and 3.3 ±1.6 to 3.9 ±0.9 in Case 4 when moving from SF to BV. Overall, BV achieves a more consistently “Good” IAQ level, while SF remains more sensitive to outdoor particle pollution because PM2.5 frequently falls into Bad or Very Bad levels.

 

a) Case1: Strong wind, PM2.5 < 10, tight building

b) Case 2: Strong wind, PM2.5 < 10, permeable building

c) Case 3: Strong wind, PM2.5 > 20, tight building

d) Case 4: Strong wind, PM2.5 > 20, permeable building

Figure 2. IAQ indicator levels (five-level scale) comparing SF and BV systems across different boundary conditions.

 

Conclusion

Using a five-level scale for CO₂, PM2.5 and formaldehyde, results show that both systems maintain consistently good-to-near-excellent CO₂ levels (≈4.5–4.7) and good formaldehyde levels (≈4.1–4.4) across all cases. In contrast, PM2.5 is the main differentiator between ventilation strategies: BV systematically improves PM2.5 indicator levels relative to SF, with the largest gains observed under high outdoor PM2.5 conditions. Consequently, the global IAQ index (mean of the three pollutant indicators) is higher and more balanced for BV than for SF in every case, confirming that balanced ventilation provides more robust IAQ performance when outdoor particle pollution increases and/or envelope characteristics vary.

Overall, the IAQ Project has created a standards-based, indicator-driven assessment to reliably evaluate the IAQ performance of ventilation systems. For Phase II, the proposed indicator framework enables an interpretable, comparative evaluation of systems and highlights the importance of particle-related indicators when assessing IAQ performance in multifamily residential buildings.

The IAQVS certification programme combines thousands of simulations, certified product performances, and dynamic modelling, to identify mechanical ventilation systems for single-family homes and apartments that improve IAQ and optimise energy consumption. Find out more about the IAQVS certification programme at www.eurovent-certification.com

References

[1]     Z. Kiani, A. Eddine, K. Taurines, K. Mendonça, and M. Abadie, “Evaluating the IAQ and energy performance of ventilation systems in multifamily buildings,” E3S Web Conf., vol. 523, May 2024, doi: 10.1051/e3sconf/202452301003.

[2]     CEN, NF EN 16798-1 – Energy performance of buildings – Ventilation for buildings – Part 1: Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics – Module M1, May 2019.

Zohreh Kiani, Kátia Cordeiro Mendonça, Ali Nour Eddine, Marc AbadiePages 54 - 57

Stay Informed

Follow us on social media accounts to stay up to date with REHVA actualities

0

0 product in cart.products in cart.