The
relation between the indoor air quality in buildings and the health of
occupants gets more and more attention nowadays. However, it is difficult to
point to health effects that have a direct relation to poor indoor air quality.
In a risk assessment study Logue (2011) indicated that the risk of indoor air
quality on shortened life expectancy is in between the risk of car accidents
and the risk of heart diseases.
There may
be a stronger relation between the indoor air quality in bedrooms and the sleep
quality of inhabitants. Strøm-Tejsen et al. (2014)
showed that a higher ventilation rate (open window) had a significant positive
effect on sleep latency and the ability to fall asleep. This research reports
the measurement of bedroom CO2 levels and nocturnal restless
behavior of an Alzheimer patient as observed by the husband of the patient.
A couple (husband and wife) is living in a naturally ventilated house. Fresh air is provided in a natural way via the envelope of the house, possibly increased by the opening of one or more windows.
Since 2007, the wife is suffering from Alzheimer’s disease, with gradual increasing symptoms of dementia. During days, she occasionally suffers from restless behaviour, indicated by periodic introvert behaviour and humming sounds. During the nights, the restless behaviour occasionally shows, indicated by snoring, apnoea, restless sleep and panic when she wakes in the night.
During nights and in the afternoon, the wife, and sometimes the husband, take a sleep in the bedroom (Figure 1). The window in the bedroom is a top-hinged turnable window which is occasionally opened according to the wish of the husband. The interior door from the bedroom to the hallway may be opened or closed, as desired by the husband.
An indicator for the indoor air quality in the bedroom is the CO2 level, which has been recorded in a 15 minute interval with a CO2 logger (Wöhler type CDL 210). This logger simultaneously records temperature and relative humidity as well. The logger was placed on a small table next to the bed on the side where the husband sleeps, as far as possible from the direct breathing area.

Figure 1.The bedroom with a view on the window.
In order to avoid psychological influence
by the indicated CO2 level, it was proposed to
cover the screen with tape, but this was refused by the husband so he could see
whether an intervention like opening a window had an effect on the CO2 level.
The nocturnal behaviour of the wife was described during the night and the day by the husband in a notebook. Incidents of restless behaviour were noted with the specific time. Also, changes in the window position and interior door position were noted. Lastly, the occupation of the bedroom was noted. The indoor air quality and the observed behaviour were recorded during 5 weeks from the 5th of February 2014 until the 13th of March 2014.
In order to give an idea how the bedroom CO2 level was dependent on occupation and on window/door position, the average CO2 level was evaluated in categories. Figure 2 shows columns in the front row for an unoccupied bedroom, the middle row columns for one person and columns in the back row when two persons are in the bedroom. Furthermore, the horizontal axis shows the positions of window and interior door (closed or open).

Figure 2. The effect of occupation, window and door position on the average CO2 level in the bedroom. Left to right: door & window closed, door open & window closed, door closed & window open, door & window open.
As expected, the CO2 level rises with the number of people in the room. The results also show that the largest reduction of CO2 can be achieved by opening the window and leaving the door open to the hallway also help to reduce the CO2 level. Obviously, opening the window increases mixing of indoor air with fresh outdoor air, while opening the door increases mixing with indoor air from the hallway. There is one exception to this last effect: when the bedroom is unoccupied, an open door to the hallway leads to a slightly higher CO2 value, because CO2 level from the hallway can be larger than CO2 level from the bedroom.
The average values of CO2 level in the bedroom are for a 5 week period, so they cannot be regarded as statistical. Moreover, the number of recordings for each situation is not comparable. There were a lot of recordings with window and door both open, while only a few short periods with window and door both closed. In spite of this, the effect of occupation and window and door position on the CO2 level is logical and gives guidance to keep the indoor air quality to a certain level.
Figure 3 shows the first 5 days of the
recording period, where the husband experimented a lot with opening and closing
of windows and doors in the bedroom. The observed restless behavior of his wife
as described in the notebook coincides with peaks in the bedroom CO2 level. Whenever this behavior was apparent,
the window and/or door were opened in order to lower the CO2 level again. According to
the observations, approximately 30 to 45 minutes after this intervention (also
indicated in the graph), his wife was breathing and sleeping normally again.

Figure 3. The bedroom CO2 level and the observed behavior of the Alzheimer patient during a five day experimental period.
After a
couple of nights of experimenting, the husband of the Alzheimer patient decided
to keep an eye on the CO2 level and intervene with window and
door opening in a more anticipating way. Figure 4 shows that the restless behavior
during sleeping has decreased in occurrences, except for some nights when CO2 levels were quite high where window or door
was left closed.
From the recorded period and the noted observations, the data seems to indicate that the restless sleep behaviour is not observed when CO2 levels are kept below approximately 800 ppm.

Figure 4. The CO2 level and the occurrences of restless behavior (arrows) during the 5
week recording period.
The
restlessness during the sleep of the Alzheimer patient in this research seems
to be coincident with high levels of CO2 in the bedroom. According to the observations of her husband during the
recording period, but also afterwards, the restless behavior has not been
observed anymore when the CO2 levels are kept below 800 ppm. The temperature and relative humidity recordings were
also available, but they had no clear deviating pattern coinciding with the
restless behavior of the Alzheimer patient.
From the
average CO2 levels recorded in the bedroom, the
advice is given to at least open the window of the bedroom in order to keep the
CO2 level below 800 ppm when the bedroom is occupied with one or two persons.
Following
this strategy, the husband decided to place two CO2 loggers permanently, one for the bedroom and one for the living room.
Also daytime restless behavior seems to have been decreased since the time that
living room CO2 levels are kept below 800 ppm by opening windows and doors occasionally. Before this
knowledge, it was concluded that the restless behavior during for instance
birthday parties was originating from the larger number of people in the living
room, bringing stress signals to the Alzheimer patient. But this research and
the observations may indicate that the elevated CO2 level itself is responsible for the restless behavior. Nowadays, people
are welcome to the house again, without restless behavior, as long as open
windows and door keep the CO2 level low.
The recordings and observations in this research are for one patient only. But following this research, a couple of initiatives have been started to monitor the indoor air quality and the nocturnal restlessness of Alzheimer patients in care facilities. Only after this larger research these early observations can be substantially backed up by more scientific evidence.
The
question arises whether the relation between CO2 level and restless behavior can be broadened to a larger group like
people suffering from dementia, or even healthy people. The author of this article
postulates that healthy people have an adaptive response to higher CO2 levels, meaning they can cope with elevated
levels, both physically and mentally, without suffering restless behavior. But
people suffering from Alzheimer, or another form of dementia, may have lost
this adaptive response to high CO2 levels and can react physically more intense and already at relatively
low CO2 levels of about 800 ppm. Extensive observational and medical studies have to be
carried out to prove if this is the case.
This
research shows that the restless behavior of an Alzheimer patient coincides
with peaks of the bedroom CO2 level above 800 ppm. The observed restless sleeping behavior like snoring,
teeth-grinding, apnea and panic were not observed anymore when CO2 levels are kept below 800 ppm. After a peak of CO2 level and coincident restless behavior, a window was opened so that CO2 level decreased and after 30 to 45 minutes the
sleep of the Alzheimer patient was observed to be restful again.
Much more
research should be carried out in the near future if the relation between CO2 level and restlessness also exists for a
larger group of Alzheimer patients or wider for a group of people suffering
from dementia or even for healthy people.
Logue JM, Price PN, Sherman MH, Singer BC
(2011), Why We Ventilate; LBNL-5093E.
Strøm-Tejsen P, Wargocki
P, Wyon DP and Kondracka A.
(2014). The effect of air quality
on sleep. In: Proceedings of the 13th International Conference
on Indoor Air Quality and Climate – Indoor Air 2014, Hong Kong, Paper HP0506.