Keywords: Low-temperature district heating, Nordic climate, Old apartment, Energy simulations, Hydrogen-production-based waste heat.

 

Jiayi Liu
Yuchen Ju
Risto Kosonen
Juha Jokisalo
Altti Meriläinen
Antti Kosonen
Aalto University, School of Engineering, Department of Civil Engineering, Finland
Jiayi.1.liu@aalto.fi
Aalto University, School of Engineering, Department of Civil Engineering, Finland
Aalto University, School of Engineering, Department of Civil Engineering, Finland
Aalto University, School of Engineering, Department of Civil Engineering, Finland
Lappeenranta-Lahti University of Technology, Finland
Lappeenranta-Lahti University of Technology, Finland

 

Lowering district heating temperatures improves efficiency and sustainability but challenges existing high-temperature radiator systems. This study investigates the feasibility of integrating low-temperature district heating with high-temperature radiator systems in old apartment buildings using backup heating. Results show over 93% annual heating coverage and over 80% peak heating coverage.

Introduction

Reducing district heating (DH) temperatures is regarded as a promising approach to improving the flexibility and sustainability of district heating systems [1]. Lower operating temperatures reduce heat losses in transmission and distribution networks, enhance overall system efficiency, and facilitate the integration of low-grade renewable and waste heat sources,such as waste heat from hydrogen production [2]. However, the transition towards low-temperature district heating (LTDH) shows practical challenges, particularly in the existing building stock, where heating systems were commonly designed for high-temperature district heating. The relatively high supply water temperatures required by these systems may limit their direct integration with LTDH networks.

A potential retrofit solution that avoids replacement of existing high temperature radiators is to introduce backup heating on the building side. The backup heater provides supplementary heating to the secondary-side supply water when the LTDH system is insufficient to achieve the required setpoint temperature. This study evaluates the energy performance of an LTDH configuration utilizing waste heat from alkaline water electrolysis with different backup heating options in apartment buildings constructed in the 1960s.

Methodology

The case study was conducted based on two apartment buildings constructed in 1969, located in Helsinki, Finland. The buildings have identical layouts and structures and are equipped with similar HVAC systems.Each building has a net heated floor area of 4994 m², heated by a radiator system connected to the district heating network.The main difference between the two buildings is the design temperature level of the radiator system. The nominal supply/return water temperatures are 80/50°C for Building A and 70/40°C for Building B.

The energy performance of the case buildings was evaluated under two district heating scenarios: a) a high-temperature district heating (HTDH) reference scenario using conventional district heating with supply temperatures of 75–90°C; and b) a low-temperature district heating (LTDH) scenario using waste heat from an off-grid alkaline water electrolysis plant, upgraded by a heat pump to a constant supply temperature of 65°C. Two backup heating options were considered for the LTDH scenario to meet the required secondary-side supply temperature: an electric heater and a return water heat pump with a hot-water storage tank. Figure 1 shows the two LTDH configurations, and Table 1 summarizes the simulation cases.

LTDH system with an electric heater

LTDH system with a heat pump

Figure 1. Diagram of the proposed LTDH system.

 

Table 1. Definitions of studied simulation cases.

Buildings

Ref. building A with 80/50°C radiators

Ref. building B with 70/40°C radiators

Heating systems

A-HTDH-80/50 (Ref.)

A-LTDH-80/50-EH

A-LTDH-80/50-HP

B-HTDH-70/40 (Ref.)

B-LTDH-70/40-EH

A-LTDH-70/40-HP

Primary heating

Conventional HTDH

Hydrogen-production-based LTDH

Hydrogen-production-based LTDH

Conventional HTDH

Hydrogen-production-based LTDH

Hydrogen-production-based LTDH

Backup heating

None

Electric heaters

Heat pump

None

Electric heaters

Heat pump

Radiator design inlet/outlet temp. [°C/°C]

80/50

80/50

80/50

70/40

70/40

70/40

 

All simulation cases were modelled using IDA Indoor Climate and Energy (IDA ICE) version 5.1, developed by EQUA Simulation AB [3]. The software has been extensively validated [4,5,6] and has demonstrated reliable performance in dynamic multi-zone simulations of thermal comfort, indoor climate, and building energy use. The simulations were performed using the Helsinki Test Reference Year 2020 weather dataset provided by the Finnish Meteorological Institute, representing average climatic conditions over the 30-year period from 1989 to 2018 [7].

Results

How much heating demand can be covered by district heating return water?

Figure 2 presents the annual purchased energy use of the investigated cases, including district heating and electricity. The solid line indicates the share of the total heating demand covered by DH. The LTDH system covered 93% and 99% of the annual heating demand in Buildings A and B, with radiator design temperatures of 80/50°C and 70/40°C, respectively. The higher-temperature radiator system required more backup heating to achieve the required supply water setpoint, resulting in higher electricity use. This electricity demand was substantially reduced when a heat pump was used for backup heating. In contrast, the benefit of the heat pump was limited in Building B due to its relatively low backup heating demand.

Figure 2. Total annual purchased energy consumption and LTDH coverage of simulation cases, LTDH coverage represents the coverage of total heating demand covered by LTDH.

 

How much heating power can be covered by district heating return water?

Figure 3 presents the purchased peak power demand and the duration curves of backup heating electricity demand. The LTDH system covered 80% and 91% of the peak heating demand in Buildings A and B, respectively. Compared with the annual energy coverage, the peak power coverage was lower, indicating that backup heating was required at relatively high-power levels during limited periods. This is also reflected in the duration curves, where high backup heating demand occurred only for short durations, while remaining low for most of the year. The use of a heat pump substantially reduced the peak backup electricity demand from 64.7 to 14.6 kW in Building A and from 27.6 to 3.4 kW in Building B.

 

(a) Purchased peak power demand

(b) Backup heating electricity power duration curve

Figure 3. Purchased peak power demand and backup heating power duration curves of simulation cases. LTDH coverage represents the coverage of total heating peak power demand covered by LTDH.

 

Conclusion

Reducing district heating temperatures is an important pathway towards more flexible and sustainable district heating systems, but the high operating temperatures of existing heating distribution systems remain a major barrier to this transition. This study investigated the feasibility of integrating 1960s apartment buildings with LTDH while retaining their existing radiator systems by introducing backup heating on the building side.

The results showed that LTDH based on waste heat from hydrogen production supplied more than 93% of the annual heating demand and at least 80% of the peak heating demand in the studied apartment buildings. The required backup heating depended strongly on the radiator temperature level, with higher-temperature systems requiring greater supplementary heating. Compared with direct electric heating, a heat pump substantially reduced the backup electricity demand, although its practical application should also be evaluated from an economic perspective.

Acknowledgement

This study is part of the B2RECoM project funded by Business Finland and the following companies and cities participating in the project: Aalto University Campus & Real Estate Ltd., ARCO Ltd., Elstor Ltd., Fortum Power and Heat Ltd., Gebwell Ltd., Granlund Ltd., Smart Heating Ltd., Sweco Finland Ltd., City of Helsinki, and City of Lappeenranta.

The authors would like to gratefully acknowledge the partners of the B2RECoM project.

References

[1] Guelpa, E., Capone, M., Sciacovelli, A., Vasset, N., Baviere, R. & Verda, V., 2023. Reduction of supply temperature in existing district heating: A review of strategies and implementations. Energy, 262, 125363. https://doi.org/10.1016/j.energy.2022.125363

[2] Lund, H., Werner, S., Wiltshire, R., Svendsen, S., Thorsen, J.E., Hvelplund, F., Mathiesen, B.V., 2014. 4th generation district heating (4GDH): Integrating smart thermal grids into future sustainable energy systems. Energy 68, 1–11. https://doi.org/10.1016/j.energy.2014.02.089

[3] Sahlin, P., 1996. Modelling and simulation methods for modular continuous systems in buildings. PhD thesis, KTH, Stockholm.

[4] Lundqvist, P., Risberg, M. and Westerlund, L. 2022. Indoor thermal climate after energy efficiency measures of a residential building in a sub-Arctic region: Comparing ANSYS CFX and IDA ICE methods. Indoor and Built Environment, 31(3), pp. 732–744. https://doi.org/10.1177/1420326X211030323

[5] Yuan, X., Hu, X., Liu, J., Jokisalo, J., Kosonen, R., Ju, Y., Xue, T., Meriläinen, A. and Kosonen, A., 2025 Techno-economic design of zero-energy detached house’s energy system with water electrolysis-based hydrogen waste heat under Nordic climate conditions.Energy and Buildings, 346, 116158. https://doi.org/10.1016/j.enbuild.2025.116158

[6] Liu, J., Junttila, A., Kosonen, R. & Jokisalo, J., 2025. Price models for the district heating return water for Nordic new apartment building with different backup heating systems. Energy and Buildings, 347(Part B), 116297. https://doi.org/10.1016/j.enbuild.2025.116297

[7] Jylhä, K., Ruosteenoja, K., Böök, H., Lindfors, A., Pirinen, P., Laapas, M. & Mäkelä, A., 2020. Nykyisen ja tulevan ilmaston säätietoja rakennusfysikaalisia laskelmia ja energialaskennan testivuotta 2020 varten. Ilmatieteen laitos, Raportteja 2020:6, Helsinki. [Online] Available at: http://hdl.handle.net/10138/321164 [Accessed 11 Augest 2026]

Jiayi Liu, Yuchen Ju, Risto Kosonen, Juha Jokisalo, Altti Meriläinen, Antti KosonenPages 47 - 50