Lucija Gruden | Eneja Osterman | Urška Mlakar | Uroš Stritih |
MSc, Laboratory for Heating, Sanitary, Solar and Air Conditioning, University of Ljubljana, Faculty of Mechanical Engineering, Ljubljana, Slovenialucija.gruden@fs.uni-lj.si | Dr., Interenergo energetski inženiring, Ljubljana, Slovenia | MSc, Laboratory for Heating, Sanitary, Solar and Air Conditioning, University of Ljubljana, Faculty of Mechanical Engineering, Ljubljana, Slovenia. | Assoc. Prof. Dr., Laboratory for Heating, Sanitary, Solar and Air Conditioning, University of Ljubljana, Faculty of Mechanical Engineering, Ljubljana, Slovenia. |
· TSP – Total Suspended Particulate
· IAQ – Indoor Air Quality
· TC – Thermal Comfort
· ECC – Elderly Care Center
· TVOC – Total Volatile Organic Compounds
· AC – Air Conditioning
· PM – Particulate Matter
· DHW – Domestic Hot Water
Energy use became more challenging during COVID-19, as the need for proper ventilation to prevent infection had to be balanced with minimizing consumption. This article reviews ventilation systems, including their technical aspects, operation, maintenance, and air quality.
Indoor air quality (IAQ) significantly affects health, particularly for elderly residents in care centers, with pollutants like CO₂, CO, NO₂, SO₂, PM, and biological agents (bacteria, fungi, viruses) being key contributors. Migliaretti et al. [1] and Atkinson et al. [2] both found links between urban air pollution and increased hospital visits for respiratory problems, especially among the elderly.
As of 2019, 703 million people globally were 65 or older, a number projected to rise to 1.5 billion by 2050. Slovenia is expected to have one of the highest old-age dependency ratios by then (Figure 1).

Figure 1. Ten countries or areas with the highest old-age dependency ratio (65+), 2019 and 2050. [3]
The GERIA study in Portugal highlighted poor IAQ and thermal comfort (TC) in elderly care centers (ECCs), with concerning levels of CO₂, TVOCs, and bacteria. Simple improvements like insulation could boost health without sacrificing ventilation. In Houston, many assisted living facilities exceeded CO₂ thresholds or were overheated, affecting vulnerable seniors [4].
Research by Fink et al. [5] underscores the sensitivity of elderly individuals with chronic diseases to IAQ and TC, emphasizing the need for well-designed indoor environments. Space heating demand studies [6] showed a base temperature difference in nursing homes, indicating that heating demands could offset some of the benefits of global warming.
Mata et al. [7] recommend a holistic approach to IAQ management in ECCs, focusing on building design, comprehensive IAQ assessments, stakeholder awareness, and automated air-flow systems. These studies underscore the strong connection between IAQ, TC, and health in elderly care settings.
A comprehensive survey analyzed energy use and ventilation in Slovenian elderly care centers (ECCs). A detailed questionnaire was distributed to approximately 200 ECCs, yielding 16 responses on building energy audits, renovation history, heat consumption, and ventilation practices. The data covered ventilation methods, types of systems used, ventilation frequency, and specific rooms ventilated, focusing on advanced systems like recuperators and CO₂ sensors. Energy consumption data were collected regarding heating and domestic hot water (DHW), compared against 2022 minimum heat consumption requirements.
Standard methods for assessing indoor air quality and energy use were employed, referencing studies such as the GERIA study and work by Satish et al. This approach provided insights into current practices and challenges, integrating energy and air quality considerations in Slovenian ECCs.
Given that people spend around 85-90% of their time indoors [11], minimizing indoor pollutants is essential. Effective practices include selecting low-emission furniture, regularly inspecting ventilation systems, and frequently airing out spaces [8]. The European GERIE study highlights the importance of proper ventilation, demonstrating its independent impact on respiratory health in elderly residents of ECCs [9]. Adverse effects were particularly pronounced in poorly ventilated environments for those over 80.
During the assessment, researchers calculated mean and median values of several air pollutants (e.g., PM10, formaldehyde, NO₂, ozone, CO₂) in each ECC. Only 19% of participants experienced adequate ventilation, and poor ventilation was linked to increased respiratory issues among elderly residents.
Space heating accounts for up to 62.8% of final energy in the residential sector [10], with 30-50% lost through ventilation. Given the push for energy efficiency, many new buildings are becoming airtight, leading to reduced air exchange rates (0.2 to 0.3 h⁻¹), below the recommended 0.5 h⁻¹ [12]. A review [13] of 20 studies on airtightness and indoor air quality revealed that mechanical ventilation could reduce PM concentrations by about 90% across various sizes, underscoring the need for effective ventilation systems [14].
Research by Satish et al. [15] examined how varying CO₂ concentrations affect human capabilities, involving 22 volunteers performing tasks at different CO₂ levels, as shown in Figure 2.

Figure 2. Effect of CO₂ concentration on various activities. [15]
To gather data on energy use and ventilation in Slovenian ECCs, a questionnaire was developed (see Figure 3).

Figure 3. The questionnaire.
The questionnaire was distributed to approximately 200 ECCs, yielding 16 responses. Most respondents reported having completed an energy audit at least once, with 14 out of 16 confirming this. While many homes had undergone renovations (Figure 4), very few had completed energy rehabilitations (Figure 5).

Figure 4. Results regarding renovation in elderly homes.

Figure 5. Results regarding energy rehabilitation in elderly homes.
Based on the Figure 6, we compared the minimum heat consumption requirements for 2022 [16] with actual heat consumption. Figure 6 shows that most surveyed ECCs are near the required energy consumption levels, although a few exhibit significantly excessive consumption.

Figure 6. Comparison of heat consumption concerning the minimum.
We also analyzed whether the data aligns with the aforementioned statistics. Figure 7 illustrates that annual energy consumption for space heating and domestic hot water (DHW) heating shows space heating typically constitutes the majority of heat needs.

Figure 7. Results of heat needed for heating and domestic hot water.
The responses regarding ventilation were limited, but we analyzed the ventilation methods and the rooms that are regularly aired. Figure 8 illustrates these methods, classified by ventilation quality and color-coded by room. Most ECCs ventilate by opening windows and doors, which is less efficient and less healthy. Some areas use fans, offering better fresh air circulation but still wasting heat. Notably, there was no evidence of recuperators being used, which would be the most energy-efficient option, typically achieving around 95% efficiency while providing adequate fresh air.

Figure 8. Ventilation methods in different rooms.
It was also noted that no CO₂ sensors were installed. Ideally, ventilation systems should be controlled based on CO₂ concentration, as highlighted in previous studies, since this significantly impacts human activity.
The survey identifies challenges and opportunities in energy use and ventilation among Slovenian ECCs. While most conduct energy audits, only 19% have completed energy rehabilitation, revealing a gap between awareness and action in energy efficiency improvements.
Most ECCs are near the 2022 heat consumption requirements, but some exceed these limits, highlighting the need for targeted interventions.
Ventilation remains a concern, with many relying on natural methods like opening windows and doors. The absence of advanced systems such as recuperators and CO₂ sensors indicates lost opportunities for energy savings and improved indoor air quality.
Comparing these findings with studies like the GERIA study highlights the ongoing need for effective ventilation to mitigate health risks for elderly residents. Overall, enhanced regulations and practical measures are essential for promoting energy efficiency and better indoor air quality in ECCs.
The questionnaire results indicate that only 19% of ECCs have undergone energy rehabilitation, while 44% have made some renovations. At least six out of 16 ECCs need to address high heat consumption. Notably, 44% rely solely on natural ventilation (opening windows and doors), and 56% use other ventilation methods only in specific areas like kitchens and bathrooms. None of the participating ECCs have recuperation systems, and only one has air conditioning for common areas, kitchens, and laundries, with no CO₂ sensors installed.
To gain a more accurate understanding of energy use and ventilation in ECCs, more data is needed. If our small sample reflects the average ECC, it's crucial to raise awareness among directors about the importance of effective and energy-saving ventilation. Most homes currently ventilate inefficiently, which could be improved by installing more economical systems, like recuperators. However, regulations for residential buildings are lacking, especially for ECCs, which typically accommodate more residents than standard homes.
Monitoring air quality is essential before or after installing ventilation systems, and using CO₂ sensors is a straightforward method. Increased CO₂ levels can also indicate higher pollutant concentrations in the air.
[1] Migliaretti G, Dalmasso P, Gregori D. Air pollution effects on the respiratory health of the resident adult population in Turin, Italy. Int J Environ Health Res. 2007 Oct;17(5):369-379. https://doi.org/10.1080/09603120701628768.
[2] Atkinson RW, Anderson HR, Sunyer J, Ayres J, Baccini M, Vonk JM, et al. Acute effects of particulate air pollution on respiratory admissions: results from APHEA 2 project. Air Pollution and Health: a European Approach. Am J Respir Crit Care Med. 2001 Nov 15;164(10 Pt 1):1860-6. https://doi.org/10.1164/ajrccm.164.10.2010138.
[3] United Nations. World Population Ageing 2019: Highlights [Internet]. New York; 2019 [cited 2022 Jun 9]. Available from: https://www.un.org/en/development/desa/population/publications/pdf/ageing/WorldPopulationAgeing2019-Report.pdf.
[4] Baniassadi A, Sailor D J, Olenick C R. Indoor air quality and thermal comfort for elderly residents in Houston TX—a case study. 7th International Building Physics Conference. 2018. https://doi.org/10.14305/ibpc.2018.ie-2.04.
[5] Fink R, Eržen I, Medved S. Impacts of the thermal environment and indoor air quality on potential risks for elderly people with cardio-vascular diseases. REHVA Journal. 2013;38-39.
[6] Lampret Ž, Krese G, Prek M. The effect of population aging on heating energy demand on national level: A case study of Slovenia. Journal of Mechanical Engineering. 2019;65(11-12):701-708. https://doi.org/10.5545/sv-jme.2019.6394.
[7] Mata TM, Felgueiras F, Martins AA, Monteiro H, Ferraz MP, Oliveira GM, et al. Indoor Air Quality in Elderly Centers: Pollutants Emission and Health Effects [Internet]. 2022. [cited 2022 Nov 11]. Available from: https://doi.org/10.3390/environments9070086.
[8] Jiang XQ, Mei XD, Feng D. Air pollution and chronic airway diseases: what should people know and do? J Thorac Dis. 2016 Jan;8(1):E31-40. https://doi.org/10.3978/j.issn.2072-1439.2015.11.50.
[9] Bentayeb M, Norback D, Bednarek M, Bernard A, Cai G, Cerrai S, et al. Indoor air quality, ventilation and respiratory health in elderly residents living in nursing homes in Europe. Eur Respir J. 2015 May;45(5):1228-38. https://doi.org/10.1183/09031936.00082414.
[10] Eurostat. Energy consumption in households [Internet]. 2022 [cited 2022 Jun 9]. Available from: https://ec.europa.eu/eurostat/statistics-explained/index.php?title=Energy_consumption_in_households#Energy_products_used_in_the_residential_sector.
[11] Brown L. National Radiation Survey in the UK: Indoor Occupancy Factors. Radiation Protection Dosimetry. 1983 4:203-208. https://doi.org/10.4236/gep.2016.45012.
[12] Jones A P. Indoor air quality and health. Atmospheric Environment 1999;28:4535-4564. https://doi.org/10.1016/S1352-2310(99)00272-1.
[13] Kempton K, Daly D, Kokogiannakis G, Dewsbury M. A rapid review of the impact of increasing airtightness on indoor air quality. Journal of Building Engineering 2022;57 https://doi.org/10.1016/j.jobe.2022.104798.
[14] Wallis S, Hernandez G, Poyner D, Holmes W, Birchmore R, Berry T. Particulate matter in residential buildings in New Zealand: Part II. The impact of building airtightness, mechanical ventilation using simulated occupancy. Atmospheric Environment: X. 2019;2 https://doi.org/10.1016/j.aeaoa.2019.100026.
[15] Satish U, Mendell MJ, Shekhar K, Hotchi T, Sullivan D, et al. Is CO₂ an indoor pollutant? Direct effects of low-to-moderate CO2 concentrations on human decision-making performance. Environ Health Perspect. 2012 Dec;120(12):1671-7. https://doi.org/10.1289/ehp.1104789.
[16] Official Gazette of the Republic of Slovenia. Rules on efficient use of energy in buildings. 2022 [cited 2022 Nov 10]. Available from: https://pisrs.si/pregledPredpisa?id=PRAV14331.
[17] Mendes A, Pereira C, Mendes D, Aguiar L, Neves P, Silva S, et al. Indoor air quality and thermal comfort-results of a pilot study in elderly care centers in Portugal. J Toxicol Environ Health A. 2013;76(4-5):333-44. https://doi.org/10.1080/15287394.2013.757213.