Zeno BastianPassive House Institute (PHI)zeno.bastian@passiv.de | Marleen SpiekmanNetherlands Organization for | Alexandra TroiEURAC
researchalexandra.troi@eurac.edu |
Key words: EPBD, energy legislation, requirements,
CEN TC 346, conservation, historic buildings, energy retrofit with
Passive House components, EnerPHit. |
Historic buildings are the trademark of numerous European cities, town and villages and are a living symbol of Europe's rich cultural heritage and diversity. They reflect the society's identity and need to be protected. However, they show high level of energy inefficiency contribute substantially to CO2 emissions and rising energy bills. Even more, these buildings do not offer appropriate indoor environment quality (IEQ) nor the conditions necessary for heritage collections preservation.
Within 3ENCULT a number of solutions have been developed and tested at case studies for improving the energy efficiency while conserving the heritage and guaranteeing long term structural health and preservation of historic buildings. This was possible by including all stakeholders in the design process of the energy retrofit. This base principal is reflected in the multidisciplinary consortium: it has gathered together scientists along with stakeholders from architecture, conservation, building physics and other specific technologies.
This article will present how the integration of historic buildings is assessed in relation to and recommended to be taken into consideration in: EPBD and EPBD CEN standards, then in CEN TC 346 and last but not least in the EnerPHit Certified Retrofit (PHI).
Legislation
is a proven instrument to help reaching energy ambitions. The EPBD is such an
instrument, put in place at a European level and influencing legislation in all
Member States in respect of energy use in the build environment. Integration of
historic buildings in the EPBD will be a driving force in striving towards the
ambitious goals set. However, (listed) historic buildings were left out the
EPBD in the first place. To realize an ambitious energy saving level in
historic buildings and really have impact in Europe, integration of historic
buildings in the EPBD might be a fruitful tool. This was investigated within
3ENCULT. The results of this investigation are described in the following
chapters.
Some
requirements in the EPBD do not exempt listed historic buildings. Large heating
and air-conditioning systems need to be regularly inspected, which was judged
by the multidisciplinary team of 3ENCULT as a reasonable requirement also for
historic buildings. Also the EPBD requires national requirements for building
systems that are replaced or upgraded. In principle this was agreed upon by the
team, but with the warning that the choice, functionality and functioning of
the systems should always be respectful of the building inner character and
take into account the necessary thermal and hygrometric comfort that is
necessary to protect the construction and present works of art (e.g. fresco’s)
and still be economically feasible under those conditions.
Member
States may exempt listed historic buildings under certain conditions from
national minimum energy performance requirements for the parts of the building
envelope that are retrofitted or replaced. The team agrees that exemptions
should indeed be possible. Although it seems reasonable to replace parts of the
envelope by high efficiency products when they are being removed anyway, we
should be aware that new elements in the façade may influence the indoor
climate and that might risk the construction or possible present artefacts. On
the other hand, where possible, high energy efficient products should be
encouraged.
In general
there was agreement among the multidisciplinary team that for transparency
reasons making an energy certificate for (listed) historic buildings, as is
done for all other buildings as well, is a good idea. Where the complex nature
of historic buildings makes it preferable that the certificate is made by an
expert who has experience with energy in historic buildings. Also it is
suggested that in case of listed historic buildings a logo, including energy and (if available) heritage value
figures on the certificate and an explanation warns the user that a skilled design
team shall be consulted to judge the proposed measures.
Finally, it
was suggested to add a requirement in the EPBD for an obligatory analysis of
energy saving potentials & options in historic buildings. The idea behind such
obligatory analysis is that in this way in an early phase of the renovation
process of an historic building energy saving measures are at least considered.
The analysis can show what measures might be fruitful from energy point of view
and which don't need additional consideration.
Such an
analysis assures that:
·
In
an early phase of the renovation process of an historic building energy
saving measures are at least considered, and biases about impossibilities are
taken away where possible;
·
Awareness
is raised about possible innovations, increasing the chance that these are
considered seriously;
· A breeding ground for promotion of energy saving products for historic buildings is created.
The major
development in the field of historic building renovation over the past few years
is a new openness on the part of architects and conservators to include
historic buildings in energy-efficient retrofitting.
When the
first version of the EPBD came out in 2002, there was a general fear that
historic buildings would be disfigured or ruined. This resulted in a quite
defensive attitude and the endeavor to exclude historic buildings from any
obligations. Nowadays, this has changed to a more constructive approach: they
want to preserve the buildings; they want them to be used and to make them more
energy efficient. Of course, this has to be done in a way that is compatible
with the heritage value of a building.
Actually, a
group of experts within CEN TC 346 pro-actively approaches the theme,
having recognized that the initiative has to come from inside the “community”.
Being developed is a guidance on how to improve energy performance of historic
buildings – not limited to officially protected ones, but covering a whole
range of building types and ages, all buildings which are “worthy of preservation”.
The experts discuss, how the heritage value as well as the physical status of
the building are assessed, which peculiarities historic buildings do have
compared to new (or newer) ones, what this means for the determination of
energy performance, how the potential of the building in all its dimension is
understood and best used and finally which aspects from reversibility over cost
to (life cycle) energy performance the assessment of possible interventions has
to consider.
Definitely,
a key factor for success identified within the group is the interdisciplinary
team and the dialogue that has to shape the process from the diagnosis to the
design and selection of best-suited intervention.
While the
EPBD and its national adaptations set mandatory requirements for the energy
demand of new buildings and renovations, there are also a number of additional
voluntary energy standards. The Passive House standard was defined in the 1990s
by the Passive House Institute in
In many
European countries the building renovation market has gained the main market
share in the recent past. However, when old buildings are renovated, it is
often difficult to achieve Passive House standard. Typical reasons for this are
unavoidable thermal bridges as well as a general building design, which was
originally not optimized for energy efficiency. For such buildings, the Passive
House Institute (PHI) introduced the EnerPHit standard in 2010. The basic
principle is to modernize all relevant parts of the building with Passive House
components. This way almost all advantages of the Passive House standard can be
realized in retrofits, even if the heating demand is not reduced all the way
down to the Passive House limit of 15 kWh/(m²a).

Figure 1. EnerPHit seal.
Typical
Passive House components, which are required for EnerPHit (Energy Retrofit
With Passive House Components) retrofits in cool,
temperate climates like Central Europe include an efficient heat recovery
ventilation system, windows with triple glazing and insulated frames, more than
Originally
the EnerPHit standard could only be applied to retrofits of non-listed
buildings in cool, temperate climates. In the 3ENCULT, the EnerPHit criteria
have been developed further in order to also allow for certification of listed
and historic buildings. This includes special provisions for buildings which
can only be renovated with interior insulation, as is often the case in
historic buildings with valuable façades. Additionally, exemptions for other
parts of the building with restrictions by the cultural heritage authorities
were introduced. The concept aims at improving the efficiency of each
individual part of a historic building as long as this is compatible with the
protection of the cultural heritage value.
Another
recent development carried out within 3ENCULT is the adaptation for application
in all European climates. The quality requirements for individual building
components will continue to be the basis of the international EnerPHit
criteria. The new component requirements for different climates were derived by
means of an economic optimization process. The process was carried out for each
location in a grid of climatic data sets covering all of
The cost-optimal component set for the end-of-terrace example house (new build) used at first in the studies, resulted in a functional Passive House[1] in almost all locations. At the same time minimum requirements for thermal comfort and prevention of moisture accumulation were met. In order to test the suitability of these component qualities for refurbishments the method was also applied to several variations of another example building, a typical 3-storey Wilhelmenian-style residential building in a historic city quarter. For this building a full refurbishment with Passive House components (with remaining thermal bridges) as well as refurbishment with interior insulation was analyzed. In additional studies only one component was refurbished as could be the case in step-by-step renovations or if selected measures are not possible because of cultural heritage restrictions. The resulting cost-optimal component qualities were often even better than for the example newbuild (see Figure 2). This can be explained by the longer heating period in less efficient buildings. Thus an individual improved building component can save more energy over the course of a year than in a Passive House, making it even more economic to invest in better quality. However, as the effect was found not to be highly significant and depends on individual building surroundings, it is not taken into account for the general international EnerPHit component requirements, as not to overcomplicate the matter.

Figure 2.Cost optimal component quality (U-value) for
basement ceiling insulation for a new building (top) and a historic building in
which only the basement ceiling can insulated (below). In the historic building
with only partial refurbishment the economic optimum is at a higher insulation
thickness than for the new building.
As
different component requirements for each location in

Figure 3. European climate zones map for EnerPHit requirements.
PHI plans
to put the international EnerPHit criteria into effect in the second half of
2014. A draft version is planned to be published on the PHI website www.passivehouse.com in April. Certification of some
pilot projects by PHI will already be possible based on this draft version.
3ENCULT proposes to the targeted before mentioned entities to use the experience and results of the project not as a "standard solution", but rather as a pool of possible measures and tools, along with guidelines on how to incorporate those into a historic building.
[1] Efficient Energy for EU Cultural Heritage, funded within FP7, GA No. 260162, www.3encult.eu
[1] A functional Passive House can be conditioned by solely heating or cooling the amount of fresh air, which is necessary for hygienic reasons.