Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
VeronikaFöldváryPhD studentSlovak University of Technology in Bratislava, Faculty of Civil Engineering, Slovakiaveronika.foldvary@centrum.sk | Lucia BorisováPhD studentSlovak University of Technology in Bratislava, Faculty of Civil Engineering, Slovakiaborisovalucia@gmail.com | DušanPetrášProfessorSlovak University of Technology in Bratislava, Faculty of Civil Engineering, Slovakia |
This
article analyzes the actual condition of building constructions, building
equipment and heating system of apartment buildings. Two apartment buildings
are compared; the first building is before renovation and it uses its own
boiler to generate energy for heating, the second building was recently
reconstructed and the energy for heating is supplied by a central heat source After
the insulation of building was carried out, economic and energy savings measures
were suggested in order to renovate the building and to find out probability of
the same. Moreover, the residents of the two apartment buildings completed
questionnaires regarding building constructions, indoor environment and
ventilation behavior, and a connection was made between the energy saving
measures and the subjective evaluations in order to investigate the impact of
the renovation on perception of the indoor environment.
The investigated apartment buildings are situated in Bratislava, Slovakia. They contain flats with two and three rooms on each floor, and there are eighty flats in each building in total. The construction height of a typical floor is 2.8 metres. Figure 1 shows the buildings before and after the refurbishment [1].
a) | b) | ||
Figure 1. Front sides of the two buildings: a) Before refurbishment b) After refurbishment. [1] |
The building
construction is in original condition. The walls are made of aerated concrete
with the thickness of 0.3 m, which does not fulfill current technical standards
on thermal insulation, because of the criteria on thermal insulation much lower
in the time when the building was built. Fifty percent of windows have been replaced
with energy efficient windows with plastic frames and the heat source was
renovated significantly in 2009, when the building was disconnected from
district heating and a local heat source for heating and domestic hot water
(DHW) was built in a boiler room located in the apartment building.
Energy
saving measures were carried out on an identical
apartment building, adjacent to the apartment building in original condition. The
envelope of the building was insulated with foam polystyrene with the thickness
of 0.08 m. Insulation of the roof is made of mineral wool, with the thickness
of 0.05 m. All of the old windows were replaced by new energy efficient
windows with a plastic frame, except for the entrance door and windows on the
first floor. After renovation the U-value improved significantly and currently
it satisfies the requirements on thermal protection in accordance with Slovak
standards.
Table 1. Comparison of heat transfer
coefficients before and after refurbishment. [1]
U-value (W/m².K) | ||
Construction
| BEFORE | AFTER |
Facade | 0.78 | 0.31 |
Side walls | 0.74 | 0.29 |
Roof | 0.28 | 0.2 |
Old
wooden windows | 2.4 | 1.3 |
Original
doors to loggias | 2.4 | 1.5 |
A
significant decrease of heat loss after insulation and replacement of the
windows can be seen in Figure 2. The specific heat loss by heat
transmission (HT) decreased by 40%, while the specific heat loss by
infiltration (HV) decreased by 45% after replacement of the windows,
compared to the situation before refurbishment.
a) | b) | ||
Figure 2. Comparison of specific heat loss before and
after implementation of the energy saving measures. a) transmission,
b) ventilation. [1] |
Energy
certification of these two buildings was carried out in 2012 in accordance with
Slovak laws and regulations. Energy need for heating was optimized after
implementation of energy saving measures of the building after refurbishment.
Energy need for DHW increased in the refurbished apartment building, because of
insufficient insulation of the distribution pipes.
Table 2.Energy
certificate of apartment houses before and after refurbishment.
Monitored data | Building before refurbishment | Energy | Building after refurbishment | Energy | ||
Heating
| Energy
need for heating system | | 597 235 kWh/a | C | 390 992 kWh/a | B |
Specific
energy requirement | 70 kWh/m².a
| 45.6 kWh/m².a | ||||
DHW | Energy
use for DHW | | 143 960 kWh/a | D | 143 960 kWh/a | D |
Specific
energy needs | | 45 kWh/m².a | 51 kWh/m².a | |||
Primary
energy | | 150 kWh/m².a | | 125 kWh/m².a | | |
CO2
emissions | | 26.45 kg/m².a | 22.08 kg/m².a | |||
Total
energy | | 115 kWh/m² | C | 96 kWh/m² | C |
The data to
compare the cost of heating are for the year 2010. Following figures compare
the cost of heating in the apartment building connected to district heating
with the cost of heat in the apartment building with own local heat source.
The cost of
heat generated in the local heat source is lower than the cost of heat
generated by district heating, when the saving per GJ is up to 44% in the building
with own local heat source.
Figure 3.Cost of
heating for the apartment building with own local heat source (left) and the building
connected to a district heating system (right). [1]
The measured energy consumption in 2010 shows that the energy consumption
of the building before refurbishment was about 28% higher than the total energy
consumption of the refurbished building.
Figure 4.Comparison of heating costs for the two apartment buildings in 2009 and
2010. [1]
Figure 5 shows comparison of the measured
energy consumptions of the buildings in 2010; the results are shown separately
for each floor. The difference between the highest and the lowest heat consumption
of flats was about 40% in the building before refurbishment, causing dissatisfaction
between residents of the building. On the other hand, the highest difference in
heating costs was only 12% in the apartment building after refurbishment with
the insulated facade and roof.
Figure 5.Comparison of measured heat consumption in flats. [1]
After
implementation of an energy saving project it is often found that the energy
consumption has increased one or two years after refurbishment. Energy
monitoring is a management tool to keep the energy consumption at low level and
to prevent the energy consumption increase after the refurbishment. It is based
on a regular readout of the energy meters. In the present case the energy
monitoring was performed by the Ensi EAB 8.1
software, developed in Norway. The energy consumption depending on mean daily
outdoor temperature (or eventually it can be also mean weekly outside
temperature if the readout is done on weekly basis) is graphically represented
by the ET-curve (Energy-thermal curve). The energy consumption for heating in Figure 6 is represented by the sloped line, whereas the horizontal line
represents the energy consumption for DHW, which does not depend on the outside
temperature. Figure 6 shows that the calculated weakly
consumption dropped from 5.19 kWh/(m².week) to 4.00 kWh/(m².week)
in the insulated building, at the mean daily outside temperature of 0°C. The hot
water consumption is higher in the refurbished building, because of the insulation
of horizontal pipes being too old and damaged (insulation of DHW distribution
pipes was not part of the refurbishment).
Figure 6.ET-curve of the two
apartment buildings. [1]
In order to
achieve comfort of the occupants in the enclosed environment, it is necessary
to fulfill several requirements at the same time. A questionnaire survey was
performed by the occupants of the buildings, containing questions regarding
various aspects of their indoor environment to allow complex assessment of
their satisfaction with their living environment.
The questionnaires
used to evaluate the indoor environment and the condition of building
constructions consisted of four main parts, containing questions regarding building
constructions, indoor environment, natural ventilation and basic information about
occupants. The questionnaire survey was conducted in January 2012 and was completed
during working days in the period from 04.00 pm to 07.30 pm [2].
Evaluation of
thermal comfort was carried out using the seven-point thermal sensation scale, as
defined in EN15251 and EN ISO 7730. The results are shown in Table 3.
Table 3.Evaluation of thermal sensation and thermal
comfort.
Indicator | Before refurbishment | After refurbishment |
PMV index | 0.74 | 0.92 |
PPD index | 16.57% | 22.88% |
Perception
of temperature | 0.14 | 0.52 |
Figure 7shows that the greater part of men and women prefer
moderately warm clothing in apartment building before refurbishment. Majority
of women prefer moderately warm clothing and greater part of men prefer light clothing
in apartment building after refurbishment.
a) | b) | ||
Figure 7. Typical clothing ensembles of residents in the apartment buildings. a) Before refurbishment. b) After refurbishment. [2] |
In both
apartment buildings the inhabitants have the possibility to set the air temperature
in each apartment. The following charts show how often people adjust the
temperature in their apartments.
a) | b) | ||
Figure 8. Utilization of temperature settings in
apartment buildings: a) Before refurbishment b) After refurbishment. [2] |
The energy need for heating system in the apartment building after refurbishment can be
classified into a better energy class. Residents of the refurbished apartment
building perceived the thermal conditions in the building as more acceptable
than residents of the apartment building before refurbishment. The present study indicated that refurbishment of a building can contribute to
the improvement of the indoor environment, however, it must be planned and
implemented with care, otherwise it might affect the
indoor environment adversely.
This
publication was supported by the Scientific Grant Agency of the Ministry of
Education of the Slovak Republic and the Presidency of the Slovak Academy of
Sciences(VEGA 1/1052/11).
[1]BORISOVÁ,
L.: Energetický audit, certifikácia
a monitoring bytovéhodomupred a poobnove, Diplomovápráca 2012
[2]FÖLDVÁRY,
V.: Hodnotenieenergetickejnáročnosti a tepelnéhostavubytovéhodomupred a poobnove, Diplomovápráca 2012
[3]DAHLSVEEN,
T. – PETRÁŠ, D.: Energetický audit a certifikáciabudov. Vydavateľstvo JAGA GROUP s. r. o., Bratislava 2008
[4]Ferenčík, K. Odstráneniesystémovýchporúch a zatepleniebytovéhodomu, Podzáhradná45-49, Bratislava..Bratislava: Správa domov SBD
Bratislava II, spol s.r.o,
[5JOKL, M.: Zdravé
obytné a pracovné prostředí. Česká matice technická, ročník
CVII 2002
[6]STN EN 15251
Vstupné údaje o vnútornom prostredí budov na navrhovanie a hodnotenie
energetickej hospodárnosti budov – kvalita vzduchu, tepelný stav prostredia,
osvetlenie a akustika
[7]STN 730540-2,
STN 730540-3 Tepelnotechnické vlastnosti stavebných konštrukcií a budov. Tepelná
ochrana budov. Časť 2 a 3.
[8] STN EN ISO
13790 Tepelnotechnické vlastnosti budov. Výpočet potreby energie na
vykurovanie.
[9]STN EN ISO 13788
- Tepelnovlhkostné vlastnosti stavebných dielcov a konštrukcií. Vnútorná
povrchová teplota na vylúčenie kritickej povrchovej vlhkosti a kondenzácie
vnútri konštrukcie. Výpočtová metóda.
[10]STN EN ISO
13789 - Tepelnotechnické vlastnosti budov. Merný tepelný tok prechodom tepla a
vetraním. Výpočtová metóda.
[11]ISO EN 7730
Moderate Thermal Environments
[12]PUSTAYOVÁ, H. – PETRÁŠ, D.: Effect of refurbishment on thermal comfort and energy use in residential multifamily building.REHVA European HVAC Journal Vol.49, Iss.6.
Follow us on social media accounts to stay up to date with REHVA actualities
0