Keywords: radon; residential buildings; indoor air quality; analytical modeling; mass balance; ventilation control; interzonal airflow; building management systems
|
|
|
|
|
|
Alireza Afshari | Samira Rahnama | Mohammad Kiani-Moghaddam | Torben Valdbjørn Rasmussen | Jakob Schytte Nymann Jørgensen | Henrik N. Knudsen |
Department of the Built Environment (BUILD), Aalborg University, Copenhagen, Denmarkaaf@build.aau.dk | Department of the Built Environment (BUILD), Aalborg University, Copenhagen, Denmark | Department of the Built Environment (BUILD), Aalborg University, Copenhagen, Denmark | Department of the Built Environment (BUILD), Aalborg University, Copenhagen, Denmark | Department manager software, ReMoni, Horsens, Region Midtjylland, Danmark | Department of the Built Environment (BUILD), Aalborg University, Copenhagen, Denmark |
Radon is a naturally occurring radioactive gas produced by the decay of uranium in soil, rock and some mineral-based construction materials [1-3]. Because it is colorless, odorless and tasteless, an elevated indoor concentration cannot be recognized without measurement. Radon can enter through cracks, joints and service penetrations in ground-contact structures and can accumulate when its entry rate is high relative to the removal provided by air exchange. Long-term exposure is associated with an increased risk of lung cancer, making radon an important indoor-environmental issue [4,5].
Danish guidance and building regulations therefore require radon-resistant construction and the use of mitigation when indoor levels are elevated [6,7]. Ventilation is one available mitigation measure, but its effect is not constant. Outdoor radon, soil-gas entry, leakage between rooms, material emissions and radioactive decay act simultaneously. Wind and the indoor-outdoor temperature difference also alter pressure and airflow through the envelope and ground-contact constructions [8-10]. Consequently, a fixed airflow cannot ensure an acceptable radon concentration at every operating condition.
Continuous measurement identifies changes in concentration but does not by itself separate the underlying sources and mechanisms. Conversely, a physical model can organize those mechanisms and evaluate how a ventilation change affects concentration in a selected room. This is particularly useful for ventilation control, where the relevant decision is the airflow needed at a given time rather than the use of permanently high ventilation. The objective of this study is therefore to formulate a transparent analytical radon model, extend it with a direct ventilation-control law and examine both components in a monitored dwelling.
The model is mainly based on a multi-source transient mass balance with an explicit control calculation. The model distinguishes outdoor-air transport, soil entry, material emission and interzonal exchange, while the controller acts only when the calculated concentration is above the target value. The full equations and nomenclature are retained in the appendices so that the main text can focus on the method, case application and interpretation of the results.
The study combines experimental investigation with analytical modeling. Measurements were obtained in an occupied detached single-family house containing a basement and a ground floor. Monitoring covered indoor radon, air temperature, carbon-dioxide concentration and ventilation-related quantities. Measurements conducted in the dwelling provided information on airflow between zones (rooms). These data were used to define model inputs, examine the calculated radon trajectory and evaluate the proposed control logic. The bedroom on the ground floor was selected as the object zone because it represents a room with prolonged occupant exposure. Its dimensions were 4.8 m by 3.5 m with a height of 2.33 m, giving a modeled volume of 39,144 m³. The bedroom exchanges air with outdoors and with an adjacent room, while the building configuration also allows radon originating beneath the building to influence the indoor concentration. The house layout, monitored zones, and bedroom selected for radon modeling and control are shown in Figure 1.

Figure 1. Plan of the detached house showing the monitored zones and the bedroom selected for radon modeling and controlling the object room.
The modeling procedure was implemented in two stages. First, a dynamic analytical expression was used to calculate the radon concentration in the bedroom from the identified source and removal terms. The model was then expanded stepwise to examine the influence of temperature difference, wind, material emission and adjacent-room leakage. Second, the complete source representation was connected to a threshold-activated controller. The controller estimated the airflow required to bring concentration back to the selected target value and converted that value into a mechanical-ventilation command after deducting wind- and stack-driven airflow.
The indoor-radon model is based on conservation of mass for the object room, radon transported with outdoor ventilation, radon carried by soil gas, emissions from material indoors and radon entering with air from an adjacent zone form the source side of the balance as well as ventilation, interzonal outflow and radioactive decay form the removal side. A transient term preserves the influence of the initial indoor concentration and describes the approach toward the concentration associated with the current source and airflow conditions.
The effective outdoor-air supply is represented as the sum of mechanical ventilation and contributions through leaks driven by wind and temperature difference. Soil-gas entry is updated with the same environmental drivers, using separate coefficients. Total room airflow also includes exchange with the neighboring room. This produces the complete expression for bedroom concentration together with three auxiliary airflow relationships. The full analytical formulation is provided as Equations (1) through (4) in the Supplementary Material accompanying the digital version of this article, together with the definition and unit of each symbol.
The control strategy uses the radon estimate and a predefined target concentration. When the estimate is at or below the target value, the existing ventilation command is retained. When the estimate exceeds the target value, the combined internal source is inferred from the current mass balance. The required effective ventilation is then obtained analytically from the steady-state form of the model. Finally, the uncontrollable wind- and temperature-driven contribution is subtracted to obtain the mechanical airflow request.
This formulation is explicit and does not require an iterative solver or empirical PID tuning. Its output is a continuous airflow command, while activation remains rule based. The controller equations comprise the error definition, the two operating cases, the aggregate source calculation, the required effective airflow, the mechanical ventilation command, and the percentage change in ventilation. Equations (5)—(11), together with the corresponding control nomenclature, are provided in the Supplementary Material accompanying the digital version of this article.
The dataset contained 121 available time steps. The measured concentration of radon in the bedroom varied from 22.1 to 220.6 Bq/m³ and exceeded 100 Bq/m³ in 41-time steps. The first model calculation neglected both wind speed and the indoor-outdoor temperature difference. Under this assumption, the estimated series closely followed the measured series (Figure 2). Because the soil-entry term was inferred from the same observations, this agreement represents a calibrated reconstruction rather than independent, out-of-sample validation.

Figure 2. Comparison of measured bedroom radon concentration with the model estimate obtained when wind speed and the indoor-outdoor temperature difference are neglected.
The top panel of Figure 3 compares the estimated radon concentration obtained by neglecting both weather-related drivers with the estimates obtained when the indoor-outdoor temperature difference or wind speed is included separately. The temperature-difference term causes a relatively small reduction for most time steps, whereas wind speed has a larger influence, particularly during periods with higher calculated concentrations. The middle panel of Figure 3 shows that adding radon emitted by building materials produces a small but consistent upward shift relative to the estimate that includes wind speed and temperature difference only. The bottom panel then adds airflow from the adjacent room. This interzonal contribution can either increase or decrease the radon estimation in the bedroom, depending on the concentration difference between the two rooms.
|
|
|
Figure 3. Stepwise influence of model components on the estimated bedroom radon concentration: top—temperature-difference and wind-speed effects; middle—radon emissions from building materials; bottom—air leakage from an adjacent room. |
With wind speed, temperature difference, material emission, and interzonal leakage included, the uncontrolled model exceeded the 100 Bq/m³ reference level in 9 of 121-time steps and reached a maximum of 127.4 Bq/m³. Figure 4 compares this uncontrolled trajectory with the 100 Bq/m³ WHO reference level and the corresponding trajectory after applying the ventilation-control signal. All nine exceedances were reduced to the target value, giving a controlled maximum of 100 Bq/m³ and a 21.5% reduction in the highest modeled value. During time steps below the target, the radon-driven controller did not request an increase.

Figure 4. Estimated bedroom radon concentration before and after applying the ventilation-control signal, shown against the 100 Bq/m³ WHO reference level. The controlled trajectory is simulated.
The control calculation is a simulation based on case-study measurements and calibrated parameters. It shows how the analytical model can translate concentration exceedance into an airflow request, but it is not a measured closed-loop experiment. Fan electricity, heating demand and actual post-control radon were not recorded as part of this analysis. Accordingly, the case supports the feasibility and transparency of the method, while verified energy savings and general performance across residential buildings require a separate field demonstration.
A multi-source analytical balance model was developed to estimate and control indoor radon level by providing the necessary direct ventilation rate command for residential rooms. The case study shows that wind and interzonal exchange can materially alter the indoor radon concentration, while emissions from indoor materials contribute with a smaller background increase. In simulation, the controller calculation was shown to be able to remove all modeled exceedances above 100 Bq/m³ and acted only when the target value was exceeded. The approach is transparent and suitable for control-oriented implementation, but independent validation, measured post-control radon and energy monitoring are necessary before broader performance claims are made.
The authors gratefully acknowledge financial support from Realdania and Landsbyggefonden.
[1] Abdo, M.A.S., Boukhair, A., Fahad, M., Ouakkas, S., Benjelloun, M., 2020. Radon exposure assessment and its decay products aerosols in some houses of the province of El Jadida, Morocco. Air Quality, Atmosphere & Health 14, 129-137.
[2] Amrani, D., Cherouati, D.E., 2006. Radon exhalation rate in building materials using plastic track detectors. Journal of Radioanalytical and Nuclear Chemistry 242, 269-271.
[3] Chao, C.Y.H., Tung, T.C.W., Chan, D.W.T., Burnett, J., 1997. Determination of radon emanation and back diffusion characteristics of building materials in small chamber tests. Building and Environment 32, 355-362.
[4] NRC, National Research Council, 2006. BEIR VII: Health Risks from Exposure to Low Levels of Ionizing Radiation.
[5] WHO, 2005. Guidelines for Drinking-Water Quality, third ed. World Health Organization Press, Geneva.
[6] Erhvervs- og Byggestyrelsen, 2007. Radon og enfamiliehuse. Copenhagen, 15 p.
[7] Erhvervs- og Byggestyrelsen, 2010. Bygningsreglement 2010. Copenhagen, 253 p.
[8] Seyis, C., Inan, S., Yalcın, M.N., 2022. Major factors affecting soil radon emanation. Natural Hazards 114, 2139-2162.
[9] Saad, A.F., Abdallah, R.M., Hussein, N.A., 2018. Physical and geometrical parameters controlling measurements of radon emanation and exhalation from soil. Applied Radiation and Isotopes 137, 273-279.
[10] Stranden, E., Kolstad, A.K., Lind, B., 1984. The influence of moisture and temperature on radon exhalation. Radiation Protection Dosimetry 7, 55-58.
The complete transient model used in the study is reproduced below. Equation (1) gives indoor-radon concentration in the target room. Equations (2)-(4) define total airflow, weather-adjusted ventilation and weather-adjusted soil entry, respectively.
| (1) |
(2) | |
| (3) |
| (4) |
Symbol | Definition | Unit |
| Indoor radon concentration in the target
room at time |
|
| Initial radon concentration in the target room |
|
| Outdoor radon concentration at time |
|
| Radon concentration in soil gas at time |
|
| Indoor radon concentration in the
adjacent room at time |
|
| Effective outdoor-air ventilation of the target room |
|
| Effective soil-gas entry airflow |
|
| Interzonal airflow from the adjacent room |
|
| Mechanical ventilation airflow |
|
| Total airflow used in the room mass balance |
|
| Radon generation rate from indoor materials |
|
| Volume of the target room |
|
| Radon radioactive decay constant |
|
| Time / model time step |
|
| Wind speed |
|
| Indoor-outdoor temperature difference |
|
| Wind-driven ventilation coefficient |
|
| Stack-driven ventilation coefficient |
|
| Wind-driven soil-entry coefficient |
|
| Stack-driven soil-entry coefficient |
|
Equations (5)-(11) define the threshold-activated controller. Equation (5) defines the control error; Equations (6)-(7) retain the current command below the target; Equations (8)-(10) calculate the aggregate source, required effective airflow and mechanical command; and Equation (11) expresses the relative ventilation change.
| (5) |
| (6) |
| (7) |
| (8) |
| (9) |
| (10) |
| (11) |
Symbols already defined in Appendix A retain the same meanings and units.
Symbol | Definition | Unit |
| Difference between estimated radon and the control target |
|
| Selected radon target concentration |
|
| Aggregate internal radon inflow excluding outdoor air |
|
| Current effective ventilation before control |
|
| Required effective ventilation after control |
|
| Current mechanical ventilation command |
|
| Required mechanical ventilation command |
|
| Relative change in mechanical ventilation |
|