Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Full version of this article is available at
the Journal website www.rehva.eu-> Rehva Journal



Manufacturers
of air handling units (AHUs) continuously improve the electrical and thermal
efficiency of their systems. These efforts include the optimization of energy
recovery. The new GEA multiple counterflow principle is intended to achieve
high energy-recovery coefficients in conjunction with low pressure drop.
Additionally, the new system allows a bypass cycle that prevents pressure drop
in the energy-recovery system with free cooling – and offers various
possibilities for frost protection. The authors describe the energy costs of
several frost protection solutions, in accordance with various climate
conditions.
Energy-recovery
systems in air handling units (AHUs) now on the market can in some cases
already satisfy the high levels of heat-recovery efficiency stipulated by the
upcoming ErP Directive. It is important to note, however, that greater heat-recovery
efficiency – as a rule – is also associated with greater pressure drop, with
negative effect on power consumption. In addition, increasing heat-recovery
efficiency will cause extract air to be cooled nearer to the outdoor
temperature. This extract air has greater humidity than the outdoor air. On
winter days with freezing temperatures, condensate from the extract air may
develop on cold surfaces of the energy-recovery system. High heat-recovery
efficiencies and therefore lower outgoing air temperatures accordingly raise
the risk of ice formation in the energy-recovery system. This, in turn, leads
to reduced effectiveness and to even greater pressure drop. The objective is
therefore to reach a satisfactory compromise among high levels of heat recovery,
low pressure drop, and effective frost protection, to enhance the total
efficiency of an air handling unit.
This new
energy-recovery system should offer a high heat-recovery coefficient and, at
the same time, should be easily kept free of ice. Also desirable here is an
energy-recovery system that can be simply circumvented in free cooling mode, so
that the system does not cause pressure drop in the transitional period. The
GEA multiple counterflow heat exchanger, now in development, offers all these
characteristics with a heat-recovery coefficient of more than 80%.
The GEA
multiple counterflow heat exchanger is based on a solution with several layers
or levels, and with a modular-configured counterflow principle (see Figure 1).
If use of
the energy-recovery system is not essential, the bypass flaps open on the
supply-air and on the extract-air side, and the air flows unimpeded pass the
energy-recovery heat exchanger – for example, in free cooling mode. During
operation of the energy-recovery system, typical pressure drop can be expected
at the order of magnitude of Δp = 80 – 140 Pa (at an AHU face
velocity of 1.5–2 m/s).
Multiple
counterflow technology offers a selection from various feasible continuous
frost-protection variants. Alternatives 1–5 are described and illustrated
below.
1. Opening
of the outside-air bypass (Figure 1), in accordance with the value
given by a surface-temperature sensor, with setpoint value ≥ 0°C.
2. Configuration
as shown in Figure 1; but instead of a fixed setpoint
≥ 0°C, the system takes the dewpoint temperature of the extract air into
account. If there is no risk of condensation in the extract air, frost
protection remains out of operation.

Figure 1.
Frost protection by ourdoor air bypass.
3. Preheating
of the outside air, without re-heater. Before its entry into the multiple
counterflow heat exchanger, the outside air is pre-heated to −2°C. (Figure 2).

Figure 2.
Frost protection with preheating of outdoor air.
4. Preheating
of the extract air, to prevent the outgoing air temperature from falling below
2°C. (Figure 3)

Figure 3.
Frost protection with preheating of extract air.
5. Recirculation
of outside air for preheating of this air to −2°C before entry into the
multiple counterflow heat exchanger, by admixture of supply air (Figure 4).

Figure 4.
Frost protection with recirculation.
The
selection of the most effective frost-protection strategies to be used will
depend in good part on the climate conditions of the installation location. The
following will illustrate these interrelationships by describing simulation of
the various frost-protection strategies for different climate conditions.
Simulations are based on the following data:
·
GEA
CAIRplus® SX 096.064 AHU
o
Maximum
air flow: 4,000 m³/h
o
Air
velocity in free cross-section: approx. 1.8 m/s
o
Energy
recovery system: GEA multiple counterflow; heat-recovery coefficient 0.807 at
balanced air flows
o
No
cooling coil
o
Fan
efficiency: 60%
·
Additional
equipment for frost-protection types 3 to 5: secondary-circuit pump for the
heater
·
Operation:
8,760 h/a at full load
·
Supply-air
temperature: 17.7°C; extract-air temperature: 22°C
·
Humidity
load: + 1.5 g/kg
Energy
prices were assumed to be 0.06 €/kWh for heat and 0.18 €/kWh for
electricity.
At the
Mediterranean location of Barcelona, the outside temperatures are so high that,
even on winter days, frost protection is not necessary.
The
simulation situation for Frankfurt am Main is more differentiated. The most
expensive frost-protection variant was no. 4, with extract-air preheating,
in which the heating and power costs added to 3,773 €/a. This variant is
not practically relevant, since heating of the extract air to 54.3°C would be
necessary. The supply-air temperature would in this case rise to 42°C. To
reduce the flow of supply air to comfortable temperature levels, the air would
have to be cooled – or cold outside air would have to be mixed in. Neither
solution would be technically feasible.
On the
basis of prevailing outside winter temperatures, variant no. 5, with 3,399 €/a,
would be the most cost-effective: i.e., for outside-air recirculation. This is
effective only for temperatures down to approx. −9°C at maximum recirculation of 45%.
During cold winters, temperatures can fall below this limit. Raising the
recirculation rate would result in higher costs.
The
remaining variants nos. 1, 2, and 3, feasible for Frankfurt, would lead to
slightly different energy costs of 3,550 €/a, 3,587 €/a, and 3,436 €/a,
respectively. The energetically most favorable solution – i.e., preheating of
the outside air – does not feature a re-heater and therefore allows only supply
air temperatures below the extract air temperature (here approx. 18°C). This is
usually sufficient due to existent internal loads and additional systems for
individual temperature control in the particular zones of the building. An
extra re-heater would mean additional investment and operating costs due to
further pressure drop. For variants 1 and 2, on the other hand, the re-heater
is already available. With respect to flexibility of the supply air
temperature, solutions with frost protection via outside-air bypass are
advisable; with respect to operating costs, however, variant no. 3 applied
without re-heater is the most favorable.
The exclusion
criteria applied for Frankfurt am Main also apply to Moscow, which is much
colder in winter (daily low outside temperatures of down to −24°C, according to weather
statistics). Variants 1 to 3 would be feasible for selection here as well. Of
these three options, the purely temperature-controlled outside-air bypass
(variant 1) would represent by far the most expensive. The air heater in
this case would necessarily provide heating duty of 56 kW to raise the air
temperature to 17.7°C, due to heat recovery being completely bypassed under
extreme winter conditions.
If surface
dewpoint temperatures were used to control the bypass (variant no. 2), the
operating costs would be 26% lower compared to the purely
temperature-controlled outside-air bypass (variant no. 1) – and would
moreover represent the strategy with minimal expenses. The bypass would be in
operation 500 h/a less, and the flap would never have to be opened 100%.
This is because a temperature drop below the dewpoint could hardly be expected,
owing to the dry cold in conjunction with the assumed humidity load of only 1.5 g/kg.
For cases with higher humidity load or AHUs with humidifiers, the results would
be worse and tend more to those of variant 1.
For the
case of frost protection by outside-air preheating, the operating expenses
would not be even 5% more expensive than variation no. 2. Despite the
disadvantage of only being able to provide supply air temperatures below the
exhaust air temperature if no additional re-heater is applied, a factor in
favor of outside-air preheating is the fact that the outcome of energy
consumption is independent of extract-air humidity. For this reason, this
variant is likewise advisable – or in cases with humidification – even
superior. This solution is also supported in terms of investments by the fact
that the heating coil and the heat generator can be dimensioned at 30 kW,
which is 46% less than required for variant 1 or 2. A detailed consideration of
the individual case may lead either to the most economic variant of dewpoint
controlled bypass, or to outside-air preheating.

Figure 5
The operational cost (heat and electricity) of frost protection in the case
study with an air handling unit of 4 000 m³/h.
These
simulations reveal that one preferable frost-protection strategy for all of
Europe is not possible. Only extract-air preheating and outside-air
recirculation do not come into consideration at all. The multiple counterflow
solution enables the possibility of implementing two cost-effective
frost-protection strategies, high heat-recovery coefficients, and low-loss free
cooling. Product launch of the new GEA multiple counterflow system is scheduled
for late 2013.
Follow us on social media accounts to stay up to date with REHVA actualities
0