Keywords: occupancy profile, cluster analysis; neural network; supermarket

Maliheh Jahanbakhsh1
Kaiser Ahmad2,3
Tuomo Niemelä4
Jarek Kurnitski2
Risto Kosonen1
maliheh.jahanbakhsh@aalto.fi

 

 

 

 

1 Department of Civil Engineering, Aalto University, Finland
2 Department of Civil Engineering and Architecture, Tallinn University of Technology, Estonia
3 Department of Civil Engineering, Tampere University, Finland
4Department of Consultancy, Granlund Oy, Finland

 

 

Occupancy profiles are important for both system sizing and energy analysis. This study provides a data-driven foundation for occupancy profiles to conduct more accurate design for HVAC systems in supermarkets. In this study, we propose new occupancy profiles for weekdays, Saturdays, Sundays, or holidays.

Introduction

Finland aims for carbon neutrality by 2035, while heating and cooling account for 40% of total energy consumption (Söderholm et al., 2025). Supermarkets are among the highest energy-consuming buildings, with energy use strongly influenced by occupant presence and behavior (Ahmed et al. 2017). Occupancy-based control can improve energy efficiency (Hoes et al. 2009; Virote and Neves-Silva 2012; Lee and Malkawi 2014; Yousefi et al. 2017; Almeida et al. 2025).

Building energy simulations often use Occupancy Profiles (OPs) from codes and standards. However, occupant behavior has changed, causing discrepancies between standard schedules and actual occupancy (Tahmasebi and Mahdavi 2017; Mitra et al. 2020; Kang et al. 2021). Fixed schedules may therefore misrepresent peak occupancy and energy demand.

Updating standard OPs is essential for improving scheduling accuracy and supporting reliable energy simulation and peak power estimation (Tahmasebi and Mahdavi 2017). Significant variations between the highest and lowest occupancy levels introduce uncertainty in peak loads and energy system sizing (Gram-Hanssen 2010; Djunaedy et al. 2011; Chen et al. 2023). This is particularly important for supermarkets, where occupancy directly affects ventilation, dehumidification, energy consumption, and finally for HVAC system performance. Higher visitor numbers require increased airflow, increasing operational costs, while oversized HVAC systems may operate inefficiently under part-load conditions and cause occupant discomfort (Burdick 2011).

To address these limitations, this study proposes new occupancy profiles using a novel deep learning-based framework to identify representative OPs and reduce the limitations of traditional distance-based clustering. The framework characterizes occupancy patterns across three day types: weekdays, Saturdays, and Sundays/holidays for Finnish supermarkets, supporting more accurate energy simulation and HVAC system sizing.

Methodology

This study examines six supermarket buildings in Finland. All supermarkets have more than 1,000 m² of sales area and are classified as large supermarkets (Uusitalo 1998). The group true data consisted of hourly shopping receipt counts. The hourly number of occupants was estimated as 1.6 times the number of receipts, based on data obtained from a building services and energy consultancy company. The datasets were provided by a Finnish building services company specializing in energy efficiency and building management systems. To derive representative OPs for three categories: weekdays, Saturdays, and Sundays/holidays, the six datasets were divided into training and test sets.

The training set included four supermarkets. Outliers were removed, the data were normalized, and the four datasets were combined into an integrated dataset for model development. The test set included Case 5 (2019) and Case 6 (2022). First, a Siamese neural network (SNN) captured nonlinear temporal and behavioral patterns through contrastive learning. Then, K-means clustering (Arthur and Vassilvitskii 2006) was applied to the learned representations to identify typical OPs for weekdays, Saturdays, and Sundays/holidays.

Results

In this study, we investigated the variation in HVAC sizing resulting from the selection of different occupancy levels, considering the 90th, 95th, 98th, and 100th percentiles and comparing them with the three representative OPs derived in this study. Fig. 1 presents the hourly occupancy levels corresponding to these percentiles for weekdays, Saturdays, and Sundays/holidays in the test cases, together with the representative OPs.

Using the 90th–95th percentile as a design reference can help maintain indoor thermal comfort during high-occupancy periods while reducing the risk of underestimation of HVAC system sizing. In contrast, the 100th percentile represents the maximum observed occupancy and therefore indicates the highest operational load experienced by the building systems. The results show that the representative OPs closely align with the 90th–98th percentile range across both weekday and weekend profiles, supporting their use as a practical design reference while avoiding potential over-dimensioning associated with absolute peak occupancy.

Figure 1. Different Percentile-based OPs for supermarkets in comparison with the typical profile: (a) Weekdays; (b) Saturdays; (c) Sundays/holidays.

Additionally, this study highlights a significant gap between standardized occupancy assumptions and actual occupancy patterns in Nordic supermarkets. This gap is examined in two ways: first, by analyzing percentile-based and typical profiles derived from the proposed model; and second, by comparing the international standards ASHRAE 90.1 (ASHRAE 2019), and EN 16798-1 (European Committee for Standardization 2019), with the empirical OPs.

A detailed comparison was conducted between the identified OPs and the profiles specified in these standards. Fig. 2 compares the typical OPs obtained in this study with those specified in ASHRAE 90.1 for retail stores and EN 16798-1 for department stores. While EN 16798-1 uses the same schedule for Saturdays and Sundays, the empirical profiles show notable differences in occupancy level, curve shape, and peak hours. The EN 16798-1 profiles have more gradual variations, but their weekend occupancy peaks sharply around 14:00. In contrast, Finnish supermarket occupancy remains relatively stable throughout the afternoon, showing greater similarity to the ASHRAE 90.1 weekend schedule. ASHRAE 90.1 shows an extended peak between 9:00 and 14:00, followed by a secondary peak that closely matches the modeled Finnish OP. Overall, EN 16798-1 better captures the general occupancy pattern of Finnish supermarkets than ASHRAE 90.1, although differences remain in the timing and magnitude of peak occupancy.

 

(a)

(b)

(c)

Figure 2. Comparison of typical OPs of large supermarkets in Finland with occupancy scheduling for department stores in EN 16798-1 and ASHRAE 90.1 for energy simulation: (a) Weekdays; (b) Saturdays; (c) Sundays/holidays.

Conclusion

This study addressed two major research gaps: the limited consideration of hourly variations in occupancy profiles (OPs) for large supermarkets and the lack of effective methods for extracting representative profiles. The findings show that standard OPs, such as ASHRAE 90.1, reasonably capture Saturday and Sunday occupancy patterns in Finnish retail stores but do not accurately represent weekday morning peaks in Finnish supermarkets. Although EN 16798-1 better reflects weekday occupancy patterns, it does not adequately capture weekend variations, which can significantly affect HVAC loads. Since the distinct occupancy patterns required for system sizing and energy simulations are not fully represented in EN 16798-1 or ASHRAE 90.1, the typical OPs developed in this study provide a more representative baseline of supermarket operation. These profiles can support more reliable energy simulations and HVAC sizing while reducing the risk of over-dimensioning caused by non-representative peak occupancy values.

References

Ahmed K, Akhondzada A, Kurnitski J, Olesen B (2017) Occupancy schedules for energy simulation in new prEN16798-1 and ISO/FDIS 17772-1 standards. Sustain Cities Soc 35:134–144.

Almeida F, Castelli M, Côrte-Real N, et al (2025) Smart energy strategies: Leveraging LSTM and LLMs for advanced energy management. Energy and AI 22:100642. https://doi.org/10.1016/j.egyai.2025.100642.

Arthur, D. and Vassilvitskii, S., 2006, June. How slow is the k-means method?. In Proceedings of the twenty-second annual symposium on Computational geometry (pp. 144-153).

ASHRAE (2019) Standard 90.1-2019 – Energy Standard for Buildings Except Low-Rise Residential Buildings.

Burdick A (2011) Strategy Guideline: Accurate heating and cooling load calculations.

Chen S, Lv Y, Wang Z, et al (2023) Typical daily occupancy profiles of express hotels and its stochasticity effect on building heating and cooling loads. Journal of Building Engineering 73:106775.

Djunaedy E, den Wymelenberg K, Acker B, Thimmana H (2011) Oversizing of HVAC system: Signatures and penalties. Energy Build 43:468–475.

European Committee for Standardization (2019) Energy performance of buildings - Ventilation for buildings - Part 1: Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics - Module M1-6. Brussels, Belgium.

Gram-Hanssen K (2010) Residential heat comfort practices: understanding users. Building Research & Information 38:175–186.

Hoes P, Hensen JLM, Loomans MGLC, et al (2009) User behavior in whole building simulation. Energy Build 41:295–302.

Kang X, Yan D, An J, et al (2021) Typical weekly occupancy profiles in non-residential buildings based on mobile positioning data. Energy Build 250:111264.

Lee YS, Malkawi AM (2014) Simulating multiple occupant behaviors in buildings: An agent-based modeling approach. Energy Build 69:407–416.

Mitra D, Steinmetz N, Chu Y, Cetin KS (2020) Typical occupancy profiles and behaviors in residential buildings in the United States. Energy Build 210:109713.

Söderholm N, Gröndahl M, Niemelä T, et al (2025) Validation of a Heat Pump System Model for Energy Recycling in Grocery Stores Through On-Site Energy Monitoring. Energies (Basel) 18:1003.

Tahmasebi F, Mahdavi A (2017) The sensitivity of building performance simulation results to the choice of occupants’ presence models: a case study. J Build Perform Simul 10:625–635.

Uusitalo, L., 2006. Consumption in postmodernity: Social structuration and the construction of the self. In The active consumer (pp. 215-235). Routledge.

Virote J, Neves-Silva R (2012) Stochastic models for building energy prediction based on occupant behavior assessment. Energy Build 53:183–193.

Yousefi F, Gholipour Y, Yan W (2017) A study of the impact of occupant behaviors on energy performance of building envelopes using occupants’ data. Energy Build 148:182–198.

Maliheh Jahanbakhsh, Kaiser Ahmad, Tuomo Niemelä, Jarek Kurnitski, Risto KosonenPages 44 - 46