Hans ErhornFraunhofer Institute for Building Physics (IBP), | Heike Erhorn-KluttigFraunhofer Institute for Building Physics (IBP), |
Susanne GeisslerSERA energy & resources e.U., | Peter WoutersBelgian Building Research Institute (BBRI), |
New buildings as well as the existing building stock must become much more energy efficient to achieve the EU energy and climate goals [1] envisaged for the years 2020, 2030 and beyond. In fact, it will be possible to almost completely cut emissions from residential and office buildings by around 90% in 2050, compared to 1990, if all efforts undertaken are successful. These efforts include quality of the works, meaning that it is not sufficient aiming at an excellent energy performance stated by design descriptions and energy calculations, but also at good quality of the works. Proper execution of building works according to plan and without errors is the precondition to achieve high building energy performance in reality, resulting in actual reductions in energy consumption and emissions. In this regard, experience shows that there are various cases where the quality of the works is an issue of concern, sometimes even causing major difficulties leading to higher expenses.
A report [2], written in the context of the IEE project QUALICHeCK, summarises critical situations on the construction site putting the careful execution and thus the high quality of works at risk. This is dealt with in the light of the importance of high quality constructions and their realisation on the building site in connection with the trend towards high performance buildings such as the nearly zero-energy buildings required by the Energy Performance of Buildings Directive (Recast) [3] for 2019 respectively 2021.
The QUALICHeCK source book [4] is available as draft version and aims to guide and support persons and organizations’ interested in determining whether a better enforcement of the quality of the works is needed. If it turns out to be relevant, the source book will help them to identify the possibilities and points for attention for implement a more effective enforcement framework.
In this respect, it is necessary to touch on a definition of terms briefly: What does Quality of the works mean? Work can be defined as a physical or mental effect or activity towards the production or accomplishment of something. In the context of this source book, works are all the activities directed to produce or refurbish a building. What is crucial in the context of this source book is that “quality of the works” for a given activity (e.g. installation of a PV system) has to be clearly defined. As such, one can come to a quite different set of specifications (“stated needs”) for the same activity and, in order to minimise the risk of disputes, one should try to minimise the number of implied needs, as different parties might have a completely different view on the implied needs.

Image: Cover page of the source book.
Table 1 presents particular findings from the QUALICHeCK project in an overview of reasons for good or poor quality of the works relating to practical procedures.
Table 1. analysis of reasons for good or poor quality of the works.
Aspects which are important for good quality of the
works | Reasons for good quality of the works | Reasons for poor quality of the works |
Clear description of work specifications | Target groups have clear instructions how to install
building and technical elements and what to consider | No consensus between target groups regarding
responsibilities |
Clear procedures to show evidence of compliance | From the beginning of the process a clear procedure
is defined to show the evidence | Unclear what are the criteria and who checks them |
Tracing procedures | A comprehensive continuous documentation allows
early recognition of faults | All documentation will be checked at the final stage
only, which does not allow the craftsmen to react in time |
Handling of innovative solutions | Continually trained and experienced craftsmen | Overstrained craftsmen who have not followed the
developments on the market |
Usability of the specifications in practice | The craftsmen understand clearly, what is expected
from them and where possible problems are | Incomplete specifications written in a difficult
language style |
Giving benefits to systems that have a high
probability to perform well | Easy to implement technology in combination with
other beneficial effects for the craftsmen | Technologies which need highly experienced craftsmen
for the installation and have no beneficial effects for the craftsmen |
Rewarding good practice | High motivation of the craftsmen | No sanctioning in case of poor quality of the works |
Specific issues for existing buildings | The specific challenges in existing buildings are
taken into account | Quality frameworks are not sufficiently specific |
Quality management approaches | Advantage of a reduced effort for daily compliance
procedures, if the company uses a collective compliance procedure | Too high costs for the compliance procedures leads
to failure to comply |
Market surveillance and integrating lessons learned | An organisation running a quality framework was
involved | Reasons can be of different nature: too low
requirements or too high and unnecessary costs |
Interrelation with European and national
legislations and standards | Possible synergies are investigated and made use of | Limitations are not respected causing refusal of the
procedures, thus hindering implementation |
In order to achieve good quality of the works, societal support is important, meaning that stakeholders understand and accept the need for energy efficiency requirements, the need for compliance and the need to check and enforce compliance.
A three-step approach has been identified in the QUALICHeCK source book how to achieve good compliance:
· There should be clear procedures what requirements must be fulfilled in order to achieve good quality of the works
· There should be clear procedures how to decide on compliance and related actions in case of non-compliance
· There should be effective control and penalties mechanisms to be applied in cases of non-compliance
The detailed description of these 3 steps is documented in the QUALICHeCK source book, as well as the handling of innovation as a key element for progress. The reader will find information how to implement second or third party control and enforcement frameworks without hindering innovation. Emphasis is also put on the fact, that control and enforcement schemes introduce always some extra costs, but as explained in the introductory part of this text, non-existence of control and enforcement schemes might be even more expensive.
During the next months, a review of the source book will be performed by public consultation of stakeholders. Please read the document on the QUALICHeCK project website http://qualicheck-platform.eu/2016/03/report-source-book-on-guidelines-for-better-enforcement-of-quality-of-the-works-draft/ and send feedback to the authors.
[1] European Commission: COMMUNICATION FROM THE COMMISSION TO THE EUROPEAN PARLIAMENT, THE COUNCIL, THE EUROPEAN ECONOMIC AND SOCIAL COMMITTEE AND THE COMMITTEE OF THE REGIONS. A policy framework for climate and energy in the period from 2020 to 2030. COM(2014) 15 final¸ Brussels, 22.1.2014.
[2] Erhorn, H.; Erhorn-Kluttig, H. and Doster, S.: Towards improved quality of the works - Documented examples of existing situations regarding quality of works. Brussels (2015), published at www.qualicheck-platform.eu
[3] European Union: DIRECTIVE 2010/31/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 19 May 2010 on the energy performance of buildings (recast). Official Journal of the European Union; 18.6.2010, L 153/13
[4] Erhorn, H.; Erhorn-Kluttig, H.; Geissler, S. and Wouters, P.: Source book on Guidelines for better enforcement of quality of the works. Brussels (2016), published at www.qualicheck-platform.eu

QUALICHeCK responds to the challenges related to compliance of Energy Performance Certificate (EPC) declarations and the quality of the building works. Find out more at http://qualicheck-platform.eu.
The QUALICHeCK project is co-funded by the Intelligent Energy Europe Programme of the European Union. The sole responsibility for the content of this article lies with the author(s). It does not necessarily reflect the opinion of the European Union. Neither the EASME nor the European Commission are responsible for any use that may be made of the information contained therein.