Keywords: Thermal comfort, Overheating, Residential building, Indoor temperature, Apartment, Monitoring data, Building simulation
|
|
|
Mats Persson | Joel André Slunitschek | Despoina Teli |
Department of Architecture and Civil Engineering, Chalmers University of Technology, Gothenburg, Sweden. Email: matsp@chalmers.se | Department of Architecture and Civil Engineering, Chalmers University of Technology, Gothenburg, Sweden | Department of Architecture and Civil Engineering, Chalmers University of Technology, Gothenburg, Sweden |
High indoor temperatures are an increasingly significant problem in Sweden, affecting comfort, health, and the energy system. During the record-hot summer of 2018, around 700 heat-related deaths are estimated to have occurred in Sweden, demonstrating that overheating is not only a matter of comfort but also a significant public health concern.
Ongoing climate change further exacerbates the problem. Trends show a clear increase in temperature in Sweden compared to the reference period 1961–2010, particularly in recent decades. The Swedish Meteorological and Hydrological Institute (SMHI) has estimated that extreme heat events, which so far have occurred every twenty years on average, may occur every three to five years by the end of the century. This implies a growing risk of overheating in buildings, which calls for both improved knowledge and effective mitigation strategies.
The Swedish housing stock is highly heterogeneous, with buildings from different time periods and varying technical characteristics. This means that overheating manifests differently across building types, and that mitigation strategies must be adapted accordingly. To address this complexity, we are conducting an interdisciplinary research project that combines engineering, architecture, sociology, and environmental psychology. The project is based on extensive measurement data from nearly 2,000 buildings and around 67,000 apartments, contributed by three large housing companies in Gothenburg. Sensors are typically installed in hallways or comparable areas to avoid direct sunlight exposure. Temperature readings were recorded every 15 minutes, and aggregated into hourly mean values for analysis.
A central issue in this work is how overheating should be defined. In Sweden today, guidance on overheating is limited. The Public Health Agency of Sweden specifies 26°C as the maximum indoor air temperature during summer, applying around the clock for vulnerable groups. For non-vulnerable groups, slightly higher temperatures may be accepted, but the extent is not specified. At night, the limit of 26°C applies to all occupants [1]. There are no clear requirements regarding how often or for how long this temperature may be exceeded. This differs, for example, from Finland, where new buildings are regulated based on the number of hours that the temperature exceeds a certain level. The lack of corresponding criteria in Sweden makes both the analysis and evaluation of overheating more difficult.
Several overheating assessment methods have been developed worldwide in response to the growing risk of overheating in buildings [2]. These methods are primarily intended for simulation studies and preventive design assessment. Applying them to large-scale monitoring datasets is more challenging, as analyses must account for occupant behaviour, real-world building performance, occupancy patterns, and data quality issues such as sensor drift and missing values [3]. Robust statistical and data management methods are therefore essential for reliable overheating assessment using monitoring data and constitute an important focus of the ongoing research project. In the analysis that follows, however, we use the currently applied threshold of 26°C as the reference value.
Analysis of temperature data from our dataset shows that the problem varies significantly between different years. During a comparatively typical year, such as 2024, the maximum indoor temperature in most apartments is around 26°C, with only a small proportion reaching 29–31°C. In an extreme year like 2018, however, there is a clear shift, with many apartments instead showing maximum temperatures around 28–29°C. Almost all apartments exceeded 26°C at least once during the summer (Figure 1).

Figure 1. Distribution of the maximum indoor air temperature in the apartments- for 2024 which represents a normal year, and for the record warm year of 2018.
Detailed analysis of hourly indoor temperatures during heatwaves (Figure 2) shows that overheating often builds up over several days, causing indoor temperatures to remain high even at night despite falling outdoor temperatures. This is particularly problematic from a health perspective, as it prevents recovery from daytime heat exposure and can lead to prolonged periods of thermal stress.

Figure 2. Hourly indoor air temperatures from 28 873 apartments during a heatwave period in 2018.
Differences between apartments are also substantial. During heatwaves, differences of up to 10°C can occur between apartments [4]. Some maintain a relatively cool and stable indoor climate, while others become severely overheated. An important explanation lies in building characteristics. In a comparison between an older and a newer building (Figure 3), the older building—with higher thermal mass—demonstrated a greater ability to dampen temperature variations and maintain lower indoor temperatures, while the newer building showed greater variation, with some apartments closely following outdoor temperature fluctuations.
|
|
Figure 3. Indoor air temperature at hourly timesteps in all apartments of two buildings of different construction years during the week 12–18 June 2023: (a) 1890 and (b) 2016. | |
A closer analysis of the newer building shows how overheating varies within the building (Figure 4). Clear patterns are associated with well-known physical factors such as floor level and external shading. At the same time, more atypical cases are identified, suggesting that additional factors play a role [5]. These may include airing habits, interior furnishing, internal heat gains from appliances, retrofits in the building, the performance of the ventilation system, or variations in the use of solar shading and cooling equipment.


Figure 4. Top: Degree hours above 26°C for individual apartments over the period from 1 May to 31 August 2019. Darker colour shade indicates higher number of degree hours. Grey shaded apartments could not be evaluated due to lack of data. Bottom: Schematic of the south façade of the building.
Temperatures are known to vary not only between apartments but also within apartments. On particularly warm and sunny days, temperature distributions within an apartment may vary considerably, depending on its characteristics. Analysis of building performance simulations of a worst-case apartment scenario in a recently constructed building demonstrated localised indoor microclimates near windows, even in cases where solar shading is applied (Figure 5). These “thermal islands” can cause local thermal discomfort and increase stratification within the apartment. Consequently, the outcomes of thermal performance assessments can vary depending on the location of the temperature measurements. For a detailed analysis of thermal comfort and overheating, indoor microclimates should be considered to fully represent thermal conditions within apartments.

Figure 5. Simulation results showing stratification patterns of operative temperature in the living room of a modelled apartment on a warm and sunny day in July 2025, at 09:00 (left) and 13:00 (right). Sensors (S1, S7, S10) show point operative temperature.
The results demonstrate that overheating is already a significant issue in Swedish residential buildings and is likely to become increasingly important as the climate continues to warm. Analysis of data from nearly 67,000 apartments shows that overheating occurs in a large proportion of dwellings, particularly during extreme summers such as 2018, when indoor temperatures frequently exceeded the currently applied threshold of 26°C. The problem varies greatly between normal years and extreme years. While overheating during typical years is often confined to heatwave periods, extreme years can result in prolonged and more severe overheating. Mitigation measures therefore need to be effective under both typical and extreme conditions. The findings also reveal substantial variation between buildings, between apartments within the same building, and even within individual apartments. Measures at multiple levels are therefore needed.
A key challenge remains the absence of well-defined overheating criteria for Swedish conditions. While the 26°C threshold provides a useful reference point, it does not fully capture the frequency, duration, or severity of overheating events. Further research is therefore needed to develop assessment methods and performance indicators that are suitable for large-scale monitoring data and that better reflect occupant exposure, health risks, and building resilience under future climate conditions.
The research was supported by the Swedish Research Council FORMAS (project Nr 2023-02542 and 2023-01163) and the Swedish Energy Agency (project Nr P2023-01488).
[1] The Public Health Agency of Sweden, ‘Public Health Agency General Recommendations on Indoor Temperature’. The Public Health Agency of Sweden, May 13, 2024. [Online]. Available: https://www.folkhalsomyndigheten.se/publikationer-och-material/publikationsarkiv/f/folkhalsomyndighetens-allmanna-rad-hslf-fs-2024-10/
[2] S. Attia et al., ‘Overheating calculation methods, criteria, and indicators in European regulation for residential buildings’, Energy and Buildings, vol. 292, p. 113170, Aug. 2023, https://doi.org/10.1016/J.ENBUILD.2023.113170
[3] M. Persson, D. Teli, and N. K Speicher, ‘Applicability of overheating analysis approaches for big indoor temperature monitoring data’, in Conference Proceeding, Montreal: ASHRAE, 2025. https://doi.org/10.63044/eq25pe87
[4] D. Teli et al., ‘Overheating in the Nordics: challenges in the Swedish multi-residential building stock’, presented at the CATE2024, Seville, 2024.
[5] J. A. Slunitschek and D. Teli, ‘Within-Building Variability in Summer Thermal Performance: A Case Study of a Swedish Multi-Residential Building’, in Conference Proceeding, Montreal: ASHRAE. https://doi.org/10.63044/eq25sl114