Keywords: Pharmaceutical cleanroom, HEPA filtration, airflow distribution, particle control, energy efficiency

 

Mariya P. Bivolarova
Annika Juel Pihl
Kiril Naydenov
Jørn Toftum
Associate professor, Technical University of Denmark
mbiv@dtu.dk
Master student, Technical University of Denmark
D.Sc., Senior Specialist Manager (Life Science & Pharma), Ramboll,
Professor, Technical University of Denmark

 

Portable air cleaners (PACs) equipped with HEPA filters may supplement mechanical ventilation in pharmaceutical cleanrooms by providing additional particle removal through air recirculation. Experimental measurements and building energy simulations show that PAC performance depends strongly on airflow rate and placement, while reduced ventilation combined with appropriate PAC operation can lower annual energy use.

Why investigate portable air cleaners?

Maintaining low airborne particle concentrations is essential in cleanrooms. Mechanical ventilation continuously supplies large volumes of conditioned and HEPA-filtered air to dilute and remove contaminants generated by equipment and operators. Because these systems operate around the clock, they account for a large share of cleanroom energy use. Consequently, improving ventilation efficiency while controlling contamination has become an important objective in cleanroom engineering.

Portable air cleaners equipped with HEPA filters have recently been proposed as a supplement to mechanical ventilation [1]. Unlike ventilation systems, PACs recirculate room air through high-efficiency filters and return the clean air to the space. This provides additional particle removal without increasing the amount of conditioned outdoor air.

Although portable air cleaners with HEPA filtration have been investigated in offices, schools and healthcare settings [2], their performance in cleanrooms is less well understood. Little information is available on how PAC airflow rate and placement interact with existing ventilation systems.

This study, therefore, evaluated portable HEPA air cleaners in a full-scale chamber that simulated pharmaceutical cleanroom ventilation.

Experimental study

Experiments were conducted in a climate chamber (4.7 m long × 4.7 m wide × 2.6 m high; 57.4 m³) configured to represent the ventilation layout and internal heat loads typically found in pharmaceutical cleanrooms (Figure 1). The chamber was equipped with three ceiling-mounted swirl diffusers supplying filtered air and low-level exhaust extraction. Two heated thermal dummies (each 73 Watts), with a 1.6 m² surface area and a height of 1.65 m, simulated operators standing in front of production equipment. A heated mock-up (400 Watts) placed on a table represented the production equipment.

The chamber was designed to reproduce representative ventilation conditions rather than to demonstrate compliance with a specific ISO cleanroom classification.

The mechanical ventilation was operated at two supply airflow rates – 160 L/s (10 ACH) (reference) and 128 L/s (8 ACH). The exhaust flow rate was kept 6 L/s below the supply flow rate to maintain a 10 Pa overpressure in the chamber. The room temperature was kept at 22°C±0.3°C, and the RH was not controlled; it was measured to be between 35% and 55%±3%.

Portable HEPA air cleaners (H14 filter) were introduced using different configurations. The parameters studied included: 1) one or two PACs, 2) two PACs airflow settings and 3) different PAC locations around the production equipment. The corresponding operating airflow rates for the PACs were 127 m³/h and 433 m³/h, resulting in power consumption per PAC unit of 7 Watts and 55 Watts, respectively.  Following the identification of the best-performing configuration, additional experiments investigated four different particle source locations.

DEHS aerosol particles were generated using an atomiser aerosol generator. In the cases shown in Figure 2, particles were released adjacent to the right side of dummy 1 at a height of 1.1 m, representing particle generation associated with an occupant. In the cases shown in Figure 3, two additional release points were studied: the right side of dummy 2 at a height of 1.1 m and the front of dummy 1 at a height of 1.45 m.

Particle concentrations were measured using two optical particle sizers (OPSs). The sampling tube of one OPS was positioned 0.40 m above the top of the equipment to characterise particle concentrations in the critical area, while the second OPS sampled near the exhaust at a height of 0.80 m above the floor, providing a measure of the particle concentration at the room exhaust. The particle size ranged from 0.3 to 0.47 µm. Before starting the particle generator in each experiment, the background particle concentration in the chamber was measured. The background particle concentration was less than 9 particles/cm³. The background concentrations were subtracted from the average values presented in Figures 2 and 3.

Annual HVAC energy demand associated with the investigated ventilation rates was estimated using dynamic energy calculations.

Figure 1. Experimental set-up: (left) Interior of the chamber; (right) Floor plan, where D – dummy.

Reduced ventilation increased particle concentrations

Lowering the mechanical ventilation rate from 10 ACH to 8 ACH increased airborne particle concentrations above the equipment by approximately 26%, while the exhaust concentration remained nearly unchanged. At 8 ACH, similar concentrations above the equipment and at the exhaust suggest near well-mixed conditions. In contrast, at 10 ACH, the lower concentration above the equipment relative to the exhaust indicates that the increased airflow altered particle transport, resulting in improved local contaminant removal and reduced exposure near the table. This suggests that ventilation performance should not be judged from the exhaust concentration alone.

Nominal equivalent air change rate and effect of supplemental HEPA recirculation

The PAC airflow can be expressed as a nominal equivalent air change rate (eACH) of recirculated room air. Because the PACs were equipped with H14 HEPA filters, their filtration efficiency for the investigated particle size range (0.30–0.47 µm) was assumed to be close to unity. Therefore, the equivalent air change rate provided by the PACs was approximated as the PACs’ volumetric airflow rate divided by the room volume. At flow rates of 127 m³/h and 433 m³/h, one PAC provided approximately 2.2 and 7.5 h⁻¹ equivalent ACH, respectively.

At 8 ACH, the effectiveness of the PACs depended strongly on their airflow rate and configuration. Two PACs operating at 433 m³/h each provided the greatest particle reduction above the worktable, outperforming the 10 ACH condition without PACs. Their combined airflow corresponded to approximately 15 eACH of recirculated air. In contrast, lower PAC airflow rates and single-PAC configurations produced considerably smaller improvements, demonstrating that both PAC capacity and airflow distribution are critical for effective particle control in cleanrooms. For practical applications, PACs should therefore be evaluated based on measured particle removal rather than on airflow alone.

Figure 2. Average particle concentrations for cases without PAC and cases with PAC at 8 ACH.

Airflow distribution remains important

Additional experiments investigated particle generation at several locations around the simulated production equipment. Figure 3 shows the results for the reference case at 10 ACH, no PAC, and the other cases were conducted at 8 ACH with two PACs operating at 433 m³/h.

Particle concentrations varied among the studied cases, reflecting the influence of room airflow patterns and particle-source location on contaminant transport. Nevertheless, compared with the reference case, supplemental HEPA recirculation with two PACs reduced particle concentrations, demonstrating the potential of additional filtered airflow to improve contaminant removal.

For ventilation designers, this is important because contamination sources inside pharmaceutical cleanrooms are rarely fixed. Operators, equipment and manufacturing processes all contribute to dynamic particle generation. The proximity of the PACs to the particle sources may have contributed to their effectiveness by removing particles before they were more widely dispersed within the room. Therefore, proper placement of supplemental filtration units remains an important design consideration.

Figure 3. Particle concentrations for different source locations.

Energy implications

Conditioning outdoor air represents a major component of cleanroom energy use. Replacing part of this conditioned airflow with HEPA-filtered recirculation can reduce HVAC energy consumption because recirculated air requires substantially less heating and cooling.

Reducing the mechanical ventilation rate from 10 to 8 ACH decreased the estimated HVAC energy required for conditioning outdoor air (Figure 4).

Although PACs’ operation increased electrical use, the estimated reduction in HVAC energy exceeded the additional PAC energy demand, resulting in 17% lower overall yearly energy use.

Figure 4. Annual energy use for the air conditioning systems in a simulated pharmaceutical cleanroom in Copenhagen.

Conclusions

Portable HEPA air cleaners can supplement cleanroom ventilation while offering potential energy savings through reduced mechanical airflow. However, their contribution to particle control cannot be determined from nominal airflow or equivalent ACH alone, as performance depends on the interaction between PAC operation, room airflow distribution and contaminant sources.

The findings support an integrated approach in which mechanical ventilation and HEPA recirculation are considered together and evaluated based on particle control in critical areas. Under the investigated conditions, this approach maintained particle control while reducing energy use. Further studies are needed to assess its applicability to other cleanroom configurations and operating conditions

References

Chun Chen, Jeffrey A. Siegel, (2023). Challenges and opportunities in air filtration for the control of infectious diseases. Building and Environment, Volume 304, Part A, https://doi.org/10.1016/j.buildenv.2026.114990

Alireza Afshari, Olli Seppänen, (2021). Effect of Portable Air Cleaners on Indoor Air Quality: Particle Removal from Indoor Air. REHVA Journal, Vol. 58.

Mariya P. Bivolarova, Annika Juel Pihl, Kiril Naydenov, Jørn ToftumPages 66 - 69