Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Keywords: Digital twin, Model calibration, Heating demand prediction, Synchronization, Building energy model
|
|
|
Hamed Amini | Kari Alanne | Risto Kosonen |
Department of Civil Engineering, Aalto University, Finlandhamed.amini@aalto.fi | Department of Civil Engineering, Aalto University, Finland | Department of Civil Engineering, Aalto University, Finland |
Physics-based simulation models are used in building energy management for applications such as demand prediction, model predictive control, reinforcement learning-based control and digital twin development. Model parameters are typically identified through calibration against measured data for a defined period and are then assumed to remain valid (Baba et al., 2022). However, in practice, building operation is non-stationary, and operational changes such as occupancy shifts, extreme weather or a pandemic further affect energy demand patterns. (Koo & Yoon, 2026). As a result, calibrated models gradually diverge from measured building performance, a phenomenon known as model drift (Amini et al., 2025).
Periodic recalibration partially addresses model drift but is computationally expensive and adapts poorly to short-term changes, particularly in multi-purpose buildings where several functions with different occupancy patterns share a common energy system (Amini et al., 2025). This study presents an automatic synchronization approach that maintains model accuracy under real operating conditions by combining retrieval from a persistent parameter library with an event-triggered recalibration mechanism, without manual intervention.
The synchronization approach starts from an hourly calibrated physics-based model, obtained by calibrating fixed parameters and operational schedules against a base-year measured dataset (Amini et al., 2025). This calibrated model and its resulting operational schedules (from hourly calibration of the models in different time periods) form the initial parameter library feeding the automatic synchronization loop, illustrated in Figure 1.
At the start of each validation window (month, week or day), stored parameter sets are simulated and evaluated against current measured data. If a set achieves hourly CVRMSE below the ASHRAE Guideline 14 threshold (30% for hourly calibration (ASHRAE, 2002)) for both AHU heating and space heating demand, it is applied directly and no recalibration is performed. Otherwise, Bayesian optimization is re-executed, warm-started from the closest-matching library entries, to recalibrate the operational schedules and minimize the model-system discrepancy. The resulting parameter set is applied to the model and added to the library before the loop proceeds to the next window.

Figure 1. Overall diagram of the calibration process and automatic synchronization loop.
The approach was evaluated on a 47,000 m², multi-purpose building complex in Espoo, Finland, comprising a shopping center, metro station and two university faculties, with two heating distribution systems: space heating and AHU heating. The building was modelled in IDA ICE using a simplified five-zone geometry (Amini et al., 2026) to be used as a training environment for deep reinforcement learning-based cost-optimal control (Bojnurdi et al., 2025)). AHU heating and space heating demand were used as calibration objectives, with 2022 as the base year and the 2023–2024 heating months as the real-time evaluation period.
The approach is evaluated using monthly and weekly validation windows, which detect discrepancy and synchronize the model to operational changes at different time scales. Monthly validation windows capture sustained shifts (e.g., altered occupancy patterns following COVID-19 restrictions), while weekly windows capture short-term events too (e.g., holiday periods, cold waves).
Table 1 summarizes the monthly rolling synchronization results for the 2023 and 2024 heating seasons (12 evaluated months). Suitable schedules were retrieved directly from the library in 75% of windows. Recalibration was triggered in the remaining three months (October 2023, January 2024, October 2024) due to AHU heating demand exceeding the error threshold. Accuracy improved by 13.0%, 2.8% and 22.3%, respectively, relative to the best retrieved set. The low improvement in January 2024 is due to measured data quality issues.
Table 1. Monthly rolling synchronization summary for the 2023 and 2024 heating seasons.
Period | Decision | Source of applied schedule / recalibration trigger | Final total heating CVRMSE [%] |
Jan 2023 | Library retrieval | Schedules retrieved from Dec 2022 | 15.9 |
Feb 2023 | Library retrieval | Schedules retrieved from Dec 2022 | 17.3 |
Mar 2023 | Library retrieval | Schedules retrieved from Nov 2022 | 21.0 |
Oct 2023 | Recalibration | Trigger: CVRMSEAHU_heating= 30.4% | 22.0 |
Nov 2023 | Library retrieval | Schedules retrieved from Dec 2022 | 19.2 |
Dec 2023 | Library retrieval | Schedules retrieved from Dec 2022 | 18.2 |
Jan 2024 | Recalibration | Trigger: CVRMSEAHU_heating= 31.8% | 17.3 |
Feb 2024 | Library retrieval | Schedules retrieved from Jan 2024 | 17.4 |
Mar 2024 | Library retrieval | Schedules retrieved from Oct 2023 | 20.4 |
Oct 2024 | Recalibration | Trigger: CVRMSEAHU_heating= 46% | 20.9 |
Nov 2024 | Library retrieval | Schedules retrieved from Dec 2022 | 18.8 |
Dec 2024 | Library retrieval | Schedules retrieved from Jan 2024 | 19.2 |
To evaluate the proposed approach, it is benchmarked against a one-time-calibrated model and a library-retrieval-only model. Figure 2 shows the synchronized model consistently predicting building energy performance with high accuracy (CVRMSE < 30%), while library-retrieval-only performs intermediately and the one-time-calibrated model violates the ASHRAE threshold, particularly for AHU heating demand in January and February of 2023 and 2024.
Table 1 shows that schedules from January–March 2022 were never selected for 2023 or 2024, since early-2022 operation was strongly affected by COVID-19 restrictions in Finland. Once operation returned to regular patterns, the one-time-calibrated model, which assumes base-year conditions remain representative, could not adapt (Figure 2). In contrast, the synchronized model could adapt to new conditions through both library retrieval and recalibration.

Figure 2. Hourly CVRMSE of AHU heating and total heating demand in monthly rolling windows, 2023-2024 heating months.
In addition to monthly synchronization, the approach was applied in a weekly rolling window setup for 2024, leveraging the schedule library accumulated during the 2022 calibration and 2023 monthly synchronization. This finer horizon suits applications sensitive to short-term operational variations, such as weekly energy demand forecasting or HVAC control optimization.
Figure 3 shows the predictive performance of the synchronized model over weekly windows, compared to the reference approaches. The proposed approach outperformed the references in all 25 validation weeks while maintaining sufficient hourly accuracy for real-time applications. Recalibration was triggered in 24% of the window, with a maximum accuracy recovery of 36%. In the remaining weeks, a suitable solution was successfully retrieved from the evolving library.
Although the synchronization approach detects prediction discrepancies without explicit knowledge of real-world events, recalibration decisions can usually be linked to identifiable triggers. For example, a severe cold wave during the Christmas holiday in Week 1, 2024 (average outdoor temperature −17°C, minimum −22°C) caused a discrepancy in AHU heating demand prediction and triggered recalibration (Figure 3). It was a holiday-related shift which was not captured by the monthly rolling synchronization. The weekly setup also responded to other short-term changes. For instance, recalibration triggered in Week 7, preceding the Finnish winter break, achieved a 36.3% improvement in model accuracy, and the resulting schedules were reused successfully in Weeks 8 and 9.

Figure 3. Hourly CVRMSE of AHU heating and total heating demand in weekly rolling windows, heating season of 2024.
Recovering accuracy quickly is also critical for real-time applications, particularly as the synchronization horizon shortens. Library retrieval reduces the need for continuous calibration, but recalibration is still occasionally required. Warm-starting the optimization from the closest-matching library entries keeps recalibration time within 1–2 hours even in the most demanding cases.
An autonomous, retrieval-first synchronization approach maintained the accuracy of a physics-based model of a multi-purpose building over two heating seasons of real operation. The approach reduced hourly CVRMSE by up to 50% and 33% relative to one-time calibration in monthly and weekly synchronization, respectively, and recovered accuracy within 1-2 hours following triggered recalibration, using warm-started Bayesian optimization. The model adapted to unforeseen operational changes, including altered occupancy following COVID-19 restrictions and short-term shifts associated with holidays and cold weather, without prior knowledge of the underlying causes. These results support the use of automatic synchronization for long-term deployment of digital twins in building energy management and demand-side flexibility applications, offering consulting engineers a practical route to keeping calibrated models representative of building operation without manual recalibration.
The authors acknowledge funding from the Research Council of Finland (formerly Academy of Finland) Consortium Project ‘Adaptive Multi-Energy Virtual Power Plant for a Complex of Buildings’ (Grant No. 348419).
Amini, H., Bjelland, D., Maria, T., Alanne, K., Hamdy, M., & Kosonen, R. (2025). Scalable and adaptive multi-stage hourly calibration of simulation models with high usage fluctuations: case studies for multi-purpose buildings. Journal of Building Performance Simulation, 1–22. https://doi.org/10.1080/19401493.2025.2586513
Amini, H., Ehteshami Bojnurdi, V., Liu, J., Atmojo, U. D., Vyatkin, V., Alanne, K., & Kosonen, R. (2026). Adaptive modular hybrid modeling of a multi-component building energy system. Energy and Buildings, 359, 117297. https://doi.org/https://doi.org/10.1016/j.enbuild.2026.117297
ASHRAE, A. (2002). Ashrae guideline 14: measurement of energy and demand savings. American Society of Heating, Refrigerating and Air-Conditioning Engineers, 35, 41–63.
Baba, F. M., Ge, H., Zmeureanu, R., & Wang, L. (2022). Calibration of building model based on indoor temperature for overheating assessment using genetic algorithm: Methodology, evaluation criteria, and case study. Building and Environment, 207, 108518. https://doi.org/https://doi.org/10.1016/j.buildenv.2021.108518
Bojnurdi, V. E., Amini, H., Atmojo, U. D., Vyatkin, V., Alanne, K., & Kosonen, R. (2025, 14–17 Oct. 2025). Deep Reinforcement Learning-Based Cost-Optimized Control for Energy Management in Facilities with Geothermal Storage. IECON 2025 – 51st Annual Conference of the IEEE Industrial Electronics Society.
Koo, J., & Yoon, S. (2026). Digital twin synchronization in closed-loop HVAC control for building operations. Automation in Construction, 182, 106723. https://doi.org/https://doi.org/10.1016/j.autcon.2025.106723
Follow us on social media accounts to stay up to date with REHVA actualities
0