Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Keywords: Standard, Indoor Air Quality, ventilation, control, assessment
|
|
|
Bjarne W. Olesen | Jarek Kurnitski | Valérie Leprince |
Intl. Centre for Indoor Environment and Energy, DTU.SUSTAIN, Technical University of Denmarkbwol@dtu.dk | Tallinn University of Technology, REHVA Technology and Research Committeejarek.kurnitski@taltech.ee | Valérie LEPRINCE, Directrice de projet
Confort des environnements intérieurs et ventilation |
The existing standard EN16798-1” Indoor environmental parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics” (2) was developed under TC156 “Ventilation of Buildings” and includes criteria for all indoor environmental parameters. The revision is now being made by different TCs and working groups, as seen in Table 1. In parallel, a similar standard is being revised by ISO 17772-1 (3).
Table 1. TCs and working groups responsible for the revision of EN 16798-1 and ISO 17772-1.
EN16798-1 (and 16798-2) |
| ISO 52007 1/8 (former ISO17772-1/2) |
Part 1.1 Overarching | CEN/TC371-WG3 | JWG TC163/205, (ISOTC163/WG4) |
Part 1.2 Thermal Comfort | CEN/TC371-WG4 | JWG TC163/205 task force 5 |
Part 1.3 Indoor Air Quality | CEN/TC156-WG25 | JWG TC163/205 task force 5 |
Part 1.4 Lighting | CEN/TC169-WGxx | ISO/TC274 |
Part 1.5 Acoustic | CEN/TC126-WGxx | ISO/TC43 |
Even if the revision includes different parts, it will still be published as a single standard. The new energy performance of buildings directive refers to the existing standard, but includes new requirements for the indoor environment that must be taken into account in the new standard. The revisions are now underway, and this paper provides an overview of the work on the indoor air quality section.
It is applicable where the criteria for indoor air quality are set for human occupancy. This document includes design criteria for the ventilation of residential and non-residential buildings to address emissions from buildings, furnishings, and human activities.
The standard does not specify design methods but provides relevant input parameters for the design and assessment of ventilation and air treatment systems, as well as building automation and control systems. In addition, it proposes methods for determining indoor air quality and classes based on different limit values.
The intent is to provide a threshold for IEQ categories according to Table 2.
Table 2. Categories for indoor air quality parameters.
Category | Level of expectation |
IAQI | High |
IAQII | Medium |
IAQIII | Moderate |
IAQIV | Low |
The categories relate to the level of expectations occupants may have. A normal level would be “Medium”, which is the level recommended for new buildings in the guidance to the EPBD. For the renovation of existing buildings, the “Moderate” level is recommended. A higher level may be selected for occupants with special needs (children, elderly, handicapped, etc.). A lower level will not pose any health risk, but may reduce comfort; it is recommended that every existing building at least meet this target.
As the existing standard, the new standard will include normative parts, but will not set a normative threshold for the different parameters. There will be an informative annex with recommended values; each country can choose to use them or develop a national annex with its own. The present paper includes examples of default thresholds.
Figure 1 provides an overview of the various parts of the standard revision. This paper will focus on the design procedures “Options for design of IAQ management system”.

Figure 1. Organisation of the standard.
The standard requires that one of the two normative procedures be used to inform the design of IAQ management systems: the Indoor Air Quality Procedure or the Ventilation Rate Procedure. Additionally, an optional method is included for designing for airborne pathogen control. The standard also keeps a minimum ventilation rate per person as a hygienic minimum airflow with a default value of 4 ℓ/s per person.
The procedure uses an integrated simulation of the building and its IAQ management system. The performance of different design solutions can then be compared against IAQ criteria defined by policymakers.

Figure 2. Principle of the Indoor Air Quality Procedure.
To make the Indoor Air Quality Procedure applicable in practice, two essential conditions must be met:
· IAQ performance objectives and criteria need to be defined by policymakers, including the relevant parameters, indicators and threshold values against which performance can be assessed.
· Default input data for IAQ simulations need to be clearly defined so that performance-based assessments can be carried out consistently and transparently.
To this end, the standard will provide more than the definition of the procedure itself. It will include:
· Default emission scenarios of pollutants, together with appropriate assumptions for outdoor pollutant concentrations and mitigation strategies
· Default indicators and thresholds for different types of zones (bedrooms, classrooms, kitchens, etc.) based on the proposed objective for this zone regarding health, well-being and building durability.
For example, to assess the long-term impact of IAQ on health, the DALY is proposed as the default indicator. The description of the calculation method for this indicator will be included in an Annex of the standard.
The calculation methods also need to reflect the dynamic and spatial nature of buildings. IAQ performance cannot always be assessed adequately using a single-zone or steady-state approach. The integration of multi-zone airflow and pollutant transport calculations, as addressed in the revision of EN 16798-7, is therefore an important complement to the IAQ Procedure.
This approach is fundamentally different from simply specifying, for example, a ventilation rate of 10 ℓ/s per person. The same airflow rate can lead to very different indoor concentrations depending on pollutant emissions, outdoor concentrations, air distribution and occupancy. Conversely, different combinations of ventilation and air cleaning may achieve the same IAQ objective. The IAQ Procedure, therefore, makes it possible to compare technology-neutral solutions according to the performance they deliver.
The performance-based approach is particularly relevant for smart ventilation and IAQ management systems. Demand-controlled ventilation, for example, continuously adjusts airflow according to occupancy or measured indoor conditions. In such systems, there is no single constant airflow rate that represents the system’s actual operation. The relevant question is instead whether the control strategy delivers the required IAQ performance over time.
The approach also provides a direct link between design and assessment during operation. The same IAQ parameters and performance criteria used in the simulation can be used to assess the building once occupied (through monitoring). This creates a common language among design, commissioning, and operation, and makes it possible to verify whether the performance predicted at the design stage is actually achieved. The revision of EN 16798-17 (Inspection of ventilation systems) will build on this approach to provide appropriate methods for assessing the performance of ventilation systems with non-constant airflow rates.
The proposed framework also creates a basis for linking IAQ and energy performance. A design can be evaluated simultaneously in terms of its energy demand and its ability to achieve the selected IAQ category. This is particularly important because ventilation strategies involve trade-offs between energy consumption and pollutant removal. The objective is therefore not to maximise ventilation, but to identify the most effective combination of measures to achieve the required indoor environmental quality.
This procedure is essentially the same as that in the existing EN 16798-1. The focus is on estimating the required ventilation rate for each room. The procedure includes three methods:
1. Method 1 Perceived Air Quality
2. Method 2 Individual Substances
3. Method 3 Prescriptive Table
Method 1: Perceived Air Quality
This concept has been used as input for the design of ventilation systems and for energy calculations for many years. The design total ventilation rate for the breathing zone is found by combining the ventilation for people and the building calculated from Formula (1):
| (1) |
qtot is the total ventilation rate for the breathing zone, ℓ/s
n is the design value for the number of persons in the room,
qp is the ventilation rate for occupancy per person, ℓ/(s person)
AR is the floor area, m²
qB is the ventilation rate for emissions from building, ℓ/(s,m²)
The contributions from occupants and the building are added because they involve the same organ: the nose.
Table 3 gives an example of default values for the calculations.
Table 3. Design ventilation rates for non-adapted persons for diluting emissions (bio effluents) from people and for buildings for different categories.
Indoor Environmental Category | Expected Percentage Dissatisfied, % | People Component, qp | Building Component, qB | ||
Airflow per nonadapted person,ℓ/(s·pers) | Very low polluting building, ℓ/(s·m²) | Low polluting building,ℓ/(s·m²) | Non low polluting building, ℓ/(s·m²) | ||
IEQI | 15 | 10 | 0.5 | 1.0 | 2.0 |
IEQII | 20 | 7 | 0.35 | 0.7 | 1.4 |
IEQIII | 30 | 4 | 0.2 | 0.4 | 0.8 |
IEQIV | 40 | 2.5 | 0.15 | 0.3 | 0.6 |
This table includes values for the people part and the emission from buildings part. To emphasise the importance of source control, three levels of building emissions are included.
By the use of these table values, the design ventilation rate can be calculated for different levels of people density and levels of building emissions (see Table 4).
Table 4 Default design ventilation rates for a combination of spaces and building types according to Method 1.
Type of building or space | Category | Floor area m²/person | qp | qp | qB | qtot | qB | qtot | qB | qtot | |||
minimum ventilation rate | |||||||||||||
ℓ/(s·m²) | ℓ/s,pers | ℓ/s,m² | ℓ/s,m² | ℓ/s,pers | ℓ/s,m² | ℓ/s,m² | ℓ/s,pers | ℓ/s,m² | ℓ/s,m² | ℓ/s,pers | |||
for occupancy only | for very low-polluted building | for low-polluted building | for non-low polluted building | ||||||||||
Single office | I | 10 | 1 | 10 | 0.5 | 1.5 | 15 | 1 | 2.0 | 20.0 | 2 | 3.0 | 30 |
II | 10 | 0.7 | 7 | 0.35 | 1.1 | 11 | 0.7 | 1.4 | 14.0 | 1.4 | 2.1 | 21 | |
III | 10 | 0.4 | 4 | 0.2 | 0.6 | 6 | 0.4 | 0.8 | 8.0 | 0.8 | 1.2 | 12 | |
IV | 10 | 0.25 | 2.5 | 0.15 | 0.4 | 4 | 0.3 | 0.6 | 5.5 | 0.6 | 0.9 | 9 | |
Land-scaped office | I | 15 | 0.7 | 10 | 0.5 | 1.2 | 18 | 1 | 1.7 | 25.0 | 2 | 2.7 | 40 |
II | 15 | 0.5 | 7 | 0.35 | 0.8 | 12 | 0.7 | 1.2 | 17.5 | 1.4 | 1.9 | 28 | |
III | 15 | 0.3 | 4 | 0.2 | 0.5 | 7 | 0.4 | 0.7 | 10.0 | 0.8 | 1.1 | 16 | |
IV | 15 | 0.2 | 2.5 | 0.15 | 0.3 | 5 | 0.3 | 0.5 | 7.0 | 0.6 | 0.8 | 12 | |
Conference room | I | 2 | 5 | 10 | 0.5 | 5.5 | 11 | 1 | 6.0 | 12.0 | 2 | 7.0 | 14 |
II | 2 | 3.5 | 7 | 0.35 | 3.9 | 8 | 0.7 | 4.2 | 8.4 | 1.4 | 4.9 | 10 | |
III | 2 | 2 | 4 | 0.2 | 2.2 | 4 | 0.4 | 2.4 | 4.8 | 0.8 | 2.8 | 6 | |
IV | 2 | 1.25 | 2.5 | 0.15 | (1.4) 1.8 | (3) 4 | 0.3 | (1.6) 2 | (3.1) 4 | 0.6 | 1.9 | 4 | |
Note: italics is for situations where the calculated ventilation rate is lower than 4 ℓ/s per person required for health. | |||||||||||||
Method 2: Individual substances
Under steady-state conditions, the design ventilation airflow rate required to dilute an individual substance can be calculated by Formula (2)
| (2) |
where
Qh is the design ventilation airflow rate required for dilution, in m³ per second;
Gh is the generation rate of the substance, in micrograms per second;
Ch,i is the guideline value of the substance, in micrograms per m³;
Ch,o is the concentration of the substance of the supply air, in micrograms per m³;
εv is the ventilation effectiveness.
Default values for the parameters will be included in informative annexes. CO2 concentration in a space is often used to evaluate the level of ventilation per person. This equation can then be used to calculate the corresponding increase in indoor CO2 levels for a given population density and people’s CO2 emissions. For this purpose, the total ventilation rate per person is calculated based on Method 1 Formula (1) as follows:
| (3) |
where
qsp is the total ventilation rate per person, ℓ/(s person)
qtot is the design ventilation rate calculated with Method 1, ℓ/s
n is the number of persons in the room corresponding to typical occupancy, -
Increase in CO2 above outdoor levels is calculated from metabolic CO2 generation and CO2 volume balance:
| (4) |
where
∆CO₂ is the CO2 concentration above the outdoor CO2 concentration, ppm
qCO2is the CO2 generation rate, ℓ/(h person)
(1000/3.6) 3600 and 106 are unit conversions from hours to seconds and litres to ppm.
For the same space types and ventilation rates as in Table 4, the corresponding increase in CO2 above outdoor levels is shown in Table 5. Therefore, these CO2 values can be used as design criteria instead of the ventilation rate to achieve the same level of IAQ.
Table 5. Increase in CO2 level above outdoor for the ventilation rates from Table 4 (Method1).
Type of building or space | Category | Occupancy | ΔCO2[ppm] | ||
person/m² | Very low-polluting | Low-polluting | Not low-polluting | ||
Single office | I | 0.1 | 315 | 236 | 157 |
II | 0.1 | 450 | 337 | 225 | |
III | 0.1 | 787 | 590 | 394 | |
IV | 0.1 | 1 181 | 859 | 556 | |
Landscaped office | I | 0.07 | 269 | 189 | 118 |
II | 0.07 | 386 | 269 | 168 | |
III | 0.07 | 630 | 473 | 295 | |
IV | 0.07 | 1 050 | 675 | 411 | |
Conference room | I | 0.5 | 429 | 394 | 337 |
II | 0.5 | 614 | 562 | 482 | |
III | 0.5 | 1 074 | 983 | 843 | |
IV | 0.5 | 1 687 | 1 523 | 1 277 | |
Note: In this Table CO2 emission value is 17 ℓ/h per person for sedentary activity. Values in italics indicate situations where the calculated ventilation rate is lower than the minimum required 4 ℓ/s per person. | |||||
If emissions from the building are calculated with Formula (2) in a more detailed fashion than very-low, low or not-low polluting used in Method 1, CO2 can be used to represent emissions from occupants only, and criteria for CO2 levels across different IEQ categories can be established. This is shown in Table 6 for sedentary persons emitting 17 ℓ/h of CO2. The rates in Table 6 are valid only for occupants as the sole source in the space. Additional rates for emissions from the building are to be calculated with Formula (2) and added to those in Table 6. If, however, the ΔCO2levels in Table 5 calculated with Formulas (3) and (4) are used, the building’s emissions will be taken into account in a more robust fashion. In this way, there is alignment between Method 1 and Method 2.
Table 6. ΔCO2levels for sedentary occupants (17 ℓ/h per person CO2) only. Airflow rates to dilute emissions from the building are to be added.
Category | ΔCO2 | Airflow |
| [ppm] | [ℓ/s person] |
IAQI | 450 | 10 |
IAQII | 650 | 7 |
IAQIII | 1 200 | 4 |
IAQIV | 1 900 | 2,5 |
If the default minimum ventilation rate is observed, IAQIV would be the same as IAQIII.
Method 3: Prescriptive table
If Table 4 is used for the prescriptive rates, then Method 1 and Method 3 are aligned.
Two methods are introduced in an informative annex to design for airborne pathogen control. The first method is the so-called quanta method, which aims to reduce the expected number of secondary infections from an infected person, but has high uncertainty in virus emission parameters. The second method is the relative risk reduction method, which enables calculation of the specified risk reduction under Category IV ventilation conditions without uncertainty related to viral load, but only with knowledge of the absolute probability of infection.
The quanta method is intended to be used in combination with one of Methods 1 to 3, so that the highest calculated ventilation rate from these methods is used as the design ventilation rate. Infection risk-based ventilation rate for the breathing zone is found by combining the ventilation to dilute the viral load and removal by other mechanisms than ventilation, calculated from
| (5) |
where
Q is the target ventilation rate for the breathing zone, ℓ/s
qq is the quanta emission specific ventilation rate for occupancy per person, ℓ/(s person)
qr is the removal rate of virus decay, deposition, air filtration and disinfection, ℓ/(s m³)
N is the design value for the number of persons in the room with the distancing >1.0 m to avoid close proximity
V is the room volume, m³.
Default values for virus-specific ventilation parameters (qq) and (qr) are given in Table 7.
Table 7. Default values for virus-specific ventilation parameters.
Space category | qq, ℓ/(s person) | qr, ℓ/(s m³)a |
Classroom | 10 | 0.24 + kf /3.6 |
Office | 23 | 0.24 + kf /3.6 |
Assembly hall | 30 | 0.24 + kf /3.6 |
Meeting room | 40 | 0.24 + kf /3.6 |
Restaurant | 40 | 0.24 + kf /3.6 |
Gym, fitness | 70 | 0.24 + kf /3.6 |
a in the case of no room air cleaner, kf = 0
An alternative method is based on the relative risk reduction. For instance, if sick leave or disease case data is available for a specific building, it can be calculated how much the ventilation would have needed to be increased to reduce the number of disease cases, for example, by 80%. This corresponds to the relative risk reduction (R1−R2) / R1 = 0.8 or the relative risk R2 / R1 = 0.2.
Relative risk reduction from the reference case can be achieved by changing the number of occupants, ventilation rate, and removal rates for the room air cleaner and UV. In the case of no air cleaner and no UVGI, the target ventilation rate corresponding to the specified relative risk reduction is calculated:
| (6) |
where
Q2 is the target ventilation rate corresponding to specified relative risk r in case 2, ℓ/s
Q1 is the ventilation rate in the reference case 1, ℓ/s
N2 is the number of persons in the room in the target ventilation case 2, -
N1 is the number of persons in the room in the reference case 1, -
r is the relative risk compared to reference case 1 with r = 1, r = R2/R1 where R1 and R2 are the number of new disease cases in the reference and target cases 1 and 2, -
Formula (6) may be used to calculate the target ventilation rate that provides a specified risk reduction from the lowest possible ventilation rate of Category IV, which will then be considered as reference case 1. Default values for relative risk to be achieved consider activities with higher virus emission rates, such as speaking and physical activities. For this reason, the recommended relative risk value is r=0.15 for meeting rooms, restaurants, and gyms. For offices and classrooms, r=0.5 is recommended.
Operation of ventilation systems is often based on Demand-Controlled Ventilation (DCV), where ventilation is adjusted to the number of occupants. As an indicator for the number of occupants, the ΔCO2concentration can be used.If ΔCO2setpoints are used as in Table 5, ventilation will be controlled to achieve the same IAQ levels as in Method 1. During unoccupied periods, the ventilation system may be stopped or operated at a reduced rate corresponding to building emissions. If the system is completely stopped, it must be started in time to reach the designed IAQ category before the occupants arrive.
It is required to assess the IAQ over time during building design or monitoring during building operation. This is important for comparing different design/operation concepts and for relating to energy performance values. There is a need to establish annual IAQ values for comparison with annual energy performance. Also, assessing the influence of IAQ on health over time and comparing it with other factors, like smoking, is important. Therefore, the standard committee is discussing several options.
The distribution of representative parameters in IAQ categories over time will be an important input to the assessment. For perceived air quality (comfort) parameters such as CO2 and ventilation rate, an acceptable deviation, expressed as a percentage of occupied hours, can be specified for the IAQ category. In contrast, for health parameters such as PM2.5, assessing daily and annual doses is important.
It is being discussed to use the TAIL concept (4) and DALY (6). It is also being discussed to calculate a yearly (monthly, weekly) value from the distribution across categories, summed with a weighting factor for each category and for outside categories.
Requirements for indoor environmental quality (IEQ) according to the latest Energy Performance Directive can be established using the revised standard EN 16798-1, as explained in this paper. This paper only dealt with the indoor air quality, but the revision of the other parts for thermal comfort, acoustic and lighting is also in progress.
(1) EPBD: Directive (EU) 2024/1275 of the European Parliament and of the Council of 24 April 2024 on the energy performance of buildings (recast)
(2) CEN “EN 16798-1:2019 Energy performance of buildings - Ventilation for buildings - Part 1: Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustic.” 2019.
(3) ISO 17772-1:2017. Energy performance of buildings - Indoor environmental Quality - part 1: Indoor environmental input parameters for the design and assessment of energy performance of buildings. ISO 2017
(4) P. Wargocki et al., “TAIL, a new scheme for rating indoor environmental quality in offices and hotels undergoing deep energy renovation (EU ALDREN project),” Energy Build., vol. 244, 2021, https://doi.org/10.1016/j.enbuild.2021.111029
(5) P. Wargocki and C. Mandin: The Tail Rating Scheme. REHVA Journal, February 2026.
(6) DALY: https://en.wikipedia.org/wiki/Disability-adjusted_life_year
(7) J. Kurnitski et al., Post-COVID ventilation design: Infection risk-based target ventilation rates and point source ventilation effectiveness, Energy and Buildings, Volume 296, 2023, https://doi.org/10.1016/j.enbuild.2023.113386
Follow us on social media accounts to stay up to date with REHVA actualities
0