Where space is limited and invasive interventions have to be avoided – be it historic buildings in particular or refurbishment projects in general – particular awareness and special solutions for HVAC systems are needed. Within FP7 project 3ENCULT a number of such solutions have been developed and tested at case studies.
Historic buildings are the trademark of numerous European cities, they are a living symbol of Europe’s rich cultural heritage & diversity and reflect the society's identity and need to be protected. They do, however, also show a high level of energy inefficiency and thus contribute with considerable CO2 emissions to climate change. And they do not always offer “comfort” – to people as well as to artworks contained in them. The research project 3ENCULT (Efficient energy for EU cultural heritage, cofunded by the European Union Seventh Framework Programme FP7/2007-2013, see http://www.3encult.eu/en/project/welcome/default.html) aims at demonstrating that a considerable reduction in energy demand – by factor 4 to 10 – is achievable, also in historic buildings, respecting their heritage value. Besides solutions for the building envelope, such as internal insulation, special HVAC solutions (ventilation with heat recovery in particular) where developed. To demonstrate the application in real buildings, one of the sulutions was realized in a case study (CS5, Innsbruck, Austria).
The
following examples show, how HVAC can improve building existing buildings.
These solutions are useful not olnly for historic listed buildings but also for
refurbishing of other existing buildings. New products, such as flat heat
recovery systems are available, which can be integrated in a space saving way
at the wall (see Figure 1) or ceiling.

Figure 1. The heat recovery system can be placed at the wall (wall mounted (left)) or in the wall (wall integrated (middle and right)). This way, the outdoor air and the exhaust air duct are as short as possible (cost, energy and space saving).
The advantage of the application of mechanical ventilation systems in historic buildings is not only the high indoor air quality and saving of ventilation losses by heat recovery, but also the low indoor air humidity to be guaranteed during the heating season. This is an important boundary condition, especially if internal insulation is applied. Damages by humidity and mold growth can largely be avoided.
Decentral
systems can help to avoid ductwork (horizontal and vertical distribution
ducts). The drawback is the number of holes to be drilled for outdoor and
exhaust air ducts (see Figure 2).

Figure 2. Wall integrated
decentral ventilation system for school buildings (supply air inlet at the
window lintel, extract air outlet besides the window.

Figure 3. Wall integrated decentral
ventilation system (view from outside). Exhaust air outlet via perforated
plate, outdoor air inlet via slit below the window sill.
A flat counter flow heat exchanger can be mounted at the parapet, whereas the supply air inlet and the exhaust air outlet are placed above and besides the window respectively. In order to avoid any grill at the façade for ambient air intake, a slit below the window sill can be applied. For exhaust air outlet, this possibility is not valid, because condensation and freezing problems at the wall surface would occur. Therefore a perforated plate or a cover plate in front of the window post is suggested as exhaust air outlet (see Figure 3).
The suggested design can be realized for buildings where an external insulation is applicable. In this case, the flat air ducts for ambient and exhaust air can be integrated in the insulation layer. After finishing the plaster (outside) and dry walling (inside), no ductwork is visible from both sides. For most of the listed buildings however, no external insulation is appropriate. In those cases a central heat recovery should be preferred.
Vertical
ducts with a horizontal distribution at the attic might be a good compromise
for historic buildings. Suspended ceilings have to be avoided, if the original
height of the room and/or the original state of the original ceiling itselve is
to be preserved.
Flat ducts
and prefabricated ductwork helps to integrate ventilation systems in existing
buildings, where space for installations is limited. It was shown, that the
pressure drop of flat ducts can be equivalent to round ducts with slightly
higher cross section area. New products especially for the refurbishing market
are available (see Figure 4).

Figure 4. Reduced clear height of suspended
ceiling by application of rectangular silencers (left). Pressure drop
equivalent cross sections of round and flat ducts (second left); Special
ductwork for integration in existing buildings (right).
As shown
in Figure 4 (left), the cross section of a flat
duct can be chosen in such a way, that the
pressure drop per meter is equivalent to that of a circular shaped
ducts. With this space saving design, the ducts can be placed behind a
suspended ceiling without changing the clear height of the room significantly.
The
principle of cascade ventilation is to guide the air from the sleeping room via
overflow openings to the living rooms and the corridor to the extract air rooms
(such as toilet, bathroom and kitchen). This principle helps to avoid ductwork
and to build energy and cost efficient ventilation systems. (see Figure 5)

Figure 5. Principle of cascade ventilation (supply air only in bedrooms, living rooms are regarded as overflow zones).
This principle is frequently used for residential buildings, within the 3ENCULT project, it was transferred to the use in school buildings (see [Pfluger 2013a]. A fan is used to duct the air from the corridor to the class rooms and back again (see Figure 6). A central heat recovery unit, placed at the attic, takes the air from the toilets and wardrobes for preheating the outdoor air, which is ducted to the staircase. This way, vertical and horizontal ducts can be avoided, because the staircase and corridors are used as a duct.

Figure 6. Active overflow ventilation in
prototype class room in Innsbruck (A), air inlet via textile diffuser and fan
from corridor (preheated supply air from central heat recovery unit at the
attic without duct via staircase and corridor).
Coaxial
duct systems, developed by University of Innsbruck can help to minimize the number
of holes through the external walls The
outdoor air is ducted through the annular gap whereas the exhaust air flows
through the central duct (see Figure 7). As shown by tracer gas
measurement, there is no danger of short circuit flow from exhaust air outlet
to outdoor air inlet.

Figure 7. Coaxial duct for outdoor air intake and exhaust air outlet developed by University of Innsbruck within the research project low_vent.com; prototype built by company POLOPLAST.
The use of coaxial ducts in ventilation systems was published in [Pfluger 2013b].
New types
of space saving heat recovery systems will help to integrate high efficient
ventilation systems in existing buildings. The innovative development of a
combination of fan and heat exchanger (see Figure 8) by University of Innsbruck is an
example of that type of unit which can be integrated in the external wall. This
will help to save space, energy and money.

Figure 8. Heat recovery fan developed by Univerity of Innsbruck within the research projekt Vent4Reno (INTERREG)
A detailed
description of the system as well as the calculations and results are given in
[Pfluger 2013c].
[Pfluger 2013a] Pfluger, R., Längle, K.: Minimal Invasive Ventilation Systems with Heat Recovery for Historic Buildings, Conference proceedings 11th REHVA World Congress, CLIMA 2013
[Pfluger 2013b] Pfluger, R., Feist, W.,
Hasper, W.: The use of coaxial ducts in ventilation systems, Pollack Periodica,
Vol. 8. No. 1, 2013, S. 89-96
[Pfluger 2013c] Pfluger, R., Speer C., Feist W., Weger J.,
Zgaga J.: Entwicklung
eines hocheffizienten Ventilators mit integrierter Gegenstromwärmerückgewinnung
für den Einsatz in der Gebäudemodernisierung, Bauphysik 4/2013
www.3encult.eu
www.buildup.eu/communities/culturalheritage
This work was financially supported by the EU FP7 program (GA n. 260162). The authors wish to express their gratitude for the financial support.