Jarek Kurnitski | Johann Zirngibl |
REHVA Technology and Research Committee, Tallinn University of TechnologyE-mail: jarek.kurnitski@taltech.ee | Ingenieurunion – Germany |
The EPBD recast proposal dated 15.12.2021 defines in article 2.2:
Article 16 « Energy performance certificates » requires that class A of an EPC shall correspond to zero-emission buildings. The definition of the best energy performance class A shall ensure the convergence of the energy performance class scale towards a common understanding of zero-emission buildings.
Annex III provides additional details:
· The total annual primary energy use of a new or renovated zero-emission building shall be fully covered, on a net annual basis, by
− energy from renewable sources generated on-site and fulfilling the criteria of Article 7 of Directive (EU) 2018/2001 [amended RED],
− renewable energy provided from a renewable energy community within the meaning of Article 22 of Directive (EU) 2018/2001 [amended RED], or
− renewable energy and waste heat from an efficientdistrict heating and cooling system in accordance with Article (24(1) of Directive (EU) …/… [recast EED]
· A zero-emission building shall not cause any on-site carbon emissions from fossil fuels
· Only where, due to the nature of the building or lack of access to renewable energy communities or eligible district heating and cooling systems, it is technically not feasible to fulfil the requirements under the first paragraph, the total annual primary energy use may also be covered by energy from the grid complying with criteria established at national level.
· Total primary energy
There was a discussion among the total primary energy used in EPBD. It seems that this is partly caused by some terminology issues. There are differences in energy terminology details in EED (and energy statistics) and EPBD, coming from the scope and purpose of directives.
EPBD use bottom-up definitions for energy calculation in buildings and makes a reference to European standards, especially to the overarching EPB standard EN ISO 52000-1.
EED recast Article 2 ‘primary energy consumption’ definition is different from total primary energy, because EED defines primary energy as the gross available energy from which ambient heat is excluded.
Amended RED defines clearly that solar thermal, solar photovoltaic, geothermal energy and ambient energy are renewable energy and therefore are to be accounted in the total primary energy in the context of EPBD.
Historically this might have been the reason that EPBD used just ‘primary energy’ which was specified in the cost optimality regulation and EN standards to be non-renewable primary energy. Because EED recast Article 2 definition 44 ‘efficient individual heating and cooling’ uses non-renewable primary energy, this should be used consistently throughout EPBD to enable meaningful energy calculation.
· “net” annual basis
“net” is not defined in the EPBD recast proposal.
It is understood that “net” emphasizes the energy exchange between the building (e.g. exported on-site PV) and the energy infrastructure (e.g. electricity grid).
It is proposed to add a definition of “net” (see proposal in “summary”
· fully “covered”
it is understood that the low amountof energy still required can be supplied by other energy carrier than the renewables defined in annex III, e.g. by the electrical grid, but that the total primary energy use amount shall be compensated (equal or lower) by the amount of renewable energy from on-site, energy communities or district heating
It should be made clear that other energy carriers than those mentioned to “cover” the energy still required can be used. This formulation excludes the renewable part of electricity from grid.
It is proposed to change “covered” by “compensate” and to include renewable energy from the energy infrastructure in the compensation.
It is not specified how the compensation has to be done, for example only by self-use, or also by exported energies. As some countries allow exporting energy others not, this decision can be taken at national basis.
If exported energy is not taken into account, the self-use of PV will be accounted on a net annual basis.
· No on-site carbon emission
The EPBD recast proposal states that a zero-emission building shall not cause any on-site carbon emissions from fossil fuels. Therefore, the possible delivered energy carriers of ZEB will only be:
· district heating and cooling;
· biomass;
· grid electricity and on-site and nearby PV electricity.
This formulation is not technology neutral because gas boilers and cogenerationare phased out on-site while they are admitted at district heating level until 2050 according to EED recast.
A technology neutral option would be to require that emissions from fossil fuels shall be compensated by renewable energy generation.
· Technically not feasible
If “due to the nature of the building …it is technically not feasible to fulfil the requirements …the total annual primary energy use may also be covered by energy from the grid complying with criteria established at national level”.
This clause makes it possible to side pass the requirements.
It is proposed to delete this clause. If it is technically not feasible to fulfil the requirements, then the building will simply not be able to reach the zero-emission level.
Attention:
Class A of an EPC shall correspond to zero-emission buildings (article 16).
There are several requirements (e.g. threshold, coverage) to be fulfilled to be classified as zero emission building.
It is not defined what happens if one of these definitions is not fulfilled.Which class the building will be if not all requirements are reached? It is needed to define a class A for the EPC.
In the example hereafter (Figure 1) ZEB requirements in the EPBD recast proposal are applied to aNZEB apartment building in Nordic climate to check if and under which conditions these requirements could be fulfilled.

Figure 1. Example case: Comparison of NZEB building in Nordic climate and the zero-emission level.
This building configuration meets current Estonian NZEB requirements with District heating (DH) and Ground Source Heat Pump (GSHP) if PV generation is 16 kWh/(m².y). Air to Water Heat Pump (AWHP) would need some improvement and gas would need major changes.
EPBD recast proposal sets, as first requirement, the total primary energy for residential ZEB in Nordic climate to 75 kWh/(m².y).
Figure 1 indicates the primary energy factors and CO₂ emission coefficients of the different energy carriers (including renewables as thermal energy extracted by the heat pumps).
Figure 1 line “EPBD No 1” shows that only the gas boiler will reach this first requirement of the zero-emission definition when calculated with PV export. Especially heat pump systems will have difficulties because the total primary energy (see table 1) includes the renewable part taken form the environment.
The second requirement in the ZEB definition ask to fully cover, on a net annual basis, the total primary energy use by renewables (without renewables from the energy infrastructure). Figure 1 line “add. PV to cover “tot. prim. energy” shows that to fulfil this requirement a high amount of additional on-site PV generation would be needed. This would be practically impossible in the example because the roof allows only to install24 kWh/(m².y) PV generation.
These results show that the total primary energy-based requirements are not sound.
· First requirement (threshold on primary energy use):
It is proposed to revise the first requirement by changing from “total primary energy use” to “non-renewable primary energy use”.
Rational:
If “total primary energy” is calculated according to existing, physical correct definitions (including the ambient heat recovered by the heat pump, heat pumps will have very high total primary energy use because of extracting energy from ambient. The valorisation of on-site renewables will be less.
Figure 1 shows that the non-renewable primary energy-based requirements can be reached. It is in line with the NZEB definition. The non-renewable primary energy use will allow to limit the non-renewable primary consumption and valorise the renewables.
It is understoodthat the reason to use the total primary energy was chosen to keep a good quality of the building envelope and high system efficiencies which should not be possible to compensate with extensive amounts of renewable energy generation. Therefore, by changing from “total” to “non-renewable” primary energy this limitation must be re-established.
These limitations could be related to the building needs (e.g. for NZEB building), to the efficiency of the technical building systems, etc. They should be defined in the chapter related to NZEB buildings.
It is proposed that Annex III refer to it.
· Second requirement (zero emission level):
The first requirement is close to the definition of a nearly zero (non-renewable) primary energy building (low amount of energy). The second requirement of the EPBD recast proposaladd as zero-emission level bythe coverage (compensation) of the total primary energy use by renewables.
It is proposed to replace the coverage of the total primary energy use by the coverage of the CO₂ emissions. This makes this requirement straightforward, clearly focussing on the target of zero-emission.
To illustrate how to reach to zero-emission level Figure 1 line “add. PV to compensate CO₂ emission” shows the amount of how much additional PV should be installed to cover the emissions. It is likely that zero-emission is not reachable in Nordic climate, because of the higher heat losses and lower solar radiation than in southern countries. Future cost optimality calculations, including better insulation, DHW heat recovery, higher system efficiency or a higher amount of delivered renewables, would help to clarify the situation.
If including onsite renewables in the total primary energies, the total primary energy does not allow meaningful energy calculation because not distinguishing renewable not causing CO₂ emissions from non-renewable energy causing CO₂ emissions. Also, the sustainability of renewables is neglected.
Attention is also drawn to the target of ZEB definition to be zero-emission. Not primary energy but CO₂ emissions should be fully covered/compensated by renewable energy to be zero-emission.
Therefore, and to clarify several terms, the following improvements could be proposed:
“Net energy” means the balance of energy exchange between the building (e.g. exported on-site PV) and the energy infrastructure (e.g. public grid).
“zero-emission building” means a building with a very high energy performance, as determined in accordance with Annex I, where the very low amount of CO₂ emissions due to energy still required use is fully coveredcompensated by energy from renewable sources generated on-site, from a renewable energy community within the meaning of Directive (EU) 2018/2001 [amended RED] or from a district heating and cooling system or from energy infrastructure, in accordance with the requirements set out in Annex III.
The total non-renewable annual primary energy use “of a new zero-emission building shall comply with the maximum thresholds indicated in the table below. If the national cost optimal level has a higher ambition than the national level shall apply.
An additional requirement shall be added to avoid that the energy use (building quality) is too much compensated by renewable energy.
Replace “total” by “non-renewable” in the table and note.
· The total annual primary energy useCO₂ emission of a new or renovated zero-emission building shall be fully coveredcompensated, on a net annual basis, by energy from renewable sources generated on-site, energy infrastructure and fulfilling …
·
With proposed changes the following requirement
becomes redundant and can be deleted.
A zero-emission building shall not cause any on-site
carbon emissions from fossil fuels.
· To avoid negative side-effect of exceptions, delete the following:Only where, due to the nature of the building … from the grid complying with criteria established at national level.
The proposed updates of the ZEB definition summarise the EU's main objectives (Energy efficiency, use of renewables, CO₂ neutrality) with a couple of common indicators. This set of indicators is based on the NZEB definition, underlining the convergence of the energy performance class scale towards zero-emission buildings by limiting negative effects of a single indicator.