At the end of 1997, the Lyon CAF moved into
new offices on boulevard Vivier-Merle in Lyon. The building has office space,
meeting rooms, a conference room and a reception area for beneficiaries.
Concerned about future running costs, the Lyon CAF asked its design division to
look into the different heating and cooling systems that could be used for the
site. Research revealed the ground source heat pump to be the most efficient.
The building has a surface area of 16,633 m² with a coefficient of loss through the walls of 0.42 W/m³°C (for G1 ref. of 0.53 W/m³°C). The installation comprises two water/water heat pumps (600 kW hot, 600 kW cold) which feed a network of 4-pipe fan coils and processing units comprising recuperators to limit energy consumption.
The hydraulic systems are fitted with variable speed pumps. The well comprises two variable speed boring pumps with a maximum flow rate per unit of 100 m³/h.
It is important to mention that investment
costs in 1995 stood at €149/m² for heating, ventilation and air conditioning
and €21/m² for the BMS, making a total of €170/m².
The heat pumps are controlled in
thermorefrigerating pump mode. A thermo frigo pump is a reversible heat pump
which can be used for both cooling and heating. It is an ideal solution in
terms of energy costs for buildings which have both cooling and heating needs.
Operating conditions:
· Chilled water is 7-12 C in summer and 10-12 C in winter.
· Hot water is 35°C when it is above 20°C outside and 45 °C when it is 0°C outside. The whole installation is managed by a BMS (Building Management System).
This is based on a fundamental principle: “always satisfy the highest demand”. The BMS must continuously measure the differences in temperature between the two systems (hot and cold). Depending on which system has a higher demand, it determines the operating conditions for the thermorefrigerating pump by prioritising hot or cold operation.
A thermorefrigerating pump has five different modes, including:
1. Heating mode. This mode is used during
cold spells. To achieve thermal equilibrium, all the cold produced by the units
is discharged into the well.

2. Majority heat and minority cold. The
building consumes more heat than cold (mid-season and start of winter). Surplus
cold is discharged into the well.

3. Heat equal cold. This mode is used when
the building consumes all the cold and heat produced. The COP is at its maximum
and no energy is discharged into the well.

4. Majority cold and minority heat. The
building consumes more cold than heat (mid-season and end of winter). Surplus
heat is discharged into the well.

5. Cooling mode. This mode is used during
summer. To achieve thermal equilibrium, all the heat produced by the units is
discharged into the well.

This site has been monitored for energy performance since 1998 with installation carried out by EDF R&D using 9 electricity meters (6 with remote reading), 1 calorie meter, 1 frigorie meter and 1 BMS remote investigation and monitoring system.
Below can be found the average consumptions and performances over 13 years (1998 to 2010).
· The total average consumption is 158 kWh/m² for an average cost of €8.8/m² excluding taxes and the maximum demand is 760 kW.

Consumption ranged from 145 kWh/m² in 2000 to 170 kWh/m² in 2008.
It should be noted that the average annual
consumption ratio in the office sector is approximately
250 kWh/m².
· Operating costs ranged from €7.7/m² excluding taxes in 2000 to €10.45/m² excluding taxes in 2010.
For information, we can regard a building as having satisfactory energy operating costs if its operating costs are no more than €11/m².
· The consumption of the geothermal thermo frigo pump and the well pumps is 40 kWh/m² (€2.6/m² excl. taxes), supplying an average of 67 kWh/m² of heat and 83 kWh/m² of cold.
The average cost of producing MWh of heat/cold is €17/MWh excluding taxes.
Compared to a traditional system (gas heating and refrigeration unit), the ground source heat pump solution gives an annual saving of €2.2/m² excluding taxes, i.e. a reduction in energy costs for heating and cooling of 48%.
It results in a fall in CO2 emissions of 14.8 kg/m², i.e. a 72% reduction.
The system’s Coefficient of Performance
(COP)* over the 10 years is 3.73 on average, meaning that for every kWh of
electricity consumed, the system supplied 3.73 in the form of heat or cold.
EDF recommended the installation of variable speed pumps for the hot and cold systems and for the boring pumps. The savings made from these variable speed drive units are as follows:
· For the bore hole pumps: 86,338 kWh or €4,055.
· For the cold water system pumps: 82,684 kWh or €4,179.
· For the hot water system pumps: 90,099 kWh or €4,277.
This gives an average saving of 259,121 kWh p.a. and €12,512 p.a. excluding taxes, which represents 10% of the building’s annual consumption and 40% of the annual consumption of the reversible heat pumps.
The additional cost for hydraulic
disconnection and the variable speed drive units was €36,000 excluding taxes,
meaning a 3-year return on investment! Monitoring has shown that a ground
source heat pump system is efficient in the long term and saves energy and
money while reducing the impact on the environment.
*COP = Hot and cold energy supplied to the building / Electrical energy consumed by the heat pumps + the well pump.
With this monitoring, you can observe that the geothermal thermo frigo pump is economically efficient and respect the environment.