Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Keywords: Air distribution, patient rooms, airborne infection, infector location, tracer gas
|
|
|
|
|
Jixuan Bao | Risto Kosonen | Simo Kilpeläinen | Kim Hagström | Jukka Vasara |
Department of Civil Engineering, Aalto University, Finlandjixuan.bao@aalto.fi | Department of Civil Engineering, Aalto University, Finland | Department of Civil Engineering, Aalto University, Finland | Halton Oy, Finland & | Granlund Oy, Finland |
General patient rooms accommodate patients, healthcare workers, and family visitors, making it difficult to identify the infectious source during daily operation [1]. Since the COVID-19 outbreak in 2019, international guidelines have placed increasing emphasis on airborne contaminant control in healthcare environments through improved ventilation strategies [2,3].
Mixing ventilation is widely applied in hospitals because it is well-known and provides uniform air distribution throughout the room [4]. In contrast, local air distribution methods deliver clean air directly to the occupied zone, providing targeted protection for occupants [5,6]. Previous studies have demonstrated the effectiveness of personalized bed-integrated ventilation close to the breathing zone [7], and occupant-targeted ventilation using jet-integrated panel diffusers that generate parallel airflow towards the patient bed [8].
This study compares different air distribution strategies for controlling airborne contaminants in general patient rooms. The effects of folded and unfolded privacy curtains are also evaluated. The results provide practical guidance for selecting air distribution methods to achieve targeted protection in patient rooms with unspecified infectors.
The experiments were carried out in a full-scale climate chamber at Aalto University, configured as a mock-up of real double-bed patient room. Figure 1 presents the room layout, measurement locations, and the tested air distribution methods. Three occupants were simulated in each test: one infector represented by a thermal breathing manikin and two susceptible occupants represented by heated dummies. The chamber measured 5.50 m × 3.80 m × 2.70 m (length × width × height).

Figure 1. Measurement points and the location of air diffusers in the mock-up patient room. M2 represents the primary infector location, while M5 is used as an alternative infector location in a separate scenario.
For the air distribution methods, four configurations were investigated: mixing ventilation (MV), occupant-target ventilation (OTV), exposed-side attachment ventilation (E-ATT), and infected-side attachment ventilation (I-ATT). MV supplied air through a four-way nozzle diffuser located at the center of the ceiling. OTV used a dynamic protective airflow panel installed above each patient bed. Both E-ATT and I-ATT supplied air through a perforated duct with a deflector mounted near the ceiling on the left side of the chamber.
Tracer gas (SF6) measurements were carried out simultaneously at nine locations under a heat gain of 17 W/m² and an airflow rate of 80 L/s. The measurement points are described in Table 1. SF6 was released from the breathing manikin to simulate virus-containing exhaled air. Before each test, the tracer gas concentration was allowed to reach steady state, followed by a two-hour measurement period. Infection probability was calculated using the dilution-based Wells–Riley model [9].
In the model, quanta generation rates of 3 and 16 quanta/h were assigned to a non-speaking patient and a speaking standing staff member, respectively[10]. The breathing rate of the infector was fixed at 0.36 m³/h [11]. For the susceptible occupants, breathing rates were determined according to their metabolic levels, with values of 0.24 m³/h for the patient and 0.45 m³/h for the staff member[12]. Table 2 summarizes the six test cases, including the air distribution method, privacy curtain configuration, and infector location.
Table 1. Locations and characteristics of the measurement points in the test chamber.
Location | M1/M2 | M3/M6 | M4/M5 | M7/M8 | M9 | M10 |
Height (mm) | 1000 | 1200 | 1600 | 1600 | Ceiling | 2000 |
Description | Lying | Seated | Standing | Standing | Total exhaust | Toilet exhaust |
Table 2. Test cases with different air distribution methods.
Case | Air distribution | Curtain | Infector |
1 | MV | Closed | Patient (M2) / Staff (M5) |
2 | MV | Open | Patient (M2) / Staff (M5) |
3 | OTV | Closed | Patient (M2) / Staff (M5) |
4 | OTV | Open | Patient (M2) / Staff (M5) |
5 | I-ATT | Closed | Patient (M2) / Staff (M5) |
6 | E-ATT | Closed | Patient (M2) / Staff (M5) |
Note: Each test case was conducted twice, with infector locations at the patient (M2) and staff (M5).
Figure 2 shows the infection probability for the patient infector located at M2. Compared with the fully mixed reference, the exposed patient (M1) consistently experienced a lower infection probability, whereas the standing staff member (M5) showed a higher infection probability. At M1, the results were similar across all air distribution methods and remained below 0.5%. At M5, I-ATT had the lowest infection probability, reducing the local exposure risk by 12% relative to the reference condition. In contrast, OTV resulted in the highest infection probability, which was 58% above the reference value. The limited distance between the two patient beds likely disturbed the local airflow around the standing healthcare worker, reducing the protective effect of OTV. Changing the privacy curtain from folded to unfolded had little influence on the infection probability.

Figure 2. Infection probability at two susceptible locations with the patient (M2) as the infector, relative to the fully mixed reference condition (CRE = 1, M9).
Figure 3 shows the infection probability when the standing staff member at M5 acted as the infector. At M1, the infection probability varied only slightly among the air distribution methods and remained below the fully mixed reference value. For the susceptible patient at M2, OTV reduced the infection probability from 58.0% above the reference in the patient-infector scenario to 8.6% below the reference in the staff-infector scenario. This clear shift confirms that OTV performance strongly depends on the infector location. The downward protective airflow effectively limited pollutant transport from the higher breathing level by supplying clean air above the patient and removing contaminants before they reached the lower breathing zone. In contrast, E-ATT and I-ATT produced the highest infection probabilities at M2 in the staff-infector scenario.

Figure 3. Infection probability at two susceptible locations with the staff member (M5) as the infector, relative to the fully mixed reference condition (CRE = 1, M9).
This study examined airborne transmission from two infector locations in a mock-up double-bed patient room, with the source represented by either a lying patient or a standing staff member. Unlike studies limited to a single infector type, the results show that the performance of occupant-targeted ventilation and attachment ventilation depends strongly on the infector location and room-use scenario.
Occupant-targeted ventilation provided better protection when the standing staff member was the infector, indicating its suitability for periods involving close staff–patient interaction, such as medical care and ward rounds. Attachment ventilation performed better when the lying patient was the infector and is therefore more suitable for general ward operation. The limited spacing between the two beds affected local airflow distribution, so the findings should be interpreted within the tested room configuration.
In practice, air distribution should be adapted to the occupied zone and the likely infector location while avoiding pollutant transport towards downstream occupants. Further testing under different ward layouts, airflow rates, and operating conditions is required before wider application. The results support the development of flexible occupant-based airflow control that combines infection control with energy-efficient operation.
The HumanIC project has received funding from the European Union’s Horizon Europe research and innovation program under the Marie Sklodowska-Curie (HORIZON-MSCA-2022-DN-01, project no. 101119726). Views and opinions expressed are, however, those of the author(s) only and do not necessarily reflect those of the European Union. Neither the European Union nor the granting authority can be held responsible for them.

[1] J. Bao, R. Kosonen, S. Kilpeläinen, K. Hagström, J. Vasara, Airborne infection risk between patients and healthcare staff under different air distribution strategies: A test chamber study, Build. Environ. 302 (2026) 114828. https://doi.org/10.1016/j.buildenv.2026.114828
[2] REHVA, REHVA COVID-19 guidance (GEN-1098.00), Eurovent (2020).
[3] R3 Nordic, R3 Nordic Guideline for Hospital Ventilation - General Requirements, Operating Suites, and Isolation Rooms, R3 Nord. (2024).
[4] F.A. Berlanga, I. Olmedo, M.R. de Adana, J.M. Villafruela, J.F.S. José, F. Castro, Experimental assessment of different mixing air ventilation systems on ventilation performance and exposure to exhaled contaminants in hospital rooms, Energy Build. 177 (2018) 207–219. https://doi.org/10.1016/j.enbuild.2018.07.053
[5] S. Sheng, T. Yamanaka, T. Kobayashi, N. Choi, N. Chou, Performance of all-air wall induction unit for displacement ventilation in a four-bed hospital ward during the cooling period, Build. Environ. 248 (2024) 111101. https://doi.org/10.1016/j.buildenv.2023.111101
[6] H. Yin, A. Li, Z. Liu, Y. Sun, T. Chen, Experimental study on airflow characteristics of a square column attached ventilation mode, Build. Environ. 109 (2016) 112–120. https://doi.org/10.1016/j.buildenv.2016.09.006
[7] W. Su, Z. Ai, B. Yang, A new personalized environment control system for hospital beds with design optimization by Taguchi-based grey relational analysis, Build. Environ. 267 (2025) 112206. https://doi.org/10.1016/j.buildenv.2024.112206
[8] K. Hagström, I. Grönvall, P. Kalliomäki, H. Maula, A. Sivula, Comfort evaluation of a dynamic protective airflow system using human test subjects, CLIMA 2022 Conf. (2022). https://doi.org/10.34641/clima.2022.87
[9] S. Zhang, Z. Lin, Dilution-based evaluation of airborne infection risk - Thorough expansion of Wells-Riley model, Build. Environ. 194 (2021) 107674. https://doi.org/10.1016/j.buildenv.2021.107674
[10] A. Aganovic, J. Kurnitski, P. Wargocki, A quanta-independent approach for the assessment of strategies to reduce the risk of airborne infection, Sci. Total Environ. 927 (2024) 172278. https://doi.org/10.1016/j.scitotenv.2024.172278
[11] W. Zhao, M.F. Ejaz, S. Kilpeläinen, J. Jokisalo, R. Kosonen, The potential of local exhaust combined with mixing and displacement ventilation systems to mitigate COVID-19 transmission risks, Build. Environ. 266 (2024) 112076. https://doi.org/10.1016/j.buildenv.2024.112076
[12] ASHRAE, ASHRAE handbook—Fundamentals (SI Edition), Chapter 9: Thermal comfort, Am. Soc. Heat. Refrig. Air-Cond. Eng. Inc (2023).
Follow us on social media accounts to stay up to date with REHVA actualities
0