Buildings energy efficiency targets have led
the research interest toward new energy saving strategies to be integrated into
the design, construction, and operation of new and retrofitted existing
buildings. Particularly for sizing and optimising purposes (especially for
NZEBs), advanced energy analysis tools should be adopted to analyse the
potential effects of crucial design and operating variables on the building
energy performances. Aim of this work is to present the results of a
comprehensive energy analysis, carried out through an in-house validated
dynamic simulation code written in MatLab (called DETECt 2.2 [1]), and referred to a non-residential
multi-zone NZEB to be located in Naples, Southern Italy [2]. In such building,
electricity is produced through a BIPV/T system, while heat is obtained by
innovative integrated solar collectors (also driving a double stage absorption
chiller for solar cooling). Different novel building integrated energy saving
techniques are taken into account: PCM, sunspace, smart daylighting, etc. A
suitable parametric analysis is carried out in order to identify the optimal
set of design and operating parameters that minimizes the building heating and
cooling energy consumptions. Details about the simulation results and the
economic feasibility of all the considered energy efficiency techniques are
provided. According to the authors’ knowledge the presented non-residential
NZEB is the first one conceived for Mediterranean climates.
The building will be built up in Naples
(Southern Italy, 40°20'N … 14°15'E), which features a Mediterranean temperate
climate with rather hot and humid summers (CDD = 185 Kd, design
temperature and humidity: 32°C and 60%) and quite mild
winters (HDD = 1 163 Kd, design and average temperature: 2 and 10°C).
The project
initiative stems from the action ED6 of the Sustainable Energy Action Plan
(SEAP, Covenant of Majors of the European Community, August 3rd 2012) and from an explicit
Resolution (n. 517 on April 21st 2011) of the Municipality of
Naples. The NZEB will be built up on three floors, two of them above the ground
level (Figure 1). It will host offices (at the
ground floor) and conference and exposition spaces (at the first floor).
Equipment rooms and stories will be located at the basement.

Figure 1. Non-residential NZEB to be built up in Naples, southern view.
In order to fulfil the criteria for passive heating and cooling techniques, the building is subdivided in ten thermal zones and it is conceived with a rectangular shape (15.0 × 24.5 m, East-West oriented longitudinal axis) with a S/V ratio equal to 0.38. In order to minimize the primary energy demand, several design parameters have been optimizedthrough a validated simulation code, DETECt 2.2, which easily enables the automatic comparison of multiple building scenarios by a single simulation run [1, 3]. Several obtained building features are reported in Table 1.
Table 1. Building envelope features.
Building element | Density [kg/m³] | Transmittance U [W/m²K] | Embedded PCM layer | Note |
Vertical walls | 800 (brick layer) | 0.23 | Yes (3 cm) | |
Tilted roof | 1 050 (concrete slab) | 0.23 | Yes (3 cm) | |
Sunspace (exterior), East
office, conference room windows | - | 1.6 | No | Emissivity = 0.10. 6/13/6 glazing filled by Argon. SHGC = 0.58 |
Other windows | - | 0.9 | No | Emissivity = 0.10. 6/8/6/8/6 glazing filled by Krypton. SHGC = 0.46 |
For optimizing the winter heat loss and the
yearly solar heat gains and radiation loads, windows are designed only on the
southern façades (Figure 1). Thus, the low building
window to wall surface area ratio (about 15%) reaches 70% if referred to the
southern façade only. Here, first floor terrace
windows are equipped by external variable tilt solar shadings. At the southern
side of the ground floor, a sunspace is designed to maximize the winter passive
heating. Such space becomes (by opening the external sliding windows) a shaded
open porch during summer. The porch ceiling width and height are optimised to
prevent indoor space superheating (Figure 2).
More details are reported in [2].
The roof surface is 70% (135 m²) covered by mono-crystalline BIPV/T panels (16.5 kWp). The remaining roof area (58 m²) is equipped by innovative building integrated flat-plate evacuated solar thermal collectors (37 kWp), providing space solar heating and cooling and DHW preparation. For both such technologies, energy performance and passive effects on the thermal building behaviour were dynamically assessed through DETECt. The roof integrated PV/T system is cooled by an air stream of 0.5 kg/s, which provides free space heating during the middle seasons. For enhancing the system energy performance, the BIPV/T system is suitably coupled to PCM panels. In summer, the hot fluid obtained by the solar thermal panels (up to 250°C) is exploited for space cooling (HVAC system supported by a 26 kW double stage absorption chiller). The passive effect of such innovative solar thermal collectors is low due to their high thermal insulation (deep vacuum up to 10-9 mbar). The HVAC system backup is obtained through a 38 kW geothermal heat pump/chiller. Heating and cooling is provided to the indoor spaces through a fan coil and primary air system (AHU of 2 500 m³/h) supported by ground-to-air and air-to-air heat exchangers (with summer evaporative cooling unit).

Figure 2. Winter sunspace, summer porch and solar radiation optimization.
The dynamic energy performance analysis is carried out through DETECt 2.2 [1-3]. Weather conditions are simulated according to the IWEC hourly data of Naples. The simulation starts on January 1st and ends at December 31st. Heating is activated from November 15th to March 31st and cooling from June 1st to September 30th (August excluded), both from 9:00 to 18:00. The winter indoor air set-point is 20°C (sensible heating only). The summer set-points for temperature and humidity are 26°C and 60% (sensible cooling and dehumidification). Occupancy rates are: offices 9 h/day, 5 d/week; expo spaces 9 h/day, 3 d/week; conference room 9 h/day, 1 d/week. Ventilation rates and internal loads are set as the standard ones for the simulated building uses.
The results of the energy analysis are shown in Figure 3. Here, the reported percentages are referred to the produced, consumed and exported primary energy for electricity, cooling and thermal uses, respectively. Primary energy produced and consumed on site and exported surplus are equal to 153.7, 40.9 and 108.1 kWh/m²y, respectively. The heating and cooling energy demands are very low resulting almost entirely covered by solar energy production (about 90 and 93% of the energy demands for heating and cooling are balanced by renewable energy). The electricity demand (about 53% of the overall building energy one) is mainly due to ventilation, lighting (optimized by modulating the windows shadings according to the optimal visual comfort) and appliances (rather high, about 42% of the demand, according to the considered building uses). The contribution on the overall balance of renewable energies is equal to 235% (remarkably high because of the large solar field designed to supply energy also to an adjacent public building) while the imported primary energy requirement is equal to 32.0 kWh/m²y. Note that according to the Italian rules (UNI TS 11300 - Italian release of EN 13790), the NZEB heating primary energy and cooling energy (not primary) demands result 1.92 kWh/m³y and 9.39 kWh/m²y, respectively (corresponding to the best energy efficiency classes: A+ and I).

Figure 3. Annual energy analysis results.
A simplified economic analysis, referred only to the extra-costs to be considered vs. a standard NZEB configuration (fulfilling the requirements of the Italian rules for the buildings energy efficiency) was also carried out. Such overall extra-cost reaches 48.2 k€ and decreases to 1.6 k€ without PCM adoption. In this case (no PCM) the SPB period (selling the exported electricity at 0.08 €/kWh) is of about 14 years without national funding. With PCM the resulting SPB period is currently too long.
Authors wish to gratefully acknowledge Action
TU1205 (Building Integration of Solar Thermal Systems, BISTS) of the European
COST, for the sponsorship and scientific support.
[1]Buonomano A., Palombo A. Building energy performance analysis by an
in-house developed dynamic simulation code: An investigation for different case
studies. Applied Energy. 2014;113:788-807.
[2]Buonomano A., De Luca
G., Montanaro U., Palombo
A. Innovative technologies for NZEBs: An energy and economic analysis tool and
a case study of a non-residential building for the Mediterranean climate.
Energy and Buildings. 2015; http://dx.doi.org/10.1016/j.enbuild.2015.08.037.
[3]Buonomano A., Palombo A. NZEBs design and simulation: a new tool for dynamic energy performance analyses. ECOS 2014, 27th Int. Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact of Energy systems.