Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Mehrdad
RabaniPhD
research fellow at Oslo Metropolitan UniversityEmail:
Mehrdad.Rabani@oslomet.no | Habtamu Bayera MadessaAssociate professor at Oslo Metropolitan
UniversityEmail: Bayera.Madessa@oslomet.no | Natasa NordAssociate
professor at Norwegian University of Science and TechnologyEmail: natasa.nord@ntnu.no |
Substantial
reductions in energy use can be achieved by promoting low energy building
technologies such as all-air systems. There is an idea that integrating active
supply diffuser with all-air systems can potentially improve their performance.
This paper numerically investigated the performance of an all-air heating system
equipped with an active supply diffuser in a cell office, constructed based on
Norwegian passive house, in terms of indoor air quality and thermal comfort of
occupants. Simulations were performed using commercial Star-CCM+ software. The
numerical results were validated using the available experimental data on the
active supply diffuser from an office. The results showed that adopting active
supply diffuser can avoid temperature stratification, which is the main
reported issue in heating application of conventional all-air systems, and
provide the thermal comfort with PPD ≤ 7% in most part of
occupancy zone.
Nowadays,
low energy building technologies have drawn many attentions due their potential
in substantial reductions of building energy use. The low energy HVAC systems
can be considered as a practicable solution when the building space heating
demands, especially in cold climate countries are really low. The passive house
(PH) concept is an example in this point that aims at promoting the energy
efficiency of buildings by significant reduction of space heating needs using a
strict insulation level of building envelope. Consequently, it is reasonable to
simplify the space heating system by covering both ventilation and space
heating needs using a so-called all-air heating (AAH) system. The all-air
heating means to supply warm air, usually at ceiling level, at a hygienic air
flow rate. However, the system performance, depending on supply air temperature
and flow rate, thermal load, and outdoor conditions, might not be desirable due
to the presence of vertical air temperature gradient (temperature stratification)
and poor indoor air quality (IAQ) due to ineffective mixing of supply air flow
with the convective plum of occupants and equipment in the zone of occupancy.
In this
regard, the AAH system performance was investigated by several research
studies. Fisk et al. [1] conducted
several experiments with a ceiling supply/exhaust configuration and the results
supported a significant short-circuiting of ventilation air between the supply
air diffuser and return air. The same phenomenon was also reported by Offermann and Int-Hout[2]. A significant stratification of
contaminants in the lower part of the occupancy zone [3], poor air distribution and temperature stratification [4], a stationary region in the zone of
occupancy [5], and non-uniform
distribution of air velocity and temperature [6] were other reported issues
associated with the application of AAH. Therefore, the AAH system performance
needs to be improved in order to be considered as a functional solution for
HVAC system in cold climate countries.
The aim of
this study was to remedy the aforementioned issues in AAH systems using an
active supply diffuser. The existing constant air volume (CAV) system could be
converted to a variable air volume (VAV) system by installing active supply
diffuser and isolating existing duct systems. Figure 1
illustrates how the active supply diffuser functions. In typical VAV systems
without active supply diffuser, the supply air velocity changes as the supply
air flow rate changes due to constant supply area. This may increase the risk
of draft in AAH systems, especially at low air flow rates. To solve this
problem, the active supply diffuser will change the supply area proportional to
the air flow rate so that a constant supply velocity is achieved for different
air flow rates.
Figure 1.
Conceptual schematic of active supply diffuser application in AAH system.
This study
used Star-CCM+ software to analyze the performance of the AAH system equipped
with the active supply diffuser in a cell office, constructed based on the
Norwegian PH standard [7] and located in
a Nordic climate. Figure 2 shows the cell office
configuration dimensions, and type of active supply diffuser. The active supply
diffuser in this system was a TTC-250 active supply diffuser comprised of
several moving plates [8]. For the
boundary condition the inlet of the active supply diffuser was modelled using
constant air velocity profile. Pressure outlet with zero gage pressure was
considered for the exhaust. Lighting, PC, and occupant were modelled using
constant heat source boundary condition 136W, 120W, and 30W, respectively. The
external wall, internal wall, window, floor, and ceiling were modelled using
heat transfer boundary conditions calculated from the energy balance with
overall heat transfer coefficients taken from the experimental study [9].
(a) |
(b) |
Figure 2. (a) Cell
office configuration and dimensions and (b) TTC-250 active supply diffuser. |
In order to
evaluate the performance of AAH system with active supply diffuser the
following parameters and index were defined:
■ Archimedes
number (Ar): describes the
characteristics of supply jet and was defined according to the Eq. 1 for
mixing ventilation system.
(1) |
where Ts was the supply air
temperature, Te
was the exhaust air temperature, u0 was the supply air velocity, and β was the coefficient of thermal expansion, a0 was the net opening area of the supply, and Qs wasthe
ventilation air flow rate.
■
Predicted mean vote (PMV) and predicted percentage of dissatisfied (PPD) – show
the thermal comfort of occupants. PMV examines the occupant thermal sensation
according to seven scale points (from −3, cold, to 3, hot) with regard to
six factors the air temperature, the mean radiant temperature, the air
velocity, the air humidity, physical activity and clothing isolation level. PPD
gives the thermal dissatisfaction predicted by PMV quantitatively. In order to
have a favorable environment for a building with low energy use, the PPD should
be less than 10% associated with −0.5< PMV < 0.5
[10].
The
numerical method was validated using the available experimental data. The
details of experimental setup can be found in [11].
Figure 3 indicates the location of experimental sensors
and the comparison of air temperature and velocity obtained from simulations
with the experimental data. It is observed that the results of simulations were
in the uncertainty range of experimental data.
(a) |
(b) |
(c) |
Figure 3. (a) location
of experimental sensors, (b) air velocity and (c) air temperature variations
at the measurement points. |
The
performance of the system was analyzed for the most critical condition with the
outdoor temperature −20 °C, which was the design outdoor temperature
for Oslo, Norway, in the winter season [12].
The active supply diffuser was also operated under two different air flow
rates: the minimum air flow rates required by the Norwegian PH standards and
the maximum air flow rates for which the active diffuser could operate. Table 1
describes the details of two scenarios. The negative Archimedes number shows
that a negatively buoyant air was supplied.
Table 1. The main parameters for the scenarios
investigated in this study.
Scenario | Tout
(°C) | Ts (°C) | V̇s(l/s) | Ar |
S1 | −20 | 24.8 | 49.4 | −1.56×10-3 |
S2 | −20 | 26.4 | 16 | −1.73×10-3 |
Figure 4 illustrates the temperature stratification and
air distribution for two cases. Maximum temperature stratification between
seated head level and ankle level was around 1.5 K (Figure 4a),
which was within the maximum recommended range by the EN ISO 7730 standard
for the IAQ category II, indicating that active supply diffuser could
avoid temperature stratification at both maximum and minimum air flow rates.
This can be also seen in Figure 4b where the throw length
towards internal wall (left side) was preserved by the active supply diffuser.
However, the throw length towards window side (right side) was different due to
interaction between cold current from the window and the supply jet.
(a) |
(b) |
Figure 4. (a) Temperature stratification and
(b) air velocity distribution for two scenarios in a plane passing through the window |
Figure 5 illustrates the variation of
thermal comfort indices for both scenarios. Using active supply diffuser could
almost satisfy PMV requirement for both scenarios (Figure 5a)
according to comfort category II [10].
The spatial distribution of PPD for both scenarios at three cross sections are
shown in Figure 5b. The thermal comfort for both cases
were always satisfied at the standard seated head level in the occupancy zone
(1.1 m above the floor) with PPD ≤ 7% implying the decent
performance of active supply diffuser in providing uniform distribution of
supply air in the occupancy zone. However, some small region above that level
located in the convective plume of occupant had higher PPD.
(a) | ||
Y = 1.4 m | Y = 1.0 m | Y = 0.6 m |
(b) | ||
Figure 5. (a) Average
PMV in the zone of occupancy and (b) PPD distribution in three cross sections
|
This study
dealt with numerical simulation of IAQ in a standard cell office equipped with
active supply diffuse and located in a Nordic climate country. Two different
scenarios for maximum allowable and required minimum air flow rates were
analyzed and the results showed that applying active diffuser at ceiling level
could avoid temperature stratification, with maximum temperature stratification
around 1.5 K, even at minimum air flow rates by changing the slot opening
of diffuser. The thermal comfort analysis showed that both scenarios almost
satisfied the average PMV requirements according to the comfort category II.
Furthermore, spatial PPD values at the seated head level was less than 7%
satisfying the requirements for the comfort category II. It is worth mentioning
that the cooling performance of active supply diffuser would be interesting to
be evaluated as the all-air system should also cover the building cooling load.
[1] W.J. Fisk, D. Faulkner, D. Sullivan, F.
Bauman, Air change effectiveness and pollutant removal efficiency during
adverse mixing conditions, 7(1) (1997) 55-63.
[2] F.J. Offermann, D.
Int-Hout, Ventilation effectiveness measurements of
three supply/return air configurations, Environment International 15(1) (1989)
585-592.
[3] A. Novoselac, J. Srebric, Comparison of air exchange efficiency and
contaminant removal effectiveness as IAQ indices, 109(2) (2003) 339-349.
[4] S. Liu, A. Novoselac,
Air Diffusion Performance Index (ADPI) of diffusers for heating mode, Building
and Environment 87 (2015) 215-223.
[5] M. Krajčík,
A. Simone, B.W. Olesen, Air distribution and ventilation effectiveness in an
occupied room heated by warm air, Energy and Buildings 55 (2012) 94-101.
[6] D. Risberg, M. Vesterlund, L. Westerlund, J.
Dahl, CFD simulation and evaluation of different heating systems installed in
low energy building located in sub-arctic climate, Building and Environment 89
(2015) 160-169.
[7] NS-3701-Criteria for passive houses and low
energy buildings, Non-residential buildings, Standard Norge, Norway, 2012.
[8] TTC- Active supply diffuser. Avaiable from: https://www.lindinvent.com/products/air-diffusers/ttc/,
2018. (Accessed 4 May 2018).
[9] A. Cablé, M. Mysen, K. Thunshelle, Can
demand controlled ventilation replace space heating in office buildings with
low heating demand?, Indoor Air conference, Hong Kong, 2014.
[10] EN ISO 7730- Ergonomics of the
thermal environment - Analytical determination and interpretation of thermal
comfort using calculation of the PMV and PPD indices and local thermal comfort
criteria, Standard Norge, Norway, 2006.
[11] A. Cablé, M. Mysen, K. Thunshelle, Can demand
controlled ventilation replace space heating in office buildings with low
heating demand?, Indoor Air conference, 2014.
[12] ANSI/ASHRAE/IES. Standard 90.1e2007 normative Appendix B: building envelope climate criteria, (2007).
Follow us on social media accounts to stay up to date with REHVA actualities
0