Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
|
Dejana SoldoM.Sc.M.E.SokoInzinjering,Serbia, www.sokoing.rsdejana.soldo@sokoing.rs |
A laboratory for
testing of samples for coronavirus called “Fiere Eye” was opened at the
Clinical Centre of Serbia in Belgrade on April 20 this year. The central
air-conditioning system of the laboratory with extremely strict hygienic and
internal parameters of temperature and relative humidity was constructed. Air
handling unit that provides the said parameters is a product of the company
“Soko Inžinjering” under the designation “K7-4 HG” made in accordance with the
standards and recommendations that the systems for this purpose must meet. All
tests of authorized validation laboratory confirmed the required parameters.
The new
laboratory for testing samples for the "Fiery Eye" coronavirus is a
donation from the Chinese BGI Institute. It was modeled on the best laboratory
in the city of Wuhan, with which China managed to defeat this pandemic. The
very name of the laboratory comes from the Chinese myth in which the
"fiery eye" can see every spirit and devil.
The capacity of
the laboratory is 2,000 samples per day, which is equal to the capacity of all
other laboratories in Serbia where coronavirus samples are currently being
tested. This lab significantly accelerated the testing of samples for Covid-19,
and thus helped suppression the spread of this global pandemic. It employs 40
health workers, molecular biologists, in three shifts, seven days a week.
The second
laboratory is in the city of Nis and has a capacity of 1,000 tests per day.
The laboratory is
located within the Clinical Center of Serbia Figure 1. The facility is
designed as a separate unit and has 750 m², of which clean rooms of class
ISO8 occupy an area of 300 m², with 12 separate rooms.

Clinical Center
of Serbia in Belgrade.
The company Soko
Inžinjering has been present on the market since 1992, and it deals with the
production of air-conditioning, heating and cooling equipment, as well as the
execution of all mechanical and BMS installations.
At the time of
state of emergency, when the virus pandemic reaches its peak worldwide, when
everyone is facing unknown, in the phase of elaborating a technical solution
due to unconfirmed technology, the task was set to produce air handling unit,
air ducts, to install complete equipment in the facility and to put the entire
air-conditioning and ventilation system into operation. A specific challenge
was to procure appropriate elements, organize production, install in the
facility and successfully put into operation, in aggravating circumstances and
a short period of 15 days, in order to meet all set requirements.
Faced with the
challenge, they were given security by numerous references from the field of
medical institutions and hospitals, their own production, as well as the fact
that they have been holding Eurovent Certificate for air handling units for 7 years
and are successfully passing all tests in terms of quality (strength, sealing,
thermodynamic performances, ...).
·
The
laboratory air-conditioning system is a separate system with respect to other
air-conditioning systems of the Clinical Centre.
·
Hygienic
construction in accordance with the standards and recommendations for this
purpose systems.
·
Application
of ventilation with fresh air dilution and laminar flow at low speed, without
the possibility of air recirculation.
·
The
adopted amount of air corresponds to a larger number of air changes, in order
to prevent the deposition of particles.
·
Use
of high efficiency filters, ePM1, intended to stop particles up to 1 micron
in size. Filtration efficiency of 50% in the first stage, then of 80% in the
second stage and with absolute filters at the end, having an efficiency of
99.97% for particles with a size of 0.3 microns.
·
Adequate
distance is provided between exhaust air discharge point and fresh air intake
with mandatory filtration of exhaust air, so as to prevent fresh air
contamination.
·
Controlled
ventilation system preventing the penetration of the air from contaminated part
to other areas, in terms of appropriate underpressure/overpressure and
prevention of exfiltration / infiltration of particles.
·
Achieving
appropriate temperature and relative humidity parameters.
The two stage air
handling unit was chosen, operating with 100% fresh air of 18,000 m³/h.
On Figure 1is given Mollier’s
Diagram showing the changes in air conditions for external design parameters in
winter and summer period and Figure 2 shows air handling unit configuration.

Figure 1.
Mollier diagram (h,x chart).

Figure 2. Air
handling unit configuration.
Heating capacity
of 200 kW with hot water regime of 80/60°C from the district heating
system was adopted. Cooling capacity is 175 kW with cold water regime 7/12°C
from the existing chiller plant.
For the second
laboratory, which was opened three months later in Nis, refrigerant R410A was
used as a cooling medium, and independent cooling system with Hitachi
"Utopia DX" condensing units.
It is planned to
maintain relative humidity within the limits from 40% to 60%, because this
range is least suitable for microorganisms. Class F7 and F9 fine filters were
installed on delivery side. Absolute H13 filters were installed, both on
delivery, and exhaust side of the air handling unit. Fans with variable rpm
speed were used, in order to achieve appropriate pressure difference.
Air distribution
ducts play an important role in air-conditioning and ventilation system, because
they significantly affect the air quality and energy efficiency of the entire
system.
Special attention
was paid to very process of fabrication and proper installation of the ducts,
whereby uniform air distribution, the highest class of sealing (air-tightness),
hygienic adequacy and easy maintenance. Figure 3 shows Air handling unit in the facility
in installation phase.
Figure 4 shows Laboratory in equipment
installation phase in city Belgrade and Figure 5 in city Niš.

Figure 3.
Air handling unit in the facility in installation phase.

Figure 4.
Laboratory in Belgrade in equipment installation phase.

Figure 5.
Laboratory in Nis in equipment installation phase.
·
EN
1886 – Ventilation of buildings, Air handling units, Mechanical performance
·
EN
13053 – Ventilation of buildings, Air handling units, Rating and performance
for units, components and sections
·
DIN
1946-4 – Ventilation and air handling units in health care areas
·
VDI
6022 – Hygienic requirements for ventilation and Air Handling Unit systems,
special
·
requirements
for systems used in people's occupations (air quality)
·
REHVA
Guidebook No.9: Hygiene Requirement for Ventilation and Air Conditioning
provides guidance on hygiene requirements for planning, installation,
maintenance and operation and describes appropriate test procedures and test
criteria for ventilation and air-conditioning systems and airhandling units.
·
REHVA
COVID-19 guidance document www.rehva.eu/activities/covid-19-guidance
·
ASHRAE
Position Document on Infectious Aerosols
Nowadays, the
world is facing an increasing threat from viruses and bacteria and no less
threat from shortage of energy-generating products. Implementation of all
safety measures on the one hand and preservation of remaining energy potentials
and the finding of possible savings on the other hand are of exceptional
importance. Finding the right balance will be a challenge for heating, cooling
and air-conditioning profession in the forthcoming period.
Follow us on social media accounts to stay up to date with REHVA actualities
0