Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities

The
building has a gross area of 182,000 sf, and contains a basement with 4
levels above grade. The spaces are distributed in the following manor:
·
Server
room, classrooms, a parking garage and mechanical and electrical rooms in the
basement,
·
The
1st and 2nd
floors contain a mix of classroom studios as well as office and support
facilities;
·
The
3rd and 4th floor
contains the main administrative offices, faculty offices and ancillary support
spaces.
Early on,
it was decided that occupant comfort and energy conservation would be a
priority. The goal was to provide comfort levels at 10% PPD (Percentage of
Person Dissatisfied) or less for each space and at the same time consume the
least amount of energy against both California’s Title 24 requirements and
ASHRAE 90.1‑2007 for LEED points.

The place
to start in creating comfortable spaces is with the architectural design and
not the conditioning systems. IBE spent considerable time working with the
architects, analysing different glazing alternatives and investigating the
inside surface temperature for the glass as this drives the mean radiant
temperature (MRT) in the occupied spaces. A dynamic comfort simulator was used
that could analyse space conditions for a single day, month or year. Having a
better understanding of the building shade characteristics and thermal
conditions, the overall thermal comfort was improved in addition to reducing
energy consumption by implementing some or all of the investigated strategies.
Claremont
McKenna College is located in Claremont, California at 34.1 degrees
Latitude. Using a software program, a sun path diagram was created to show the
total solar radiation on south and west facing surfaces of a 90‑degree
structure. The sun path diagram reveals the maximum solar radiation potential
for September and July are 450 W/m² (144 Btu/h ft²). and 530 W/m²
(168 Btu/h ft²) respectively. The design peak days
selected for the analysis were July 30th for the western facing
windows and September 24th for the southern facing windows.
On the
fourth floor of the southern façade of the college there are 0.45 m (1.5 ft.)
long fins protruding from both sides of the windows. There is also a 0.45 m
overhang above the windows.
The
material characteristics of the fins are very important. The material should
have a high reflective factor to reflect solar radiation from being absorbed
into the shade. In Claremont California the peak solar intensity is 530 W/m²
(168 Btu/h ft²). By allowing only minimal radiation to hit the
windows, the solar gain to the space is reduced significantly. At the same
time, the solar radiation penetrating the fins must be utilized to enhance the
natural day lighting of the spaces.
The inside
surface of the fins must also be carefully selected., If the surface has a
higher reflectance than any radiation reflected from the glass, after being
allowed to hit the glass, could be reflected back into the building from the
shade. If the inside surface of the fins is not reflective, the solar radiation
reflected from the glass will be absorbed by the fins.
The glazed
surfaces of the college were carefully selected as the glass had to perform to
reduce solar loads, yet permit natural day light to enter the spaces. During
the winter the glazing must have a low U value to reduce heat losses. A low U
value is most often obtained by having a coating on either the second or third
surface of the double glazed construction. The ideal glazing is one with a
balance between a high visible light transmittance and low shading coefficient.
This is often a difficult compromise to maintain a clear appearance yet achieve
the required shading performance.
The glazing
type used in the analysis for the College was an insulating glass with a low
shading coefficient of 0.32 and high visible transmittance of 62%, a winter night-time
U value of 1.65 W/m² K and a summer U value of 1,42 W/m² K.

The choice
of an appropriate conditioning system was based upon the required comfort
compliance requirements. But the different characteristics of classrooms and
offices would lead to two different conditioning systems.
Based upon
previous design for academic buildings such as Cooper Union, we had some
excellent operational feedback that would help us select a system for CMC. Each
classroom was designed for 30 students, with and without computers. Experience
in designing academic buildings over the years requires a flexible solution, taking
into consideration the amount of students attending classes and at what time of
day will the classes be held. The basis of the design is a variable volume
ventilation air supply; we chose to provide 20 CFM of outside air for each
person present. By providing 34 m3/h the ventilation rate
qualifies for the LEED point for extra ventilation. The cooling provided by
supplying 34m3/h per student and with a maximum of 30 students in
the room is nearly sufficient to maintain a space temperature of 23,5°C. But we
were looking for comfort compliance so a radiant ceiling was introduced mainly
for heating during the brief and relatively mild winters in California. The
choice of a radiant ceiling was based upon the system being able to control
radiant temperatures in the space, especially for the first lesson of the day
and with only a minimum of students present. The radiant ceiling would provide
heat to the space and control space radiant temperatures and the ventilation
air would be supplied in amounts determined by individual space CO2‑sensors. Another spin off from this methodology is the reduction
in fan power for the ASHRAE 90.1 energy performance. Once the choice for a
radiant ceiling was made, investigations then took place to look at the
utilization of cooling from the radiant ceiling. It was basically the same
scenario as heating, if the class was partially occupied the ventilation air
would be reduced and the cooling and radiant temperature control would be
performed by the radiant ceiling.

Figure 1. Percentage of people dissatisfied for
different air conditioning methods for the classroom.
The results
show that comfort conditions comply with ASHRAE standard 55 when a radiant
ceiling is introduced as part of the conditioning system for the classrooms.

Figure 2. Controls for the classrooms and meeting
rooms at CMC.

Figure 3. One of the meeting rooms at CMC which is
conditioned in the same manner as the classrooms.
We decided
to use active beams to condition the offices and administrative spaces at CMC.
The choice was based upon our quest for occupant comfort and individual control
in each space. Constant volume primary air is supplied to each beam; the
sensible cooling from the primary supply air is only about 15–20% of the space
sensible cooling load. The larger portion of the cooling load is provided by
the control of cooled water flowing through the beam. By putting the control
emphasis on the water side control of the system, the response time is improved
and this increases the efficiency of the system.

Figure 4. Typical office space with floor to ceiling
glass.

Figure 5. A plan view of the active beams and primary
air connections for each space. The temperature, humidity and CO2 sensors are also shown for each space.

Figure 6. Control systems for offices conditioned by active
beams.

Figure 7. Percentage of people dissatisfied for two
different glass types for the corner office.
A central
cooling and heating plant was provided to serve this building. The central
plant is located at the basement level to the north of the building.
The chiller
plant consists of two 560 kW frictionless chillers. Each chiller has a
variable speed primary pump. The chillers also have the capability of having
their speed varied to improve efficiency. Condenser water for the chillers is
cooled by a single cooling tower having variable speed fans. The condenser
water loop is constant volume.
There are
two variable volume chilled water loops:
1. There is a 5.5°C loop that transports water
to the air handling units, CRAC units and fan coils in the IDF rooms.
2. The second loop has a variable supply
temperature from 12.8°C to 14.4°C for the active beams and the radiant ceiling
panels.
Two boilers
each with a 580 kW capacity provide water at a constant volume to a common
header.
There are
two variable volume heating hot water loops:
1. There is an 80°C loop that transports water
to the air handling units.
2. The second loop has a variable supply
temperature for the active beams and the radiant ceiling panels.
An energy
model was constructed to explore the building’s performance against the
California Energy Code (Title 24). This code provides a measuring stick based
upon the size and use of a building.
The
Reference Baseline building shell is comprised of metal frame wall with R‑13
batt insulation, insulated glazing with a T‑24 maximum shading
coefficient and roofing with a R‑19 insulation.
Lighting
systems were specified to meet Title 24 allowances of 15,5 W/m².
The
Reference Baseline mechanical system was an overhead VAV system and a central
heating and cooling plant as allowed by Title 24 standards.

Figure 8. Annual TDV Energy Use Summary (kBtu/sqft.yr)
compare with kWh/m² per year.
Figure 8 shows the EnergyPro output for the
energy analysis. The reference Standard Design is a building of the same size
and usage built in accordance with the prescriptive requirements of Title 24.
By taking the performance approach, we do not need to follow the prescriptive
requirements as long as our proposed building out performs the standard
building.
Based on
the preliminary model, the proposed building is performing 32.3% better than
the standard model, although the value of 37.9% better than Title 24 is used
for Savings by Design as this excludes process loads.
The
building includes the following features to increase the performance of the
building to exceed Title 24 minimum standards by 37.9 percent:
·
High
performance lighting systems in classrooms, seminar rooms, meeting room and
offices, with occupancy sensors and daylight harvesting sensors.
·
High
performance glazing
·
High
efficiency frictionless chillers
·
Wall
insulation increased to R‑19 and roof insulation increased to R‑30.
·
Daylight
harvesting sensors.
For the
LEED submittal the percentage of Energy savings was 63.5% and the cost savings
were 46.7%, which was good for 10 LEED points.
Follow us on social media accounts to stay up to date with REHVA actualities
0