Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
|
| |
Dirk Van OrshovenMSc Mechanical Engineering,Project leader EN ISO 52003 and EN ISO 52018,DVO, Belgiumdirk.van.orshoven@skynet.be | Dick van DijkMSc Applied PhysicsEPB-research –The NetherlandsEPB-research@dickvandijk.nl |
These 2 EN ISO
standards (i.e. parts 1) [1][2] and their accompanying technical
reports (i.e. parts 2) [3][4] are of an unusual nature in the set
of EPB documents. As a rule, the EPB assessment documents concern inspections/measurements
or calculations. The documents at hand concern neither of these aspects, but
deal with the productive use of the output (EPB indicators) of the assessment
standards for setting requirements, for rating, or for other possible
applications. This can be called the "post processing" of the results
of the EPB assessment.
The documents
EN ISO 52003-1 & -2 deal with the general principles and their application
to the overall energy performance. Documents EN ISO 52018-1 & -2 concern their
application to various fabric features and to the thermal energy balances for
heating, cooling or free floating temperatures (overheating and/or
undercooling).
By
describing explicitly different aspects related to the development of EPB
regulations, all parties involved can gain a better and explicit understanding
of the issues at hand, thus facilitating the policy making process. In the case
of public regulations, the parties include not only the regulators themselves,
but also all stakeholders involved in the policy development, notably diverse
organizations representing citizens, designers, supply industry, construction
companies, craftsmen, etc.
Successively,
the following concepts are defined and discussed in the standard and its
associated technical report (both replacing EN 15217 and ISO 16343):
·
EPB
features
·
Numerical
EPB indicators
·
Tailoring
for requirements and for ratings
·
EPB
requirements
·
EPB
rating
·
EPB
certificate
Several of
these aspects are described in more detail in a previous REHVA article [5] and are not repeated here.
These
documents are new. They list and discuss a variety of possible partial EPB features
and indicators for requirements related to the thermal energy balances and to the
fabric, notably summer and winter (free floating) thermal comfort, energy needs
for heating and cooling, overall envelope thermal insulation, individual
element thermal insulation, thermal bridges, window energy performances,
envelope air tightness and solar control.
In the
standard itself (i.e. in part 1) [2] a very brief possible motivation
for each possible requirement is given and different possible EPB indicators
are described that can be used for each feature. Annex A provides tables that
allow regulators to report in a standardized manner the mix of EPB features and
corresponding EPB indicators that have been chosen for the requirements in
their jurisdiction. Annex B proposes motivated default requirement mixes for
different climates.
The
technical report (i.e. part 2) [4] formulates for each EPB feature background
considerations with respect to the following aspects (in as far as applicable):
a more detailed discussion of possible motivations, possible indicators, comparable
economic strictness of the requirements, practical points of attention, testing,
new construction and renovation issues, exceptions and other possible aspects.
Part 2 also
illustrates in its annex A a practical manner in
which fictitious cooling can be integrated in the overall energy performance by
means of a conventional probability weighting factor. In this way, an energy
efficient overall design can be stimulated that strikes a good balance between
summer and winter thermal comfort.
As
explained in EN ISO 52003 ([1], [3] and [5]), for some EPB features/indicators the
numeric value that corresponds to the technical and economic optimum often
varies strongly from 1 construction project to another, depending on function,
size, shape, etc. In order to treat all buildings in the same manner (e.g.
reflecting the same technical and economic strictness), it is for these
indicators thus of crucial importance to use variable value requirements or
references that take into account all relevant project-specific features of
each individual building. This is called tailoring.
Figure 1 illustrates on the basis of some
200 real dwelling shapes (each individual cross) how for a given set of
technical measures (level of overall thermal insulation, degree of airtightness,
energy efficiency of the ventilation system, etc.) the numeric value of the specific heating need (i.e. the heating need per useful floor area) can strongly
vary from one project to another. The x-axis is the ratio of the envelope area to
the useful floor area. This numeric variability of equal technical-economic
strictness obviously explains, in combination with other potentially variable
factors, the similar variability of the overall energy performance; see Figure 4 in [5].
If the
reference value that is used to set a requirement is a fixed value (in casu: requirement expressed as a constant maximum value in
kWh/m² disregarding building shape or size: e.g. red horizontal line), then
buildings with a relatively large envelope area[1] (compared
to the floor area) would need a large technological-economic effort to meet the
requirement, while on the other hand buildings with a relatively small envelope
area would need only a small technological- economic effort to meet the same
requirement. Such mismatch would correspond to a suboptimal use of investments
both on a societal and on a private level. A more equitable reference for the
requirement takes into account this variation and determines project-specific,
tailored quantitative requirements.
A more
detailed discussion of the graph and further analysis and illustrations of the
issue for the specific heating need can be found in annex B of EN ISO 52018-2 [4].

Figure 1. Example of the impact
of a fixed (constant value) requirement versus a more appropriate variable
value (tailored).
A similar
issue arises with a requirement on the mean thermal transmittance of the
thermal envelope. It is commonly accepted that the adequate amount of glazing
needs to increase with the useful floor area: the broader the building is the
more glass is needed for sufficient daylight access and visual outdoor contact.
As in practice, the thermal transmittance of transparent elements (windows, etc.)
is (due to physical-technical and economic reasons) typically much higher than
that of opaque envelope elements, an increasing share of transparent area in
the envelope (which reasonably, is thus approximately proportional to the
useful floor area) leads to a requirement that increases linearly with the
floor to envelope ratio (i.e. the inverse of the shape factor), as illustrated
in Figure 2. The minimum value of the straight line (for
an x-value of 0) corresponds to the (average) thermal transmittance requirement
for the opaque elements. The slope of the line depends on the features of the
transparent elements: the reasonable fraction as a function of the useful floor
area, and their thermal transmittance requirement.
There are
however logical limits to the maximal mean thermal transmittance. It should
never be larger than value of transparent elements, and in addition, not the
entire envelope needs to be glazed: floors are usually opaque, roofs are opaque
or only need to be partially transparent, and parts of the facades below the
working plane, which do not meaningfully contribute to daylighting anymore,
generally do not need transparent elements. In general, the maximum limited is
therefore restricted to a constant value above a certain Ause/Aenv value. This is illustrated with the
dashed line in Figure 2.

Figure 2. Motivated example of
a curve for the maximum mean thermal transmittance as a function of the inverse
of the shape factor.
Documents
EN ISO 52003-1 & -2 and EN ISO 52018-1 & -2 document in a critical
manner useful knowledge, distilled from decades-long experiences, that supports
politicians/regulators and stakeholders in taking well-informed decisions,
optimally tailored to their own jurisdiction. In this manner a well-considered
EPB regulation can be developed that matches the sophistication of the EPBassessment
methods.
[1]
EN ISO 52003-1, Energy performance of buildings – Indicators,
requirements, ratings and certification – Part 1: General aspects and
application to the overall energy performance
[3]
CEN ISO/TR 52003-2, Energy performance of buildings – Indicators,
requirements, ratings and certification – Part 2: Explanation and justification
of ISO 52003-1
Follow us on social media accounts to stay up to date with REHVA actualities
0