The ambition in sustainable development of the built environment is to reduce the harmful impact of the nature of materials and building energy use [1]. Often the building energy use and the minimization of its CO2 eq emissions are considered to be the desired goal. However, as the energy use decreases the importance of CO2 eq emissions originating from building materials and products increases. Thus, what kind of materials and building products are used becomes more important [3]. In addition, the minimization of CO2 eq emissions is perhaps not the only desired target, but we need to consider also the minimization of primary energy use, since it highlights rather well the use of natural resources.
The aim of the study is to
1)Find out the different available options in the design phase in order to minimize the energy consumption;
2)Consider how the CO2 eq emissions from the embodied energy from building materials and CO2 eq emissions from energy use in the building should be treated;
3)Consider how we should weight the primary energy use and the CO2 eq emissions of different design options. In this study is a real office building was studied.
The studied building is an office building located in Helsinki developed by Skanska Commercial Development Finland. The building was under design phase and the aim was to study different alternatives in order to choose the most energy and environmental efficient way to erect the building. The gross floor area of the nine storey building is 26 000 m². The geometry of the building is quadratic. The studied properties are shown in Table 1.
The buildings were modelled in a dynamic IDA simulation environment [2]. The building model was the architect’s real 3D model but the building spaces were simplified to 43 different zone models each representing typical uses of the space type, such as office rooms, meeting rooms, cafeteria, etc.
Table 1. Studied design alternatives. The control systems include ventilation and lightning.
Feature | Case 1 | Case 2 | Case 3 | Case 4 | Case 5 | Case 6 |
Building envelope excl. windows | Building Code 2010 | Building Code 2010 | Building Code 2010 | Building Code 2010 | Building Code 2010 | Passive house |
Windows (W/m²K) | 1.0 | 1.0 | 1.0 | 1.0 | 0.7 | 0.7 |
Ventilation heat recovery | 70% | 70% | 80% | 80% | 90% | 90% |
LED lighting | in garage | in garage | in garage | in garage | in all spaces | in all spaces |
Systems control level | building | room | room | building | room | room |
In the 2010 Building Code the U-values for external walls is 0.17 W/m²K, base floors 0.16 W/m²K, roofs 0.09 W/m²K and doors 1.0 W/m²K. The ventilation heat recovery requirement in the 2010 Building Code is 45%, which was not used in calculations, since that was not an option in the design phase. In the so called passive house level the U-values for external walls is 0.08 W/m²K, base floors 0.15 W/m²K, roofs 0.08 W/m²K and doors 0.7 W/m²K.
The embodied CO2 includes energy consumption of building materials and products, the use of raw materials and greenhouse gases. The most important greenhouse gases are fossil fuel derived CO2, CH4 and N2O. In the calculations the greenhouse gases are transformed to CO2 eq by using IPCC’s characteristic factors.
Energy Sources and their CO2 Equivalent Emissions and Primary Energy
The studied alternatives for energy and their CO2 emissions are shown in Table 2.
Table 2. Primary energy factors and CO2 equivalent emissions used.
Primary Energy Factor | CO2 equivalent * | |
District heating average | 1.87 | 0.22 |
District heating bio | 0.4 | 0.12 |
Electricity average | 1.87 | 0.38 |
Electricity from district heating average | 1.87 | 0.38 |
Peak electricity from nuclear power | 2.8 | 0 |
Peak electricity from coal | 2.0 | 0.928 |
District cooling | 0.25 | 0.12 |
Green electricity | 0.2 | 0 |
* Unit: kg CO2/kWh.
The service life for building was assumed to be 50 years. The embodied CO2 emissions from building materials and process were estimated according to design drawings.
The energy consumption was highest in the case 1 and lowest in the case 6. But the energy consumption in case 4 was also really high, being nearly the same as in the case 1 and showing that the building level control is inefficient with respect to energy saving. In particular the heating energy consumption is the highest when the control is at the building level. The energy consumption was 20% lower in case 6 compared to case 1. The only difference between cases 3 and 4 was the temperature control. In case 3 the control was at the room level, while in the case 4 the control was at the building level. That resulted in a 7% difference in total energy consumption and a 20% difference in space heating, in addition the difference in cooling was also 20% between those two cases (Figure 1). Since in office buildings the electricity use has higher importance than heating, case 6 does not have that much difference in consumption, even though the insulation values are much better (equal to passive house). The major difference between cases 3 and 5 was the LED lightning, in case 5 all lightning was done by LEDs, which clearly resulted in a lower energy consumption.

Figure 1 Yearly energy consumption in different cases. Electricity AC represents for electricity for air conditioning systems.
The Finnish Building code is very advanced with respect to reducing heat losses from buildings; e.g., the U-values and ventilation heat recovery, as well as air tightness of the building envelope, are required to be rather good. This can be clearly seen from the energy consumptions (Figure 1). The CO2 equivalent emissions of heating are also rather low due to the low energy consumption when average Finnish district heating, cooling and electricity are used as energy sources (Figure 2). In Figure 2 heating includes both space heating and domestic hot water.
Due to the low heating energy consumption the embodied CO2 emissions and electricity are dominant components in the CO2 emissions. That is actually rather surprising, since case 1 is the typical building code level in new office buildings, and only ventilation heat recovery is clearly better than the average in new buildings. In this study the embodied CO2 includes energy consumption of building materials and products, and the use of raw materials and greenhouse gases.
Evidently, if all the electricity used is generated from renewable energy sources and for district heating and cooling bio-fuels are used, the embodied CO2 emissions have the highest share and the over all CO2 equivalent emissions decrease dramatically (Figure 3). However, the problem with renewable electricity is that the power plants produce renewable energy on a yearly basis. Thus, sometimes the electricity might originate from fossil fuels for a short period of a time if not enough electricity from renewable sources is available. The electricity produced by fossil fuels is substituted by renewable energy on a yearly basis to get the balance. Usually this means excess energy, e.g., from wind power.

Figure 2 The share of each energy consumption and embodied CO2 in different cases when average district heating, cooling and electricity are used. The heating includes both space heating and domestic hot water heating.

Figure 3 The share of each energy consumption and embodied CO2 equivalent in different cases when district heating, cooling from bio-fuels is used and electricity is from renewable energy sources.
Figure 4 shows the primary energy consumption as a function of the relation between embodied and energy-derived CO2 eq emissions. The CO2 eq embodied corresponds to the CO2 eq emissions from materials during their lifetime and CO2 eq energy corresponds the CO2 eq emissions from energy use in the building (heating, cooling and electricity). When all different options for heating, cooling and electricity sources were compared it can be clearly seen that the nuclear-based energy alternatives all ended up with rather high primary energy consumption and since the building energy use is carbon neutral, the embodied CO2 emissions become dominant (Figure 4).
If low primary energy is the target, then bio-based district heating systems seems to be effective as well as the use of electricity from renewable energy sources. Ground heat or the average local heating performed rather similarly in respect to primary energy use. This is because the ground heating systems use electricity but they can utilize the “free” thermal energy obtained from the ground. It can be seen that the local variations do have an effect on both primary energy use and CO2 eq emission; in some parts the average Finnish values do have a good correlation to local energy production, but in some places the local production is closer to biomass-based production and in other locations closer to peak conditions. The lowest primary energy use is in alternatives based on bio local heating, cooling and green electricity. The lowest relation between CO2 eq embodied and CO2 eq energy in addition to low primary energy use was with the cases based on bio local heating, cooling and average electricity. When average electricity or nuclear energy based electricity was used, there was a clear trend in that energy saving gave the highest primary energy use savings.

Figure 4 Primary energy consumption as a function of the relation between embodied and energy derivated CO2 equivalent emissions.
The reduction of energy use reduces both the primary energy use and CO2 emissions. The reduction of electricity use has a high importance for both primary energy use and CO2 emissions when fossil fuels are used. Often energy originated from fossil fuels is also used as a complimentary source of energy, thus the importance of reducing energy use and especially electricity originated from fossil sources has a high priority.
The lowest CO2 eq equivalent emissions were achieved when bio-based, renewable energies or nuclear power was used to supply energy for the office building. Evidently then the share of CO2 eq emissions from embodied energy from building materials and products became the dominant source for CO2. The lowest primary energy was achieved when bio-based local heating or renewable energies were used in addition to local cooling. Obviously the highest primary energy was when nuclear power was used. When the primary energy use and CO2 eq are minimized the CO2 eq originated from materials become rather dominant. In this study the CO2 eq emissions originated from building materials and products is between 2.4 to 3.1 higher compared to CO2 eq emissions originated from building energy use during running time.
[1] Citherlet, S.; Clarke, J.A.; Hand, J. Integration in building physics simulation. Energy Build. 2001, 33, 451–461.
[2] IDA Simulation Environment. Available online: www.equa.se
[3] Jonsson, A. Tools and methods for environmental assessment of building products—methodological analysis of six selected approaches. Build. Environ. 2000, 35, 223–238.
[4] Airaksinen M., Matilainen P., 2011, A Carbon Footprint of an Office Building Energies, Energies, 4(8), 1197-1210