Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
|
|
Xavier Kuborn | Sébastien Pecceu |
Belgium Building Research Institute, Belgium | Belgium Building Research Institute, Belgium |
Combustion appliances are used in many buildings to provide space heating and domestic hot water. These appliances emit smoke that mostly contains carbon dioxide and water vapour, but also, depending on the type of fuel and the quality of the combustion, unburned hydrocarbons such as carbon monoxide, soot, tars and particulate matter. These products must be kept away from the ventilation air supply openings to limit their impact on the indoor air quality (IAQ).
An efficient way to prevent the flue gas from entering the building is to place the exhaust terminal above the top of the roof (see Figure 1), as far as possible from the ventilation air supply openings. The wind velocity, combined with the buoyancy of the smoke, will move the plume away from the building and dilute it into the atmosphere.
|
|
Figure 1. Streamlines of the wind flow around a building from
a CFD simulation, with a superimposed qualitative representation of the smoke
plume. | |
To reduce the installation costs of modern appliances, the chimney is often as short as possible and the exhaust terminal is mounted on a vertical wall, right next to the appliance. In that case, the plume might be partially trapped in a recirculation zone and remains close to the building with less dilution, increasing the risk of contamination. A minimal distance between the exhaust terminal and the ventilation air supply openings must be determined in order to avoid the recirculation of the pollutants inside the building.
Specific methods can be found in European and Belgian standards. A comparative example is given in Table 1. It highlights the discrepancies between the existing methods and the need for a tool to select the most appropriate one, or to develop a more widely accepted one.
Table 1. Discrepancies between the different
standard methods.
Geometrical configuration | Standard reference | Recommended distance |
| NBN EN
15287-2(2008) NBN B
61-002(2006) NBN D
51-003(2014) | Δh = 30 cm Δh = 320 cm Δh = 500 cm |
| NBN EN
15287-2(2008) NBN B
61-002(2006) NBN D
51-003(2014) | ΔL = 30 cm ΔL = 340 cm ΔL = 100 cm |
The minimal distance between the horizontal mounted flue gas exhaust system and the ventilation air supply openings depends on many parameters, including the heating power of the appliance, the temperature of the flue gas, the pressure of the exhaust and many others. But the most important parameter is the wind flow pattern around the building, that depends on the shape of the building and on the direction of the wind. Depending on the flow pattern and on the position of the exhaust terminal, the flue gas plume can be driven away from the building by the wind, or be taken back against it.
A relevant method to study the wind flow pattern and the flue gas dispersion around buildings is to perform computational fluid dynamics (CFD) simulations.
The complex physics of the problem is
described by a set of equations (the Navier-Stokes
equations) that are solved by a CFD tool. The concentration field of the
pollutants around the building is determined from the solution of the
equations. For industrial
(non-academic) research, an alternate version of the Navier-Stokes
equations (RANS equations : Reynolds-Averaged Navier-Stokes
equations) and a turbulence model (k – ω SST) are used, as it has been proven
appropriate in other studies dealing with flow around buildings
| |
|
|
Figure 2. The numerical domain (above) and
examples of geometries (below) derived from a four facades
building.
To visualize the computed pollutant field near the facades of building, an iso-contour at a dilution of 100 is shown in Figure 3. This specific iso-contour represents the locations in space where the concentration of the pollutant is 100 times lower than that at the exhaust terminal. A dilution of 100, for gas-fired appliances, is considered to be representative of a sufficient air quality to be used for building ventilation
Figure 3 also shows that the smoke plume
goes backward against the wind and along the façade as the exhaust terminal is
located in a recirculation zone. The iso-contour representing a dilution of 100
is not connected to the exhaust terminal, as either the initial velocity of the
flue-gas or the wind pattern initially moves it away from the building before
pulling it back against the façade.
The result
presented in Figure 3 is an instant picture of a specific
set of operating parameters, but it does not reflect the risk encountered in
real life, as the many parameters are dependent on the environmental
conditions, including the wind velocity, the wind direction and the outside
temperature, that are variable in essence. If a yearly overall effect is to be
accounted for, a statistical approach using all the relevant environmental
parameters needs to be used. However, this approach implies that many different
numerical simulations need to be done in order to get all the relevant results.
Fortunately, many similarities can be identified, and the results of several
numerical simulations can be used to complement other similar cases, using an
appropriate scaling. For instance, the flow pattern around the building remains
the same for any wind velocities above 2 m/s, which reduces the need to perform
new numerical simulations for different wind velocities. However, the wind
velocity is accounted for in the scaling as it increases the dilution of the
smoke plume.
|
Figure 3. Representation of the iso-contours
of concentration of the flue gas around a detached house.
Assuming
that the heating appliance is operating at nominal power, only height numerical
simulations (one per main wind direction) are needed to determine the impact of
the smoke on the façades of buildings. Knowing the wind velocity and wind
direction for each hour of the year, these height numerical simulations and the
scaling procedure are used to compute the pollutant field for each hour, which
in turn is used to compute the probability that a concentration threshold is
reached or exceeded on the façades of the building. Such probability is shown
in Figure 4 for a dilution of 100 (left-hand
side of the figure) and 1000 (right-hand side of the figure).
|
|
Figure 4. Probability that the dilution of a
pollutant is below a threshold of 100 or 1000 on a yearly basis.
The next
steps of this project are to further validate the method and to develop a tool,
based on these numerical results, that could be used by the heating specialist
to determine the suitable locations for the exhaust terminal for many
environmental parameters and building geometries.
This paper is written in the frame of two pre-normative studies called In-Vent-Out and In-Vent-Out 2, funded by the Belgian Federal Public Service and the Belgian Building Research Institute.
This
article is based on a paper presented at the 40th AIVC - 8th TightVent & 6th venticool
Conference, 2010 “From energy crisis to sustainable indoor climate - 40 years
of AIVC” held on 15-16 October 2019 in Ghent, Belgium.
Carlo Gualtieri, A. A. (2017). On the Values for the
Turbulent Schmidt Number in Environmental Flows. Fluids.
Fougairolle, P. (2009). Caractérisation expérimentale
thermo-aéraulique d’un jet transverse impactant ou non, en turbulence de
conduite.
Gousseau P, B. B. (2010). CFD simulation of near-field
pollutant dispersion on a high-resolution grid: a case study by LES and RANS
for a building group in downtown Montreal. . Atmospheric Environment 45, 428-438.
Kiyoshi Uehara, S. W. (2003). Studies On Critical Reynolds
Number Indices Forwind-Tunnel Experiments On Flow Within Urban Areas. Boundary-Layer Meteorology 107, 353-370.
Ramponi R, B. B. (2012). CFD simulation of cross-ventilation
for a generic isolated building: impact of computational parameters. Building and Environment 53, 34-48.
Tominaga, Y. M. (2008). AIJ guidelines for practical
applications of CFD to pedestrian wind environment around buildings. Journal of wind engineering and industrial
aerodynamics,
1749-1761.
Follow us on social media accounts to stay up to date with REHVA actualities
0