Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
People spend ~90% of their lifetime indoors
and providing the right environment takes energy and resources. Many efforts
have been undertaken to reduce energy consumption of buildings and today’s
regulations require strict airtightness of buildings. In parallel to the improvements
of the building envelope, the request for sufficient and energy-efficient
ventilation increased. Energy-efficient ventilation schemes have to be applied
as heat losses caused by ventilation are getting more and more pronounced in
conjunction with reduction of the overall energy demand of buildings. Several
studies of today’s airtight buildings showed that sufficient ventilation is necessary
to provide a healthy and comfortable indoor environment and to maintain
building integrity. Measures to improve indoor air quality are cost-effective, considering
potential benefits of reduced sick leave, reduced medical costs and better
performance at work gained at improved indoor air quality.
Today’s ventilation schemes are mainly based on time-scheduled ventilation. However, fixed ventilation schemes often do not account for the right ventilation demand and can lead to a waste of energy. More advanced active systems apply demand controlled ventilation (DCV) using sensors for indoor air quality (IAQ) control. Bad IAQ is often related to humans and their bio-effluents and the most common indicator is carbon dioxide (CO2), whose production is proportional to the human metabolic rate. Nevertheless, the use of CO2 as indicator and state-of-the-art sensors for CO2 quantification, mainly based on non-dispersive infrared adsorption technology, are limited. Events coming along with more complex mixtures of gaseous compounds, mainly volatile organic compounds (VOCs), released by human bio-effluents, cooking odours, outdoor pollutants, cleaning supplies as well as building material and furniture emissions, cannot be detected with CO2as indicator, but play a pronounced role for human air quality perception and some are even a hazard to human health.
AppliedSensor is an international supplier of gas sensing solutions for air quality, comfort, control and safety applications. Improved reproducibility and stability together with low cost potential led to application-driven developments of micro-machined metal oxide semiconductor (MOS) gas sensors for industrial and commercial products in everyday life.
AppliedSensor developed a family of low-cost and compact products for IAQ monitoring and energy-efficent DCV (Table 1). These sensor modules close the gap between direct CO2 and VOC only detection. The detection of relevant indoor VOCs and potentially harmful substances (e.g. CO) is faciliated by the MOS sensing element. An empirical algorithm correlating proportionality of CO2 production rate and metabolic VOC generation allows the iAQ-modules to provide measures of both, CO2 and VOC related events at the same time, and makes the modules applicable in almost every indoor environment. The correlation between human CO2 and VOC production provides a standardized output signal in CO2 equivalent units [ppm] according to the request of HVAC planners and ventilation standards refering DCV settings to CO2 concentrations above outdoors.
The professional iAQ-modules (iAQ-100, iAQ-2000, iAQ-engine, iAQ-Duct Kit) can be used for exhaust/supply air flow control in suitable centralized and decentralized ventilation systems and for automatic window actuation. In addition, AppliedSensor offers the personal indoor air quality monitor (iAM). Plugged to the computer or USB adapter the iAM makes building occupants aware of indoor air conditions signaling ventilation demand by three LEDs (green, yellow, red). The application software can be downloaded from www.appliedsensor.com.
Table 1.AppliedSensor’siAQ modules.
Sensor modules | Measurement
range | Interface | Dimension/weight | Characteristics | |
iAQ-2000 | 450-2000 ppm CO2-eqivalents | I²C, 0-5 V, | 43 x 22 x 7 mm/4 g | Broad application range | |
iAQ-engine | I²C, 0-5 V | 17 x 10 x 4 mm/3 g | Smallest design | ||
iAQ-100 | PWM | 56 x 29 x 14 mm/10 g | Protection class IP 67 | ||
iAQ-Duct Kit | I²C, 0-5 V, | 43 x 22 x 7 mm/4 g | iAQ-2000 with cable, sensor on TO39 for probe-tip integration | ||
iAM | USB | - | Personal IAQ monitor enables manual ventilation | ||
The developed iAQ-modules have been optimized
based on case studies in a variety of environments such as offices, meeting rooms,
schools, kitchens, restrooms and bedrooms.
The benefit of VOC-based IAQ control
compared to CO2-based DCV becomes obvious in
indoor spaces where
changes of CO2 are too small for ventilation
control but indoor air is dominated by odorous events, affecting perceived air
quality to a large extent (e.g. kitchens, restrooms, smoking areas). The iAQ-module allows capture of CO2concentrations and odorous events at the same time, whereas NDIR sensors are only able to
measure the CO2production linked to
the grade of occupancy. The main signals caused by cooking
activities, that can be attributed to VOCsare only detected by the iAQ-module
in the background of CO2 (Figure 1,
right hand side: cooking event).
Implementation
of the empirical algorithm for CO2 prediction
based on anthropogenic VOC detection allows reliable correlation of predicted
and measured CO2 concentrations in indoor spaces
where no appreciable human activity takes place. The perfect correlation of
predicted CO2 equivalents calculated from the
detected VOC level compared to the measured CO2
concentration using NDIR technology is shown by means of a meeting room on the
left hand side of Figure 1.
Figure 1. VOC vs. CO2 approach: predicted and measured CO2 concentrations (meeting room/kitchen).
For long-term stabilty testing, iAQ-modules are permanently operated in the field for more than seven years. Real-life tests comparing long-term operated modules with new sensor modules showed, that perfect functionality in the field is guaranteed even for iAQ-modules with more than 60.000 operating hours (Figure 2).
Figure 2. Long-term stability: Left: 10 weeks IAQ monitoring data of permanently operated
iAQ-2000 module. Right: Real-life test after 60.000 operating hours (iAQ-100).
The iAQ-modules have been tested in various centralized and decentralized commercial ventilation systems for DCV. The main focus has been on energy demand and resulting IAQ compared to natural and time-scheduled ventilation. DCV ensures that fresh air is supplied to interior spaces whenever necessary. When defined threshold limits are exceeded, the module alerts the climate control system to increase ventilation. When VOC levels are minimized, the module instructs the system to decrease ventilation, thereby saving energy and lowering building operation costs.
The results when triggering the supply air rate with the iAQ module instead of applying time-scheduled ventilation are very promising: In a 80 m³ office with two employees, the supply air rate could be reduced by 60% compared to time-scheduled ventilation according to DIN EN 15251 (Figure 3, left hand side) while maintainig good air quality (CO2 concentrations did not exceed 1000 ppm for the design value of 2 people in the office). The ventilation settings can be taken from Table 2.
60% less supply air resulted in 70% less power consumption for the fan and 15% less heating energy demand during heating period 2009/2010 (Figure 3, right hand side).
Table 2.Ventilation settings - office.
Ventilation
Strategy | Description |
Time-scheduled ventilation | Ventilation according to EN 15251 (assuming IAQ category II, low
polluting building material and equipment, 2 attendees) ·
Total air
flow rate: 125 m³/h (Mo-Fr 08:00 a.m. to 06:00 p.m.) ·
6 m³/h
otherwise |
DCV using iAQ-module | Sensor output, 450-2000 ppm CO2 equivalents serves to trigger the ventilation rate
in linear scale from 6 m³/h to 125 m³/h |
In a highly frequented meeting room
designed for 8 people and time-scheduled centralized ventilation of 70 l/s
from 08:00 a.m. to 6 p.m., 50% supply air rate could be saved within one week
applying a 3-step DCV scheme as shown in Figure 4, left
hand side. Step 1: 35 l/s, corresponding to sensor output > 700ppm, step
2: 50 l/s, corresponding
to sensor output > 900ppm and step 3: 70 l/s, corresponding to sensor output
> 1300 ppm.
Figure 3. Left: Supply air rate [m³/h] - DCV compared to time-scheduled
ventilation. Right: Energy demand during winter period 2009/2010 for DCV and
time-scheduled ventilation.
Installation of the sensor module in an air handling unit in a fitness center resulted in 24% less operating time, which translates to 60% energy cost saving with the overall IAQ rated good.
Figure 4. Left: DCV – meeting room. Right: DCV – fitness center.
The
energy findings obtained by the case studies accentuate the need for DCV with AppliedSensor’s
iAQ-modules regarding actual load conditions in buildings. Human adaption often
prevents air quality perception and results in high indoor pollution loads. Time-scheduled
ventilation needs air flow rates to be adjusted before start-up depending on
the average grade of occupancy or activity in the respective room which often
results in a lack of overlap of operation time, ventilation demand, occupancy
profiles and indoor pollution load. IAQ control with the developed iAQ-modules however
ensures that fresh air is supplied to rooms whenever necessary minimizing the amount
of supply air and hence the energy consumption compared to time-scheduled
ventilation (Table 3).
Table 3. Case studies DCV - Supply air rate reduction.
Case study | Supply air
rate reduction |
Office | 60% |
Meeting room | 50% |
Fitness center | 24% |
Follow us on social media accounts to stay up to date with REHVA actualities
0