Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities

Keywords: office building, ground source
heating and cooling, nZEB, energy efficient design, low energy building,
seasonal heat storage |
The Entré
Lindhagen Building which is the new headquarters of Skanska and the Nordic bank
giant Nordea is a very low energy office building. The building is designed to
be one of the greenest office buildings in the Nordic countries without
compromising on indoor climate and functions for the tenants. The office building,
located in the central part of Stockholm, has 57,500 m² rentable floor
area and consists of three parts in 9 office floors and a common basement floor
including garage in 3 levels. Skanska leases half of the building and Nordea
Bank leases the other half. The building was finalized in January 2014. The
expected delivered energy use is 49 kWh/m².

Figure 1.
The façade with external sun shading.
Under the
garage there is an energy storage which consists of 144 bore holes with double
U-tubes 32 mm PE in active depth of 220 m. The system is called
Skanska Deep Green Cooling (DGC) which has a patent in Sweden, is approved for a
patent in US and has patent pending in Europe.

Figure 2.
Illustration of Skanska Deep Green Cooling and a simplified technical
connection scheme of the system.
Summer time
the building is cooled by the energy storage system. In winter time the system
partly heats the building by preheating the supply air for ventilation and at
the same time restoring the energy storage to normal temperature.
The system
solution does not include compressors and the expected COP is therefore high,
between 20 – 30 (!). A smaller building consisting of 3000 m²
rentable area and 12 boreholes is already in use with DGC. A validation of the
performance of the system after one year of operation has resulted in COP=15
with lower annual cooling demand than expected. The system is robust,
consisting only of circulation pumps, heat exchangers and a self-regulating
chilled beam system in office floors.

Figure 3.
The main circulation pumps for the Skanska Deep Green Cooling in the front and
the ground heat exchanger in the rear.
The ground
temperature is used in the same level as the undisturbed ground temperature at
the same depth which makes the system independent of geometry due to heat
losses. The temperature level above freezing makes it possible to use normal
city water in the ground loop instead of ethanol mixture.
The system
is designed to match the entire cooling demand of the building, both indoor
climate demand and process cooling of server rooms, etc. Winter time the ground
temperature level is reset after a hot summer by preheating the outdoor supply
air to the air handling units in an additional coil in the AHUs. The two nearby
multi-family buildings are also connected to the DGC system and preheat outdoor
air for ventilation with additional coils and the DGC gets rid of summer heat
to achieve normal ground temperature level for next summer. Delivered Energy for
heating and power including elevators, fans, pumps, heat losses from pipes and freezing
protection of storm water system, but excluding lighting electricity outlets
for PC, etc is expected to be 49 kWh/m²heated area (65,265 m²)
where heating demand is 33 kWh/m²and power for building
services 16 kWh/m². Cooling demand totally covered by the DGC system is
calculated to be 26 kWh/m² including process cooling. Power to pumps and
pressure drop over coils for DGC is expected to be less than 1 kWh/m² and
is included in the building use above.

Figure 4.
Office air handling unit in operation. Screen dump from BMS.

Figure 5. One
of the office Air Handling Units.
Air
handling units are made for low face velocity around 1.0 m/s through the
coils and filters and the ducting systems are made for max 5 m/s in the
shafts and max 3 m/s on the office floors according to Skanska Commercial
Development Standard, see REHVA Journal 3/2011. Heat recovery is made with
double run around coils and a temperature heat recovery efficiency of over 80%
which enables using all exhaust air for heat recovery, even air from toilets.
The lighting on the office floors is equipped with daylight control and
presence control to further reduce the energy demand.
By these
measures described above the building is very energy efficient. But to reach
what we in Skanska call “deep green” we have to reach net zero primary energy.
As we now have gone from picking the low hanging fruits to the high hanging
fruits, the next step is to include renewable energy. But when we have examined
this we realized that by, for example, balancing the annual heat demand which
will occur during winter with solar heating which will occur during summer, the
environmental usefulness of this will be none or it could even increase the
environmental impact!
How is then the nZEB building possible?
Now we
enter into investigations and studies of the infrastructure of the local
district heating and its connection to the north European power grid. If we
should export heating from the solar heating panels to the district heating
grid during summer, the garbage incineration fueled Combined Heat and Power
plant in the district heating grid has to reduce its production, while there is
less demand for/place for waste heat and that will lead to less production of
power in the CHP plant which will lead to more power production in the existing
coal fired power plants in the north European power grid with more carbon
dioxide emissions. In winter we need the same amount of heat that we produced
by solar collectors in the summer, but now it is produced not only by CHP but
also by bio-fueled boilers or/and even by fossil-fueled boilers. In this case,
the load matching is bad even if we use grid interaction.
How to make the solar heating to have a
positive impact in an advanced district heating system?
In a
northern location like Stockholm we need a seasonal heat storage in order to
get a better load matching between the renewable energy production and the
building heat demand using solar heating. This is not a new technology. Skanska
was the constructor of a 100,000 m³ uninsulated rock cavern filled with
hot ground water used for seasonal storage and heated by solar collectors and
an electric boiler for a local district heating system in Lyckebo, 80 km
north of Stockholm in the 1980s. For the seasonal storage the geometry is of
great importance to avoid too high annual heat losses. To use this technology
in cities, you need large outdoor areas in remote places near railways,
motorways, etc to mount solar collector fields and large seasonal storages to
reduce the losses (heat losses per m³ will decrease by increasing the volume of
the storage). So this has to be made as business development with many
stakeholders. One single building owners do not have the possibility to build
such a system. The district heating company that owns the network has to be
involved, a number of building owners has to agree to invest or to go into long-term
energy agreements with a solar heating seasonal storage system owner. The LCC
cost is also higher than traditional district heating and that has to be
financed somehow, as a part of a green offer to the tenants. We are doing
potential studies, thesis about customer opinions, legal matters, planning case
studies together with the universities, energy companies and the customers.
Skanska is also
developing similar business cases with wind mill organizations on how to keep
out of the certification systems to assure a real addition of green – not only
greenwashing - to have an alternative to put renewable installations on the
buildings if and when that seems wise.
Our efforts
in these projects are aimed at finding reasonable solutions which will increase
the use of renewable energy sources and replace fossil fuels. At the same time
the solutions have to be robust and allow the use of different solutions in
cooperation with the grid when that seems as a good opportunity, instead of
doing it only on the building level and calculating energy meter figures
without taking into consideration the consequences out in the grid, such as
load matching. This implicates the demand for a wider definition of nZEB in
order to make it possible to include initiatives for renewable energy made out
in the grid to be part of the nZEB definition, given that it is a proven real
addition that is equal with initiatives for renewable energy made on the
building. During February 2014, REHVA is starting up a production of a
guidebook lead by Jarek Kurnitski that will show the implications of
on-site and nearby renewable energy systems (RES). IEA annex 52 and task force
40 are working with monthly time steps of load matching and grid interaction.
In Sweden, the consulting company IVL in February 2014 started a project funded
by three different organizations to define methods and different time steps to
show energy performance and carbon dioxide emissions where load matching and
grid interaction are taken into consideration when using RES.
These
initiatives and business development steps are parts of a long-term process
that will hopefully result in real solutions and products that will be accepted
by the market players, the building codes and the classification systems to
make rational decisions possible, and not just sub-optimizing when adding
renewable energy to the buildings in the near future. The result will be a very
low energy building with RES added to the infrastructure grid to reduce the
energy demand down to zero.
Follow us on social media accounts to stay up to date with REHVA actualities
0