Gaëlle GuyotCerema Centre-Est46 rue St Théobald38081 L’Isle d’Abeau Cedex, France.gaelle.guyot@cerema.fr | Max ShermanLawrence Berkeley National Laboratory1 Cyclotron RoadBerkeley, CA 94720, USA | Iain WalkerLawrence Berkeley National Laboratory1 Cyclotron RoadBerkeley, CA 94720, USA |
Indoor air quality is another major area of concern in buildings which is influenced by ventilation. Because people spend most of the time in residential buildings (Klepeis et al., 2001), especially in their bedrooms (Zeghnoun et al., 2010), and 60–90% of their life in indoor environments (homes, offices, schools, etc.) (Klepeis et al., 2001; European commission 2003; Brasche and Bischof, 2005; Zeghnoun et al., 2010; Jantunen et al., 2011), indoor air quality is a major factor affecting public health. Logue et al. (2011b) estimated that the current damage to public health from all sources attributable to IAQ, excluding second-hand smoke (SHS) and radon, was in the range of 4,000–11,000 μDALYs (disability-adjusted life years) per person per year. By way of comparison, this means that the damage attributable to indoor air is somewhere between the health effects of road traffic accidents (4,000 μDALYs/p/yr) and heart disease from all causes (11,000 μDALYs/p/yr). According to the World Health Organization (WHO, 2014), 99,000 deaths in Europe and 81,000 in the Americas were attributable to household (indoor) air pollution in 2012. Health gains in Europe (EU-26) attributed to effective implementation of the energy performance building directive, which includes indoor air quality issues, have been estimated at more than 300,000 DALYs per year.
In order to conciliate energy saving and indoor air quality issues, interest in a new generation of smart ventilation systems, including demand-controlled ventilation (DCV), has been growing for 30 years. A number of ventilation standards and national regulations have progressively integrated an allowance for smart ventilation strategies and/or DCV systems in residential buildings. Simultaneously, progressively energy performance regulations include the opportunity to claim credit in energy calculations for savings from such systems. In Europe, several countries enable the use of DCV systems in ventilation codes, including Belgium, France, Spain, Poland, Switzerland, Denmark, Sweden, the Netherlands, Germany (Savin and Laverge, 2011 ; Kunkel et al., 2015 ; Borsboom, 2015). The corresponding energy regulations are more or less recent.
Thanks to “performance-based approaches”, such systems must often be compared either to constant-airflow systems (“equivalence approaches”) or to fixed IAQ metrics thresholds. Given these opportunities, DCV strategies have been used at massive scale, notably in France and in Belgium, for more than 30 years. On August 1st, 2016, 23 DCV systems in France, 34 in Belgium, 37 in the Netherlands have received an agreement. Most of them are CO2 or humidity-based strategies.
IAQ performance-based approaches could be used in many ways. Table 1 gives an overview of the performance-based approaches used in 5 standards and regulations. Each country uses different IAQ indicators, calculated through different methodologies and compared to different thresholds. The common thread in all of these methods is the use at a minimum, of the exposure to a pollutant generated indoors (very often the CO2), sometimes combined with the condensation risk. A minimum airflow rate for unoccupied periods is also often required.
Table 1. Overview of performance-based
approaches to residential smart ventilation in 5 standards and regulations.
Country | Person in charge | Ventilation Equivalence method | Calculated IAQ indicators | Credit in EP-calculation | Minimum airflow |
USA and Canada (ASHRAE 62.2 2016) | The manufacturer, specifier or designer is supposed to certify that
the calculation meets the requirements. | Single zone modelling, Dt < 1 h, constant pollutant
emission rate. | No specifically defined pollutant. Yearly average relative exposure R<1. At each time-step Ri<5. | No. | Can be null if the total airflow rate equivalence is required over any
3-hour periods. |
France | The manufacturer for each (humidity) DCV system
shall pass through an agreement procedure. | Multizone modelling with MATHIS, Dt = 15 min, Conventional entry data. | Per room, over the heating period: 1/CO2 cumulative
exposure indicator E2000 < 400,000 ppm.h. 2/Number of hours TRH>75%
<600 h in kitchen, 1000 h in bathrooms, 100 h in other rooms. | Average equivalent exhausted airflow (m3/h) can be
implemented in the
EP-calculation. | Switch off not allowed, minimum airflow is 10-35 m3/h according to
the number of rooms in the building. |
Spain (<2017) | The manufacturer for each DCV system shall pass through an agreement
procedure. | Multizone modelling with CONTAM, Dt = 40 s,
Conventional entry data. | Per room, over the year: 1/ Yearly average CO2 concentration < 900 ppm. 2/ Yearly cumulative CO2 exposure over
1600 ppm E1600 < 500,000 ppm.h. | Yearly average ventilation airflow could be implemented in the
EP-calculation. | |
Spain (summer 2017) | The designer of the building, of the base of
information given by the manufacturer. | A performance-based approach for all ventilation
systems is going to be implemented, using a software and conventional data at
the design stage of each building. | Per room, over the year: 1/ Yearly average CO2 concentration < 900 ppm. | Yearly average ventilation airflow could be
implemented in the EP-calculation. | The minimum airflow during unoccupied periods is set
to 1.5 l.s-1 in
each room. |
Belgium (<2015) | The manufacturer for each DCV system shall pass through an agreement procedure. | Multizone modelling with CONTAM, Dt = 5 min,
conventional entry data both deterministic and stochastic. | Per room, over the heating period: 1/CO2 cumulative exposure indicator E’950. | An energy saving coefficient freduc is extrapolated and can be implemented in
the EP-calculation. | |
Belgium (since 2015) | The person involved in EP-calculation and
manufacturer for each DCV system. | No-more existing. | No-more existing. | Published conventional energy saving coefficients
can be used directly in the EP-calculation. They depend on the sensing type,
type of spaces and the regulation type | Minimum airflows over 10% of the minimum constant
airflow for each room. An intermittent ventilation is allowed if the average
on 15 minutes enables to comply with this 10%. |
The Netherlands | The person involved in EP-calculation (standard approach) | Even if correction factors are given in the standard, a complementary
equivalence approach can be performed, using the multizone pressure code
COMIS, in a semi-probabilistic approach. | Per person, over the heating period: Cumulative CO2 exposure over
1200 ppm: LKI1200 < 30,000 ppm.h. | Either, | A function of the number of type of occupants. |
Pushed by the international movement toward nearly-zero energy buildings, smart ventilation system success is not about to end. In Europe, two recently published directives n°1253/2014 regarding the eco-design requirements for ventilation units and n°1254/2014 regarding the energy labelling of residential ventilation units (European Parliament and the Council, 2014) are moving toward a generalization of low-pressure systems, DCV systems and balanced heat recovery systems at the 2018 horizon.
The common thread in all of these performance-based approaches is the use, at a minimum, of the exposure to a pollutant generated indoors (very often the CO2) and condensation risk. Such approaches and corresponding selected IAQ indicators could be criticized in many ways but they exist and have been tested for few years. They could be considered as an interesting background for future IAQ performance-based approaches at the design stage of every new residential building.
The authors would like to thank Samuel Caillou (BBRI, Belgium), Pilar Linares and Sonia García Ortega (CSIC, Spain), and Wouter Borsboom (TNO, the Netherlands) for their help in the description of the past and current performance-based approaches for DCV systems in their countries.
Funding was provided by the U.S. Dept. of Energy, CEC and Aereco SA. The contribution of Cerema is funded by the French Ministries in charge of sustainable development, transports and urban planning, and by the Région Auvergne Rhône-Alpes. The sole responsibility for the content of this publication lies with the authors.
Borsboom, W., 2015. Quality and compliance on building ventilation and airtightness in the Dutch context.
Brasche, S., Bischof, W., 2005. Daily time spent indoors in German homes--baseline data for the assessment of indoor exposure of German occupants. Int. J. Hyg. Environ. Health 208, 247–253. doi:10.1016/j.ijheh.2005.03.003
Communiqué de presse - Indoor air pollution: new EU research reveals higher risks than previously thought [WWW Document], 2003. URL http://europa.eu/rapid/press-release_IP-03-1278_en.htm (accessed 11.28.16).
European Parliament, the Council, 2014. Directive 1253/2014 with regard to ecodesign requirements for ventilation units.
Jantunen, M., Oliveira Fernandes, E., Carrer, P., Kephalopoulos, S., European Commission, Directorate General for Health & Consumers, 2011. Promoting actions for healthy indoor air (IAIAQ). European Commission, Luxembourg.
Klepeis, N.E., Nelson, W.C., Ott, W.R., Robinson, J.P., Tsang, A.M., Switzer, P., Behar, J.V., Hern, S.C., Engelmann, W.H., 2001. The National Human Activity Pattern Survey (NHAPS): a resource for assessing exposure to environmental pollutants. J. Expo. Anal. Environ. Epidemiol. 11, 231–252. doi:10.1038/sj.jea.7500165.
WHO, 2014. Burden of disease from Household Air Pollution for 2012. World
HealthOrganization.
Zeghnoun,
A., Dor, F., Grégoire, A., 2010. Description du budget espace-temps et
estimation de l’exposition de la population française dans son logement. Inst. Veille Sanit. Qual. L’air Intér. Dispon. Sur Www Air-InterieurOrg.
Follow us on social media accounts to stay up to date with REHVA actualities
0