Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Gabrielle MasyMaster School of Province de Liegegabrielle.masy@hepl.be | FlorentDelarbreMaster School of Province de Liege | Cleide AparecidaJCJ Energetics | Jules
HannayJCJ Energetics | Jean LebrunJCJ Energetics |
Keywords: nearly zero energy building, nZEB,
net zero energy building NZEB, house, energy efficiency. |
The method
considered is combining measurements with computer simulation; it has already
been tested in the frame of the previous IEA ECB annex 53 project “Total Energy
Use in Buildings: Analysis & Evaluation Methods”: the measured consumption
of a dwelling was compared with the simulated consumption on different time
bases. The new idea consisted in using the measured indoor temperatures as
input data in the simulation.
Satisfactory
results were obtained, but this was a relatively “easy” case: a poorly
insulated building with negligible solar heat gains and direct electric heating.
The passive
house considered in the present case study might be much more difficult to characterize:
solar heat gain plays an important role and, even during the so-called “heating
season”, the net space heating demand is, most of the time of the same order of
magnitude as other power demands (sanitary hot water, appliances and lighting).
“Passive”
verifications based on a recording of indoor temperatures and energy
consumptions without interference with current life of building occupants might
require too long periods of observation and produce too inaccurate results.
“Active”
verifications will be therefore also considered: they will consist in analyzing
the building response to some artificial variation of heating power thanks to
some “co-heating” equipment.
The house
is built in a very open environment; it’s South oriented, with large glazing
area on that side (Figure 1). Other façades (Figure 2) are much less open to sunshine. According to Passive House Planning
Package (PHPP) description, the building has the following characteristics:
·
Internal
volume: 894 m³
·
Reference
heated floor area: 232 m²
·
Windows:
44 m² (with 31 m² South oriented), triple glazing, U=1 W/m²K
·
Opaque
walls: 244 m², U=0.12 W/m²K
·
Roof:
174 m²U=0.1 W/m²K
This gives,
for the whole envelope, a total area of 583 m² and an average U value of
0.174 W/m²K. According to the pressure test result, the infiltration is of
the order of 0.32 1/h at 50 Pa of overpressure. Per unit of floor
area, the nominal heating power and the yearly heating demands are supposed to be
equal to 9 W/m² and 14 kWh/m² if the whole house is heated.
Figure 1.
South-West corner.
Figure 2.
North-West corner.
Figure 3.
Vertical North-South cross section.
The large
South-oriented glazing is protected from outside by motorized blinds.
The house
is ventilated thanks to a dual-duct mechanical system with fresh air
pre-heating through both ground-connected heat exchanger and air/air recovery
(effectiveness estimated to 65%).
The house
ground floor is equipped with a water floor heating system.
Electric
floor heating is used in both bath rooms (installed powers: 250 and 150 W
in the large and small bath rooms respectively).
The office
room of the second floor is occasionally heated by an electrical convector.
Ground
floor space heating and sanitary hot water systems are supplied from a common
hot water tank heated by an electrical resistance of 4 kW and by 4 m²
of evacuated tubes solar collectors installed on the roof.
The solar
heat exchanger, the electrical resistance and the (space and sanitary) heat use
connections are located at the bottom, at the middle and at the upper part of
the tank, respectively (Figure 4).
The
electrical resistance is controlled in such a way to maintain a temperature of
55°C in the upper part of the water tank. 22.5 m² of PV collectors are
also installed on the roof; their nominal power is of the order of 4500 W.
They are expected to produce a total of the order of 4200 to 4800 kWh/year.
Figure 4.
Boiler equipped with electric resistance and solar thermal collectors, supplying
heat to the living zone heating floor and providing domestic hot water.
In order to
reduce the overheating risk in the living room,external blinds
openings are automatically adjusted every half hour according to the indoor
temperature, provided the heating system and the indoor lighting are switched
OFF.
The
mechanical ventilation is sized for a nominal air flow rate of 350 m³/h. Electric
fan provides thee rotation speeds. Occupants usually impose the middle rotation
speed corresponding to 45% flow rate reduction factor.
The outdoor
air is supplied through 8 outlets (Figure 5):
·
Ground
floor: 3 in the living room
·
First
floor: 1 in each of the three sleeping room and 1 in the office room
·
Second
floor: 1 in the west room
Extractions
are realized through 9 inlets:
·
Ground
floor: 2 in the kitchen, 1 in the toilet and 1 in the technical room
·
First
floor: 1 in each of the two bath rooms, 1 in the washing room and 1 in the
toilet
·
Second
floor: 1 in the east room.
In nominal
conditions, the air should be distributed as follows:
·
Ground
floor: supply 150 m³/h, extraction 130 m³/h
·
First
floor: supply 200 m³/h, extraction of 185 m³/h
·
Second
floor: supply and extraction of about 35 m³/h
Figure 5.
Simplified scheme of the house floor building zones with nominal outdoor air
flows.
In winter
time, the water temperature of the floor heating system is usually maintained
between 28 and 30°C.
The
building is occupied by a four people family (two parents and two children).
All of them are out (for work and school) during week days. The hot water
consumption is estimated to 200 l and 7 kWh per day. This heat demand
is almost completely covered by the solar system in summer time.
Electrical
consumption was manually recorded on a two year period (Figure 6). It corresponds to the integration of the total electricity
consumption of the building. Negative slopes along this curve corresponds to
time periods during which the PV collectors are producing more electricity than
required and sending back energy to the network.
Figure 6.
Integrated total electricity consumption (electricity counter).
The total
electricity consumption and the PV cell production recorded from 1st January
to 31st December 2012 are plotted on Figure 7. The difference is provided by the grid.
Figure 7.
Measured total electricity consumption Wtotal
and PV cell production WPV for a year.
The
corresponding measured electricity consumptions devoted to the boiler, bath rooms
electric floor heating and fans are plotted in Figure 8. The electricity consumptions
devoted to other uses (lighting, appliances and pumps) are deduced from the
energy balance.
Figure 8.
Measured total electricity consumption including the boiler resistance for
space heating and DHW, the electric floor heating in the bathrooms, the fans
and the other uses (lighting, appliances and pumps) for year 2012 (cumulated
curves).
The “fans”
curve corresponds to the consumption of the fans of the mechanical ventilation
system. This consumption (173 kWh/yr) is marginal (it’s even null in some
periods during which the ventilation was not operational).
An energy
balance of the measured electricity consumption is provided in Figure 9.
Figure 9.
Breakdown of electricity consumptions for year 2012.
If not
taking the lighting and appliances consumptions, this house can be considered
as a “nearly zero energy building”: the thermal and PV collectors are roughly
covering the whole (space and sanitary water) yearly heating demand.
Space
heating and sanitary hot water consumptions provided by the boiler are not
actually distinguished in these records (only the total is actually measured). Figure 10 provides a balance of the boiler energy inputs (solar thermal
collectors, electric resistance) and outputs (domestic hot water production and
floor heating in the living zone).
Figure 10.
Energy balance of the boiler for year 2012.
The sanitary
hot water consumption (2554 kWh) on Figure 10 corresponds to an
extrapolation from records having been taken before the installation of the solar
system (7 kWh per day). The production of the solar thermal collector is
expected to reach 2000 kWh per year. The heating demand of the living zone
computed through a dynamic simulation with EES solver, on the basis of 2012
weather data, reaches 513 kWh. It seems to be strongly underestimated.
This is probably due to a stack effect occurring in the staircase that provides
heat from the living zone to the upstairs.
The
analysis of measured electricity consumptions in this passive house inhabited
by occupants who are very motivated for energy saving purposes shows, that the
house can be considered as a “nearly zero energy building”: the thermal and PV
collectors are roughly covering the whole (space and sanitary water) yearly
heating demand. They do not cover the whole lighting and appliances consumptions.
It is
difficult to provide an accurate energy balance of the house on the basis of
the available data, as the effective heat production of the solar thermal
collectors is not recorded. Heat production of the solar thermal collectors
should be measured in order to provide a complete balance of the system.
Dynamic
simulation of the building provided with a floor heating systems at the ground
floor seems to underestimate the ground floor heating demand, probably because
of a stack effect occurring in the staircase and providing heat from the living
zone to the upstairs.
The support
of the Walloon Region of Belgium to the work described in this project is
gratefully acknowledged.
Follow us on social media accounts to stay up to date with REHVA actualities
0