Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
The
suppliers of heat emitters have advertised and promoted positive individual
features of the product, like higher heat radiation, lower back wall losses and
quicker response to control. But this is not that simple: energy efficiency is
associated with the heating process and therefore the matter has to be seen in
the whole, not as a sub-optimization of the details.
There are
of course differences between different radiators and convectors, but the
question is, what are the differences in terms of comfort, energy efficiency
and in the end money?
The purpose
of this article is to provide answers to these essential questions with
objective measurement-based information.
In Figure 1 the considered heat emitter types are illustrated.
Figure 1.
Investigated heat emitters: Normal 2-panel radiator with parallel flow (PAR),
typical 2-panel radiator with serial flow (SER), ideal 2-panel radiator with
serial flow (SERi), conventional round tube/lamella convector with or without
casing (CON) and ideal convector (CONi) like trench convector (not illustrated).= Air bleed.
For
comparison of the heating process in buildings, following functions of heat
emitters are essential:
·
Human
response to the heat emission
·
Heat
radiation into the room
·
Back
wall heat losses
·
Temperature
control function
·
Heat
output capacity at partial loads
·
Influence
on heat generation
Secondary
and from the comparison perspective unimportant items like heat storage and
distribution (pipe work) losses as well as other control methods have not been
taken into consideration in this review.
Main part
of the measurement results referred to in this article are from laboratory
tests performed by Dr. Konzelmann at the WTP GmbH Berlin (Figure 2) and from the analysis done by Professor Kurnitski and his team at the
Tallinn University of Technology as well as from our in-house analysis [1].
Figure 2.
Measurement set up at the WTP GmbH Berlin laboratory.
In
laboratory measurements, we wanted to find out how a normal 2-panel radiator
(PAR) and a typical 2-panel radiator with serial flow (SER) behave under the
control of a thermostatic radiator valve under comparable conditions.
Conclusions of the ideal 2-panel radiator with serial flow (SERi), conventional
convector (CON) and ideal convector (CONi) function can also be drawn with
sufficient accuracy from the measurement results.
Humans are to
detect small and rapid temperature variations in their environment. Up to 0.1
degrees step changes at operative temperature are measured in our own
experimental tests. Instead, slow temperature changes, less than one degree in
15 minutes [2], are not perceived, because the human body's own heat regulation
system is able to adapt to that change under normal conditions. This provides
an explanation why we do not experience a problem, when the thermostat
regulates the radiator water flow and the radiator temperatures shift
correspondingly.
The best
location of the radiator is beneath the window where it blocks the downdraught,
the convection flow from the cold window surface. Another important feature of
the radiator is its thermal radiation, which compensates for the radiant effect
of the colder window surface, creating the conditions for thermal comfort. In
fact, the radiator beneath the window extends the usable interior space.
The 75%
part load means that the free heat gain rate is 25%. The free heat gains
consist of internal heat gains and solar radiation influence. The average cabin
cooling effect was 774 W. Flow temperature was set on 50°C. Thermostatic
radiator valve TRV was a conventional proportional one and water flow rate
lowered to a level of around 1/3 ṁN, where the PAR radiator heat output was in
balance with the heat demand. Differential pressure was kept constant in all
measurements. Nominal flow rate, ṁN, is the flow value of the radiator measured in
the EN 442 conditions and temperatures flow = 75°C, return = 65°C and air =
20°C.
As shown in
Figure 3, The main observations of the test results are
that the SER had around 15% lower heat output capacity than PAR and resulting
to a 26% higher flow rate and to around 3.7°C higher return water temperature.
SER got also an average front panel temperature of 4.5°C higher and 2.5°C lower
average rear panel temperature than the PAR ones.
Figure 3.
PAR and SER running with TRV control at 75% part load conditions.
Theoretically,
the SERi heat output capacity could be a bit higher than SER although own
laboratory measurements of a commercial product did not confirm this difference
[1]. Obvious is that SERi gets at same conditions practically the same flow
rate and return temperatures as PAR. Due to the lower flow rate than SER at
these conditions the front and rear panel temperatures are slightly lower than
the SER ones. For comparison purposes (Table 1) we can well approximate the SERi
panel temperatures: the front 4.0°C higher than the PAR one and the rear
respectively 3.5°C lower than the PAR one. Convector features are handled in
the later part of this review.
Table 1.
75% part load measurement results. * Estimated value
Tflow = 50°C Tair = 20°C Фcool = 774 W | Trtn °C | Tfront °C | Trear °C |
PAR | 32.5 | 39.1 | 40.1 |
SER | 36.2 | 43.6 | 37.6 |
SERi | 32.5* | 43.1* | 36.6* |
CON | – | – | – |
CONi | – | – | – |
Panel
radiator heat output capacity depends not only on the temperatures, but also on
the flow rate and the pipe connection. Radiators with top-bottom-same-end (TBSE)
as well as top-bottom-opposite-ends (TBOE) connections are not so sensitive to
the water flow rate changes that bottom-bottom-opposite-end (BBOE) connections
are. This function is shown in the redrawn graph of Schlapmann [4], Figure 4. Here we can also see the reason why SER has a reduced heat capacity:
the SER rear panel is connected as BBOE and the heat capacity is clearly lowered
at smaller water flow rates. – Increased SER
radiator sizes are needed.
Figure 4.
Panel radiator heat capacity depends also on flow rate and connection type.
A 42% part
load means that the heat gains cover 58% of the heat demand. Measurements were
carried out with an average cabin cooling effect of 875 W and flow
temperature of 70°C in order to get well-measurable function values.
Thermostatic
radiator valve TRV starts to reduce the water flow to the level on which the
radiator heat output corresponds with the heat demand. The proportional control
is no longer reached and the control mode starts to fluctuate as on-off. Water
flow shut-off time is around 30% of the on-off cycle, however, with PAR a bit
longer than with SER.
At start
phase of the fluctuation both temperatures, air and globe, react a bit quicker
with PAR than with SER, due to the higher output capacity of PAR, Figure 5. However, this difference equalizes due to the fact that TRV determines the pace: During regular fluctuation both radiators PAR
and SER have the same cycle time, Figure 6. And that is why there are no
practical differences in the controllability of radiators. Convectors may
benefit slightly from the reduced output capacity at high heat gain rates and
the shut-off time can be shorter. This feature is described in the chapter Return water temperature influence.
Due to the
insufficient differences at on-off modes, the temperature fluctuation impact on
the energy use has not been taken into consideration in this article (generally
it depends on the control used).
Figure 5.
PAR heats up the room slightly quicker than SER.
Figure 6.
PAR and SER running with TRV control at 42% part load conditions. On-off-mode.
Water flows
fluctuate between 0 and 60 kg/h. Flow-rate-weighted average return
temperatures of SER were 2.1°C higher than the PAR ones. Front panel mean
temperature of SER was 5.3°C higher than PAR. Rear panel mean temperature was
correspondingly 3.2°C lower for SER.
Condition
for a PAR (radiator type 22-600-1400), where Tflow = 70°C and Trtn = 32°C with continuous flow, in
other words TRV is still in proportional mode, corresponds to the heat gain
rate of 35%. Obviously the TRV can modulate the flow up to this 35% heat gain
rate and at higher heat gains the TRV changes over to on-off operation.
Corresponding SER values and estimated SERi values are shown in Table 2.
Table 2. 42%
part load results.*Estimated value
Tflow= 70°C Tair= 20°C Фcool = 875 W | Weighted Trtn °C | Tfront °C | Trear °C |
PAR | 32.1 | 40.3 | 40.7 |
SER | 34.2 | 45.6 | 37.5 |
SERi | 32.1* | 45.1* | 36.5* |
CON | – | – | – |
CONi | – | – | – |
For
comparison purposes two different building types have been selected, old and
norm: A post WWII building without thermal insulations layers in the walls, but
2-glass-windows and a norm building representing both newer building types,
from the 90s, and renovated older buildings. Old and norm building features
displayed in Table 3 have been used for calculations.
Table 3.
U-values of reference buildings
External
wall U-value | Window
U-value | |
Old building | 1.39 W/m²K | 2.8 Wm²K |
Norm building | 0.27 W/m²K | 1.2 W/m²K |
Climate
conditions are taken according to Dresden (Germany), where the design outdoor
temperature is -15°C.
Outdoor
temperature of 0°C has been chosen as reference, because it is reasonably near
to the mean temperature of the heating season.
Reference
room is 16 m², window 1.4 x 1.5 m² and heat emitter size 1.4 x 0.6 m².
Heating system design temperatures are 70/55/21°C for old building and 55/45/21°C
for norm building. System flow temperatures at Tout= 0°C are in old building 50°C and in norm
building 41°C. Air change rate is 1/h in both cases. Full load heat demands are
in the old building 890 W and in the norm building 420 W. Heat gain
rates are at these conditions in old building 25% and in norm building 35%.
Default is that at both conditions the TRV works in proportional flow mode.
These
conditions are chosen in order to show the maximum differences between the
heaters. However, in practice the differences are smaller.
With help
of the conversion graph in Figure 7, based on the measured
temperatures, it is possible to estimate the average panel temperatures from
the flow and return temperatures of radiator (Table 4
and 5).
Figure 7.
Radiator temperatures of PAR and SERi in relation to the flow temperature and
the part load rate.
Table 4.
Radiator surface temperatures, old building. *Selected value
Old
building | PAR | SER | SERi | CON | CONi |
Front panel mean, °C | 39.1 | 43.6 | 43.1 | 31* | – |
Rear panel mean, °C | 40.1 | 37.5 | 36.6 | 31* | – |
Table 5.
Radiator surface temperatures, norm building. *Selected value
Norm
building | PAR | SER | SERi | CON | CONi |
Front panel mean, °C | 28.0 | 31.0 | 29.8 | 25* | – |
Rear panel mean, °C | 28.2 | 27.0 | 26.5 | 25* | – |
Based on
these average front panel temperatures it is possible to calculate the heat
radiation influence according to ISO 7726 standard. Measurement point is in the
middle of the room at 0.6 m above floor level, referring to a person in a
sitting position. These calculations are made by Equa Simulation Finland Oy [5].
There is no
standardized calculation method for energy estimations, but the following
calculation method, mean operative temperature MOT, is commonly used. In Tables 6
and 7are the calculated air temperatures giving the same operative
temperatures of 21°C at different heat emitter cases. SER shows the lowest air
temperature due to the highest radiation and CONi respectively the highest.
SERi is quite similar as SER.
Table 6.
Air temperatures giving the same 21°C MOT, old building.
Old
building | PAR | SER | SERi | CON | CONi |
Air, °C | 21.38 | 21.26 | 21.27 | 21.59 | 21.90 |
Table 7.
Air temperatures giving the same 21°C MOT, norm building.
Norm
building | PAR | SER | SERi | CON | CONi |
Air, °C | 21.14 | 21.05 | 21.06 | 21.21 | 21.32 |
Reference location
Dresden’s design outdoor temperature for heating is -15°C. Climate data for the
calculations is taken from the Weather Underground.
Degree-day
value of the old building with base temperature 17°C is 2902 and the difference
of one degree corresponds with 10% difference in energy use.
Norm
building degree-day value with base temperature 15°C is 2354 and the difference
of one degree corresponds with 12% difference in energy use.
Tables 8 and 9 show how much operative temperature
differences (Tables 6 and 7) add to energy needs of different
emitter types.
Table 8.
Heat radiation influence in old building.
Old
building | SER/SERi | PAR | CON | CONi |
Additional energy | 0 | + 1.2% | + 3.3% | + 6.4% |
Table 9.
Heat radiation influence in norm building.
Norm
building | SER/SERi | PAR | CON | CONi |
Additional energy | 0 | + 1.0% | + 1.8% | + 3.1% |
From the
measurement results of WTP GmbH Berlin it is possible to calculate, with good degree
of accuracy, the back wall heat losses caused by the heat emitter, see Table 10, 11 and 12.
Table 10.
Emitter back and back wall temperatures in old building. *Selected value
Old
building | PAR | SER | SERi | CON | CONi |
Emitter back mean, °C | 40.1 | 37.5 | 36.6 | 31* | – |
Back wall mean, °C | 29.5 | 28.1 | 27.6 | 24.7 | – |
Table 11.
Emitter back and back wall temperatures in norm building.*Selected
value
Norm
building | PAR | SER | SERi | CON | CONi |
Emitter back mean, °C | 28.2 | 27.0 | 26.5 | 25* | – |
Back wall mean, °C | 23.3 | 22.6 | 22.4 | 21.6 | – |
Following the
back wall temperature values the radiator back wall losses can be calculated at
outdoor temperature of 0°C.
Table 12.
Back wall losses caused by the heat emitter.
Additional
energy need | PAR | SER | SERi | CON | CONi |
Old building | + 2.24% | + 1.91% | + 1.79% | + 1.10% | – |
Norm building | + 0.36% | + 0.28% | + 0.26% | + 0.18% | – |
Bleeding of
the air is a problem at construction of the serial panel radiators. In order to
get the serial panel radiator to function ideally, both panels, front and rear,
should be bled separately. To enable this, complicated air venting arrangements
are needed. Therefore, the product costs will increase.
All
commercial SER products are compromised by having a tiny opening between the
front and rear panels. This helps to bleed the air through the same air vent at
the upper end of the radiator, but it inevitably leads to a leak flow from front
panel to rear panel resulting in a situation, where the top of the rear panel
is warmer than the flow water from the front to back panel. This prevents the
water rising up in the rear panel, which causes an additional reduction on the
output capacity of the rear panel particularly at the part load conditions.
This has been found in the measurements [3].
The leak
flow in SERi radiator reduces also the output capacity and equalizes the front
and rear panel temperatures. However, the disadvantage is not as serious as in
SER radiators.
Serial
panel radiator has an increased flow resistance. When parallel panel radiator
resistance corresponds with around kv 3.3, serial panel resistance is more
than the double, kv 1.3. The pressure difference between the panels can be
a few hundred Pascal even in normal sizes of serial radiators and the leak flow
through even smaller openings is unavoidable.
As shown in
Figure 4 panel radiator output capacity depends also on
the connection type and flow rate. We can recognize that SER radiator’s rear
panel connection is BBOE type and thereby SER radiator capacity is always
smaller than the PAR one. In addition, the leak flow reduces the output
capacity further.
As
mentioned above in the 75% part load case, the return water temperature of SER
radiator was measured 3.7°C higher than in the PAR. Also, in the 42% part load
case this reduction was remarkable – the higher return water temperature,
the higher the condensing boiler and heat pump fuel consumption.
Heat output
capacity of convectors with round pipe/lamella construction depends strongly on
the water flow type, turbulent or laminar. When the flow rate is decreased, the
convector output capacity decreases in accordance with the Reynolds number.
This dependence, according to Dr. Konzelmann [3], is shown in Figure 8.
Figure 8.
Convector heat output depends on water flow conditions.
Example: Typical
convector construction with heat output capacity at dT50K (EN442) is 800 W.
In case of 75% part load, flow temperature of 50°C and 248 W heat demand
the return water temperature rises up to a level of 39°C. – Comparable case, PAR radiator with a return water
temperature of 33°C. |
Note. This heat output capacity reduction effect has
not been taken into account in the product standards EN442 and EN16430:
standard heat output values are valid only at full load conditions with
relatively high water flow rates. Design flow rates are often clearly lower,
which leads to incorrect design selections.
In Figure 9 we can find, according to Professor Oschatz’s measurement and study
[6], the dependence of heating system return water temperature on the condensing
gas boiler combustion efficiency: trend line value 0.4%/K. The burner load rate
has also a slight influence on the efficiency: the lower load the higher
efficiency and respectively the higher load the lower efficiency.
Figure 9.
Condensing boiler combustion efficiency depends on system return water
temperature
Annual
coefficient of performance, COPa, is also linked not only to the system flow
water temperature, as often assumed, but also to the system return water
temperature. According to the calculations done the change of one degree in
system water temperature gives a COPa change of 1.2% [8]. In addition, the COP
value depends on the heat pump condenser temperature. It is also measured that
the system flow water temperature has a 2/3 and system return water temperature
a 1/3 influence to the condenser temperature, Figure 10.
Figure 10.
Influence to heat pump efficiency, Prof. Kurnitski [7]. Flow water temperature
2/3 and return water temperature 1/3.
In
conclusion, we can say that in both condensing boiler and heat pump, lowering
the system return water temperature by one degree, the heat generation
efficiency rises by 0.4%.
When using
the return water temperatures from the 75% par load case, SER has 3.7°C higher
return water temperature than PAR and SERi, and CON and CONi respectively
around 6°C higher than PAR and SERi, following figures for heat generation efficiencies can be calculated, Table 13. These values are valid for both reference buildings with a reasonable
accuracy.
Table 13.
Relative heat generation influence and additional energy needs.
Heat
generation influence | PAR/SERi | SER | CON/CONi |
Additional energy | 0 | + 1.5% | + 2.4% |
Table 14 shows a collection and summary of
the relative effect of different heat emitters on the heating system
efficiency: additional energy need.
Table 14.
Relative effect of different heat emitters on system efficiency
Additional
energy need | PAR | SER | SERi | CON | CONi |
Old building | + 3.4% | + 3.4% | + 1.8% | + 6.8% | + 8.8% |
Norm building | + 1.4% | + 1.8% | + 0.3% | + 4.4% | + 5.5% |
According
to the results differences between the radiators in both old and norm buildings
are very small, max 1.5%. However, the convectors differ clearly from the
radiators.
Heat
radiation differences of different radiator types are so small that they are
practically out of human perception capability [9].
When the
functional differences between the radiators are small, the decisive difference
is their price. But how much more money is meaningful to invest in radiators
that are claimed to be more energy-efficient?
Example: In
a typical German detached house of 170 m² from the mid-90s the space
heating energy is around 15 000 kWh per year. When using the gas
price of 0.065 €/kWh, the heating bill is around 975 €/a. The result
difference between a “standard radiator” and an “ideal serial panel radiator”
is 1.1%. The corresponding energy cost difference is on average 10.70 €/a.
This divided typically into 10 radiators results in maximum annual savings of 1.07 €
per radiator. For instance, the price of an “ideal
serial panel radiator” for the end user is several dozens of euros higher than the price of a
standard radiator. This extra price, for example 30 € for the end user, divided by 1.07 €/a
leads to a pay-back time of 28 years!
The reduced
heat output capacity of the “typical serial panel
radiator”
causes needs to increase the radiator size: for example, a typical 10% addition
increases the price for the end user by around 25 €, and this without any pay-back.
The
additional heating energy demand and the lack of radiant effect of convectors
seem to be more noticeable: there must be additional arguments for convector
selection.
In modern
energy efficient buildings, which are better insulated and often equipped with
heat recovery ventilation, the heating energy demand is only half or less of
the “norm building” used in this review. Therefore, the small differences of
radiators in new buildings are completely irrelevant from the energy saving
point of view.
In
conclusion, it is clear that there is no tangible, financial nor physiological
benefit for home owners to pay the increased cost associated with the alleged
but unsubstantiated “more energy efficient radiators”. – A standard radiator is the best option.
[1] RETTIG ICC Research Centre, EN442 laboratory.
[2] ASHRAE ANSI standard 55.
[3] WTP GmbH Berlin, EN 442 laboratory.
[4] Schlapmann, HLH 9-76.
[5] Equa Simulation Finland Oy.
[6] Technical University of Dresden.
[7] Tallinn University of Technology.
[8] IVT VPW2100 software.
[9] Human Thermal Model, VTT Technical Research
Centre of Finland.
Follow us on social media accounts to stay up to date with REHVA actualities
0