Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities

Keywords: air conditioning, seasonal efficiency, certification, SCOP, SEER, Eurovent Certita Certification, energy label |
| Launched in 1994, the Air Conditioners certification programme was the first programme of Eurovent Certita Certification (ex Eurovent Certification Company). After almost 20 years it is well recognized on the market as well as the mandatory energy efficiency labelling for air conditioners below 12 kW since 2003. |
This certification programme concerns comfort units, air-to-air and water-to-air below 100 kW (nominal capacity in cooling mode). It also applies to units intended for both cooling and heating by reversing the cycle. Concerning multi-split air conditioners, only systems with two indoor units are included.
The purpose of all Eurovent Certita Certification Certification Programmes is to encourage honest competition and to assure customers that equipment is correctly rated on the market. The purpose is achieved by verifying the accuracy of ratings claimed by manufacturers by continuing testing of production models, randomly selected, in independent laboratories.
One particularity of Air Conditioners programme is to apply the “Certify-all” principle, meaning:
All products of the
relevant certification programme manufactured or sold by a Participant inside
the defined scope must be certified. When applicable, “Certify-all” principle
means at least “all products inside the defined scope presented, at least, on
the European market”.
“Certify-all” brings clarity and transparency and therefore increases the value of the whole system.

Figure 1. Steps in the certification process
of the product performance.
The certified performances depend on the product (below or above 12 kW) and the applicable EU Directives.
Commission Regulation (EU) No 206/2012 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to EcoDesign requirements for air conditioners and comfort fans gives requirements for all air conditioners with the cooling capacity under 12 kW (AC1) introduced on the European market after the 1st January 2013.
The Directive defines energy efficiency as shown in the Table 1.
Table 1. Requirements of minimum energy efficiency of air condition units with cooling capacity under 12 kW in the European market according to the EC regulation (see the definitions of abbreviations in the article by Sandrine Marinhas in this issue).
| Air conditioners, except
double and single duct air conditioners | |
SEER | SCOP (Average climate) | |
If GWP of refrigerant > 150 for < 6 kW | 4,6 | 3,8 |
If GWP of refrigerant ≤ 150 for < 6 kW | 4,14 | 3,42 |
If GWP of refrigerant > 150 for 6–12 kW | 4,3 | 3,8 |
If GWP of refrigerant ≤ 150 for 6–12kW | 3,87 | 3,42 |
GWP = Global Warming Potential | ||

Figure 2. The model of the required energy label for all air conditioning unit in the European market from the beginning of 2013.
Moreover, Commission Regulation (EU) No 626/2011 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to energy labelling of air conditioners makes mandatory energy labelling of all air conditioners with the cooling capacity below 12 kW introduced on the European market after the 1st January 2013. The Directive defines, for each function, the energy class going from A+++ (more efficient) to G (less efficient). The classification is given in the Table 2.
Table 2. Energy Classification for Conditioners except double ducts and single ducts.
Energy Efficiency Class | SEER | SCOP |
A+++ | SEER ≥ 8.50 | SCOP ≥ 5.10 |
A++ | 6.10 ≤ SEER < 8.50 | 4.60 ≤ SCOP < 5.10 |
A+ | 5.60 ≤ SEER < 6.10 | 4.00 ≤SCOP < 4.60 |
A | 5.10 ≤ SEER < 5.60 | 3.40 ≤ SCOP < 4.00 |
B | 4.60 ≤ SEER < 5.10 | 3.10 ≤ SCOP < 3.40 |
C | 4.10 ≤ SEER < 4.60 | 2.80 ≤ SCOP < 3.10 |
D | 3.60 ≤ SEER < 4.10 | 2.50 ≤ SCOP < 2.80 |
E | 3.10 ≤ SEER < 3.60 | 2.20 ≤ SCOP < 2.50 |
F | 2.60 ≤ SEER < 3.10 | 1.90 ≤ SCOP < 2.20 |
G | SEER < 2.60 | SCOP < 1.90 |
The SEER and SCOP, mentioned in the Directive, represent the usual operating conditions of the equipment over a season. This operating condition can be better assessed by comparing equipment at representative reduced capacities (Table 3).
European standard EN 14825 provides part-load conditions and calculation methods for calculating the SEER and SCOP of such units when they are used to fulfil the cooling and heating demands.
Other energy consumptions can occur when the unit is not used to fulfil the cooling and heating demands such as those from a crank case heater or when the unit is on standby. These consumptions are considered in the calculation methods for reference SEER and reference SCOP.
Fixed capacity air conditioners deal with varying loads by varying the operation time. The efficiency of the system is dependent on the effectiveness of the controlling thermostats. Variable capacity air conditioners, by continuous or step control of the compressor, can more closely match the varying load improving system efficiency.
Table 3. Testing conditions for rating of air conditioning units and the information available from the units tested and certified by the Eurovent Certita Certification.
Cooling Mode | Heating Mode |
Performances in Standard
rating conditions | |
Cooling Capacity @ 35°C EER @ 35°C | Heating Capacity @ 7°C COP @ 7°C |
Seasonal Performances | |
Design Capacity | Design Capacity Bivalent Temperature Performance @ T°biv TOL (Operation limit temperature) Performance @ TOL |
SEER Annual
electric power consumption | SCOP Annual
electric power consumption |
Auxiliary Power consumption (Standby mode, Off mode...etc.) | |
Sound Power Level | |
These Seasonal Energy Efficiency Ratio for cooling mode (SEER) and Seasonal Coefficient of Performance for heating mode (SCOP) came in addition, since the 1st January 2013, to the well-known Energy Efficiency Ratio (EER and COP).
Some new characteristics are currently being tested with a view of being certified, as the performances at Bivalent Temperature[1] or at Operation limit temperature[2], and also the annual electric power consumptions. These new items will better help customers to compare and make their choices.
The certified performances available on the Eurovent Certified Performance Website are listed in Table 3.
Figures 3 and 4 show the distribution of the Seasonal Performance in relation with
the capacity.
|
|
Figure 3.
Seasonal Energy Efficiency Ratio for cooling mode (SEER). Each dot represents
a different unit. (Eurovent 2013 certified data for Air conditioning units
<12kW). | Figure 4.
Seasonal Coefficient of Performance for heating mode (SCOP). Each dot
represents a different unit. (Eurovent 2013 certified data for
Air-conditioning units <12kW). |
Figure 5 shows the SEER in relation with the SCOP.

Figure 5.
SEER vs. SCOP (Eurovent 2013 certified data for Air conditioning).
These graphs show that the requirements for the European regulation were more stringent for the heating mode than for the cooling mode, as the cut-off is more vertical than horizontal. Indeed, as shown in Figure 5, strong parallel requirements on both performances would have generated a more angular shape of the distribution.
SCOP limits SEER when SCOP is between 3.4 and 3.75. For a SCOP above 3.8 the amplitude of SEER is increased (SEER up to 7 to 8). Correlation between SCOP and SEER becomes chaotic for high SCOPs: these units are for sure on the radar screen of certification for verification of their high declared performance.
Currently, the certified data are EER and COP at Standard Rating Conditions and Sound Power Level.
Table 4. Rating conditions and standards used to measure the performance of the air conditioning units with cooling capacity over 12 kW.
Cooling Mode | Heating Mode |
Performances in Standard
rating conditions | |
Cooling Capacity @ 35°C EER @ 35°C | Heating Capacity @ 7°C COP @ 7°C |
Sound Power Level | |
The objective of the Eco-design Directive is to
improve the energy efficiency and to reduce the environmental impacts. The
seasonal performance of air conditioning units represents better the energy
efficiency of the unit than peak performance. A first draft of regulation based
on Eco-design Directive, including the seasonal performance criteria was in
consultation with stake holders already in 2013.
This document contains products in relation with:
·
ENER[3]
Lot[4]
21 (central air heating products)
·
ENTR[5]
Lot 6 (air conditioning products)
·
ENTR Lot 1 (high temperature process
chillers)
This future directive will impact:
·
Heat Pumps air-to-air ≥ 12 kW
·
Heat Pumps water-to-air up to 1 MW
·
Chillers (reversible Heat Pumps in cooling
mode) air-to-water and water-to-water up to 2 MW
and also:
·
Air Conditioners air-to-air ≥ 12 kW
·
Air Conditioners water-to-air up to 2 MW
The preparatory study identified the following
significant environmental aspects to be regulated:
·
Energy efficiency
·
Carbon dioxide and nitrogen emissions,
·
Sound power levels.
The energy performance requirements related to the
seasonal performance SCOP/SEER with calculation methods very similar to those
already existing in EN 14825.
Consequently, if the timeframe doesn’t change, all Air
Conditioners (below and above 12 kW) have to have Seasonal Performances Data
from January 2017 and will have to respect the Directive requirements.
The Air Conditioners programme offered
by Eurovent Certita Certification will integrate these parameters as soon as
possible in order to /offer to our participants a programme in line with the future
EU directives.
Making the certified data easily available for end-users and consultants has always been a priority for Eurovent Certita Certification. Our directory of certified data, available since the creation of the company, and launched as an interactive website around 2001, brings reliable data to end-users. In addition to the certified data a dedicated description page for each certification programme containing the outline of the programme, definitions and rating conditions is made accessible and constantly updated to help visitors understand the value of certified data (http://www.eurovent-certification.com)
We are at the turning point concerning the Energy
efficiencies for all thermodynamic systems (Air Conditioners, Rooftops, Liquid
Chilling Packages …). The usual energy efficiencies achieved at full load are
going to disappear gradually in order to be replaced by new performances which
will better describe these units in terms of energy consumption. Soon, the new European
Regulation will change also the current market by fixing higher requirements. With
them, the verification of the published data by a third-party body, such as
Eurovent Certita Certification for e.g., remains a useful added value to verify
the announced performances as a complement to the market surveillance, and to help
comparing the products thanks to the online database.
[1]Bivalent temperature: lowest
outdoor temperature point at which the heat pump is declared to have a capacity
able to meet 100 % of the heating load.
[2]Operation limit
temperature: lowest outdoor temperature at which the heat pump can still
deliver heating capacity, as declared by the manufacturer.
[3]ENER=
Directorate General of Energy
[4] Lot= product group
[5]ENTR=
Directorate General of Enterprise and Industry
Performance of air-conditioners used to be compared at a fixed condition. However, this condition does not represent the usual operating conditions of the equipment over a season, which becomes especially important for the calculation of the energy efficiency. Seasonal performance first appeared in Eurovent Certification programme for chillers in 2006. The European Commission defined a seasonal efficiency for residential Air Conditioners applicable since 1st January 2013; consequently Eurovent Certita Certification has updated its programme in accordance with this regulation.
Keywords: air conditioning, seasonal efficiency, certification, SCOP, SEER, Eurovent Certita Certification, energy labe
Scope of the programme Air Conditioners certification programme concerns comfort units, air-to-air and water-to-air below 100 kW (nominal capacity in cooling mode). It also applies to units intended for both cooling and heating by reversing the cycle. Concerning multi-split air conditioners, only systems with two indoor units are included. Process of Certification The purpose of all Eurovent Certita Certification Certification Programmes is to encourage honest competition and to assure customers that equipment is correctly rated on the market. The purpose is achieved by verifying the accuracy of ratings claimed by manufacturers by continuing testing of production models, randomly selected, in independent laboratories.
Follow us on social media accounts to stay up to date with REHVA actualities
0