Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
The full length version of this article is available at the journal website: http://www.rehva.eu/ -> REHVA Journal
EPBD recast
(2010/31/EU) launched nearly zero energy (nZEB) target in 2010 with the need
for the Member States to define what nZEB for them exactly constitutes. REHVA
experts realized the problem that various definition of nZEB may cause in
Europe and established a task force to prepare technical definitions and system
boundaries for energy performance calculations.
Starting
point for technical definitions is the requirement of nZEB in EPBD recast
formulated as buildings with a very high energy
performance
and where energy need is covered to a very
significant extent by energy from renewable sources. Since EPBD recast does not give
minimum or maximum harmonized requirements as well as details of energy
performance calculation framework, it will be up to the Member States to define
what “a very high energy performance” and “to a very significant extent by
energy from renewable sources” for them exactly constitute.
nZEB
definition shall be based on delivered and exported energy according to EPBD
recast and prEN 15603:2013. The basic energy balance of the delivered and
exported energy and system boundaries for the primary and renewable energy
calculations, are shown in Figure 1 and 3
(for on site and for nearby assessment), and described with detailed system
boundary definitions in Figures 4 and 5.
According to EPBD recast, all components of the energy use are mandatory except
the energy use of appliances (households, elevators/escalators and outlets)
which may or may not be included. With the inclusion of appliances, energy use
in the buildings includes energy used for heating, cooling, ventilation, hot
water, lighting and appliances.
Figure 1. System boundaries for on site assessment (nearby production not linked to the building) connecting a building with on site renewable energy (RE) sources to energy networks. System boundary of energy use of building technical systems follows outer surface of the building in this simplified figure; system boundary of delivered and exported energy on site is shown with dashed line. In the case of nearby production, the nearby system boundary will be added, as shown in Figure 3.
According
to Figure 1, for delivered electricity and thermal energy
it applies:
(1)
and
(2)
where
Eus is total energy use kWh/(a);
Edel is delivered energy on site (kWh/a);
Eexp is exported energy on site (kWh/a);
Eren is on site renewable energy without fuels
(kWh/a);
subscript el
refers to electricity and T to
thermal energy.
An example in Figure 2 explains the use of Equation 1. An all electrical building with energy use of 100 has a PV system generating 20, from which 10 is used in the building and 10 is exported. With these values, delivered energy on site becomes:
Figure 2. An example of an all electrical building explaining the use of Equations 1 and 2.
In order to
be able to take into account a new nearby renewable energy production capacity
contractually linked to the building and providing the real addition of the
renewable capacity to the grid or district heating or cooling mix in connection
with construction/development of the building(s), the system boundary of Figure 1 has to be extended. (If not contractually linked to the building,
nearby production is calculated with primary energy factors of the network mix
as shown in Figure 1.) To calculate delivered and
exported energy nearby, the energy flows of nearby production plant
contractually linked to building are to be added/subtracted to the delivered
and exported energy flows on site, Figure 3. Prerequisite to apply this nearby
assessment, is the availability of national legislation allowing to allocate
such new capacity to the building/development with a long term contract and
assuring that the investment on that new capacity will lead to a real addition
to the grid or district heating or cooling mix.
Figure 3. Nearby assessment boundary to be used in the case of nearby energy production linked contractually to the building. Compared to on site assessment boundary, delivered and exported energy flows on site are replaced by delivered and exported energy flows nearby.
Primary
energy indicator sums up all delivered and exported energy (electricity,
district heat/cooling, fuels) into a single indicator. Primary energy and
primary energy indicator are calculated from delivered and exported energy with
national primary energy factors as:
(3)
(4)
where
EPP is the primary energy indicator (kWh/(m²
a));
EP,nren is the non-renewable primary energy
(kWh/a);
Edel,i is the delivered energy on site or nearby
(kWh/a) for energy carrier i;
Eexp,i is the exported energy on site or nearby
(kWh/a) for energy carrier i;
fdel,nren,i is the non-renewable primary energy factor
(-) for the delivered energy carrier i;
fexp,nren,i is the non-renewable primary energy factor
(-) of the delivered energy compensated by the exported energy for energy
carrier i, which is by default equal
to the factor of the delivered energy, if not nationally defined in other way;
Anet useful floor area (m²) calculated
according to national definition.
Net zero
energy building definition has an exact performance level of 0 kWh/(m² a)
non renewable primary energy. The performance level of “nearly” zero energy is
a subject of national decision taking into account:
·
technically
reasonably achievable level of primary energy use;
·
how
many % of the primary energy is covered by renewable sources;
·
available
financial incentives for renewable energy or energy efficiency measures;
·
cost
implications and ambition level of the definition.
The
following definitions were prepared for uniformed EPBD recast implementation:[1]
net zero energy building (net ZEB)
Non-renewable
primary energy of 0 kWh/(m² a).
nearly zero energy building (nZEB)
Technically
and reasonably achievable national
energy use of > 0 kWh/(m² a) but no more than a national limit value of
non-renewable primary energy, achieved with a combination of best practice
energy efficiency measures and renewable energy technologies[2] which may or may not be cost
optimal[3].
The set of
detailed system boundaries are extended from the assessment boundary of prEN
15603:2013. As stated in EPBD recast, the positive influence of renewable
energy produced on site is taken into account so that it reduces the amount of
delivered energy needed and may be exported if cannot used in the building
(i.e. on site production is not considered as part of delivered energy on
site), Figure 4.
Figure 4. Three system boundaries (SB) for on site assessment (nearby production not linked to the building), for energy need, energy use and delivered and exported energy calculation. System boundary of energy use applies also for renewable energy ratio calculation with inclusion of RE from geo-, aero- and hydrothermal energy sources of heat pumps and free cooling as shown in Figure 5.
In order to
calculate the share of renewable energy use, renewable energy ratio RER, all
renewable energy sources have to be accounted for. These include solar thermal,
solar electricity, wind and hydro electricity, renewable energy captured from
ambient heat sources by heat pumps and free cooling, renewable fuels and off
site renewable energy. Ambient heat sources of heat pumps and free cooling are
to be included to the renewable energy use system boundary, because in RER
calculation, heat pumps and free cooling are not only taken into account with
delivered energy calculation based on COP, but also by the extracted energy
from ambient heat sources. Renewable energy use system boundary is shown in Figure 5.
Figure 5. Renewable energy use system boundary for renewable energy ratio RER calculation. In addition to energy flows shown in Figure 4, renewable thermal energy from ambient heat pump and free cooling sources (heat exchangers) is accounted.
The
renewable energy ratio is calculated relative to all energy use in the
building, in terms of total primary energy. It is taken into account that
exported energy compensates delivered energy. By default, it is considered that
the exported energy compensates the grid mix or in the case of thermal energy,
the district heating or cooling network mix. For on-site and nearby renewable
energy the total primary energy factor is 1.0 and the non-renewable
primary energy factor is 0. Total primary energy based RER equation is the following:
(5)
where
RERP is the renewable energy ratio based on the
total primary energy,
Eren,i is
the renewable energy produced on site or nearby for energy carrier i, kWh/a;
fdel,tot,i is the total primary energy factor (-) for
the delivered energy carrier i;
fdel,nren,i is the non-renewable primary energy factor
(-) for the delivered energy carrier i;
fexp,tot,i is the total primary energy factor (-)of the
delivered energy compensated by the exported energy for energy carrier i;
Edel,i is the delivered energy on site or nearby
for energy carrier i, kWh/a;
Eexp,i is the exported energy on site or nearby
for energy carrier i, kWh/a.
Consider an
office building located in Paris with following annual energy needs (all values
are specific values in kWh/(m² a)):
·
3.8 kWh/(m²
a) energy need for heating (space heating,
supply air heating and DHW)
·
11.9 kWh/(m²
a) energy need for cooling
·
21.5 kWh/(m²
a) electricity for appliances
·
10.0 kWh/(m²
a) electricity for lighting
Breakdown
of the energy need is shown in Figure 6.
The building has a gas boiler for heating with seasonal efficiency of 90%. For the cooling, free cooling from boreholes (about 1/3 of the need) is used and the rest is covered with mechanical cooling. For borehole cooling, seasonal energy efficiency ratio of 10 is used and for mechanical cooling 3.5. To simplify the calculation, emission and distribution losses of the heating and cooling systems are neglected in this example. Ventilation system with specific fan power of 1.2 kW/(m³/s) and the circulation pump of the heating system will use 5.6 kWh/(m² a) electricity. There is installed a solar PV system providing 15.0 kWh/(m² a), from which 6.0 is utilized in the building and 9.0 is exported to the grid.
Energy
calculation results are shown in Figure 6, in the building technical systems
box. Gas boiler with 90% efficiency results in 4.2 kWh/(m² a) fuel energy.
Electricity use of the cooling system is calculated with seasonal energy
efficiency ratios 10 and 3.5 respectively. Electricity use of free cooling,
mechanical cooling, ventilation, lighting and appliances is 39.8 kWh/(m²
a). Solar electricity of 6.0 kWh/(m² a) used in the building reduces
the delivered electricity to 33.8 kWh/(m²
a). The rest of PV electricity, 9.0 kWh/(m2 a) is exported. The
delivered fuel energy (caloric value of delivered natural gas) is 4.2 kWh/(m²
a).
In this
example, it is considered that 20% of the grid electricity is from renewable
sources with the non-renewable primary energy factor of 0 and the total primary
energy factor of 1.0. For the rest of 80% of the grid electricity the total and
non-renewable primary energy factor of 2.5 is used. Therefore, the
non-renewable primary energy factor of the grid mix is 0 · 0.2 + 2.5 · 0.8
= 2.0 and the total primary energy factor is 1.0 · 0.2 + 2.5 · 0.8
= 2.2. It is assumed that exported electricity compensates the grid mix.
Figure 6. Calculation example of the energy flows in nZEB office building.
Figure 7. Some nZEB office buildings are calculated and reported according to REHVA definition that makes it possible to compare the results. See in Journal 3/2011, 2/2012 and 5/2012 for these buildings from France, the Netherlands, Switzerland, Finland.
REHVA nZEB
Task Force and CEN EPBD project group members are greatly acknowledged for this
work: Francis Allard, Derrick Braham, Dick van Dijk, Jacquelyn Fox, Jonas
Gräslund, Per Heiselberg, Frank Hovorka, Risto Kosonen, Jean Lebrun, Zoltán
Magyar, Livio Mazzarella, Ivo Martinac, Vojislav Novakovic, Jorma Railio, Olli
Seppänen, Igor Sartori, Johann Zirngibl, Michael Schmidt, Maija Virta, Karsten
Voss, Åsa Wahlström.
[1] ‘reasonably achievable’ means by comparison
with national energy use benchmarks appropriate to the activities served by the
building, or any other metric that is deemed appropriate by each EU Member
State.
[2] Renewable energy technologies needed in
nearly zero energy buildings may or may not be cost-effective, depending on
available national financial incentives.
[3] The Commission has established a comparative
methodology framework for calculation of cost-optimal levels (Cost optimal).
Follow us on social media accounts to stay up to date with REHVA actualities
0