Aleksandar PjevićCompany: Lindab GroupMain project engineerThe member of KGH – Serbian HVAC&R Societyaleksandar.pjevic@lindab.com |
The main problems that occur in the case of increased humidity above certain level in buildings of various purposes are the next:
· development of mold and bacteria
· condensation on all structures
· corrosion
· feeling of stuffy and uncomfortable air
· forming of frost or ice on heat exchangers.
Just because of that, different buildings and facilities presented in Table 1, require air drying treatment in order to avoid the indicated consequences :
Table 1. Building types and humidity problems
Buildings that require moisture removal | Consequences | |
1 | Pharmacy - production of hygroscopic medicaments | a) Medicaments cannot be used |
2 | Ice halls and hockey arenas | a) Deterioration of ice quality b) Increasing of the ice thickness c) Condensation of water vapor |
3 | Facilities with swimming pools | a) Destruction of the building structure and external walls, corrosion on metal surfaces b) Bad climatic conditions for living and strong smell of chlorine |
4 | Food industry, raw material warehouses | a) Formation of places with intensive growth of fungi and bacteria, issues of the microbiological situation b) Corrosion |
5 | Beer production | a) Growth of bacteria and microorganisms b) Low quality products |
Condensation method. The essence of the method is based on the principle of water vapor condensation, contained in the air, when it is cooled below the dew point.
The executive mechanism of the process is a heat pump with a freon contour, whose elements, the evaporator and the condenser, are located one after the other (Figure 1).

Figure 1. Functional diagram of the condensation method.
Moisture adsorption. Adsorption is the separation of a substance from a gaseous medium or solution by means of a surface layer of a liquid or solid. (Figure 2).
Thanks to the porous capillary structure of the adsorbent, it very efficiently draws water vapor out of the air, but if it is saturated with moisture, the efficiency drops drastically.

Figure 2. Scheme of sorption method of air drying.
In order to achieve a continuous process, the adsorbent must be periodically regenerated, i.e. it is necessary to eliminate the accumulated moisture by blowing hot air. In accordance with the above, the change and decrease in relative humidity can be illustrated by means of H-x diagrams (Figure 3):
· air heating
· cooling and then heating the air
· sorption air dehumidification

Figure 3. Changes in the condition of the air in the H-x diagram leading to a decrease of relative humidity.
Sorption method against condensation. If we generally compare two conceptually different, and, in any case, realistic methods, dehumidification by cooling is functional in the case of small changes in moisture content in the air, because the difficulties in operation are necessarily manifested by freezing frost and ice on the heat exchanger – cooler with temperatures below 0°C, as soon as the task of removing a larger amount of moisture occurs.

Figure 4. Comparison of different air drying methods in the H-x diagram,
On the other hand, sorption dehumidifiers function normally in the case of the elimination a large amount of moisture from the air, and they require a smaller amount of air than the condensation method to remove the same amount of moisture.
Real application of different methods in practice. The dehumidifier with integral freon contour works better in high humidity conditions, where there is no risk of ice freezing on the freon evaporator, especially for swimming pools.
Sorption humidifier works well in both dry and humid environments, but is more expensive to invest in and operate than condensation-type air drying in humid environments.

Figure 5. Areas of two methods application depending on the drying air parameters.
Different variants of the air drying sorption method. The RECUSORB principle (Figure 6) implies integrated heat recovery in the part of the sorption rotor, as a result of which the energy costs of rotor regeneration are reduced, and the dried air is drier and cooler compared to other sorption drying methods. It is characteristic for climates with moderately humid climate.
The CONSORB principle (Figure 7) is primarily used in very humid climates, where it shows more significant efficiency compared to RECUSORB.

Figure 6. Schematic overview of the sorption drying method RECUSORB.

Figure 7. Schematic overview of the sorption drying method CONSORB.
Sorption method compared to condensation. The LCC calculation performed in this paper is based on the recommendations of the Eurovent certification system and the provisions of important standards in this area VDI 2067-1 and DIN V 18599-3.
In the HVAC technique, there are rough estimates of the operating costs of air conditioning units (Figure 8), but for accurate conclusions about expected costs it is necessary to calculate the LCC life cycle costs.

Figure 8. The share of various factors in the total cost of the equipment operating.
As a rule, the calculation takes place in accordance with the climatic conditions of the facility on which the equipment is planned to be installed and the period of its operation.
The behaviour of the building in the climatic sense is simulated by different scenarios which primarily depend on the parameters of the outside air. The following influential variables, such as energy prices, investment and maintenance costs, complete the base for the calculation.
Concept of sorption method for air drying. The AHU for process air in hygienic design (Figure 9) is equipped with a mixing section with the aim of recirculating 50% of air from the room, filter section, sorption rotor, water heater, freon evaporator, compressor, fan, silencer and second stage filter. Part of the unit are sections for rotor regeneration using room air, filter, with electric heater and fan.

Figure 9. The drawing of Air Handling Unit for process air treatment.
A ventilation unit for air extraction and recirculation has been designed separately. An obligatory element in this concept is the remote freon condenser, and the correctly chosen rotor is most responsible for the functionality and dehumidification of the air (Figure 10).

Figure 10. Technical characteristics of the sorption rotor.
Tandem compressors ZR94 + ZRD94 (Figure 11), one of which is digital, due to precise automatic regulation, together with the evaporator and remote condenser, cool the heated air after the rotor with a slight deviation from the desired parameters of the incoming air.

Figure 11. Cooling circuit with tandem compressors in the AHU.
Concept of condensation method for air drying. It was designed the two-stage AHU with mixing section, air heater, glycol cooler with the specific temperature regime of propylene glycol −3 / −8°C, electric heater, fan, silencer and a second-stage filter (Figure 12).

Figure 12. Drawing of AHU for air drying by condensation method.
The specificity of this unit is the need for cooling and drying the air to a temperature of 0°C, as a result of which there is the formation of frost and ice on the exchanger, which must be eliminated due to functionality by means of electric heaters built into the fins. This need also requires the use of a non-standard chiller which has the ability to cool a mixture of water and glycol to a regime of −3 / −8°C.
Table 2. Input data for LCC analysis (Location: Moscow, Russian Federation).
Review period | 15 years | |
Period of operation time | 15 years | |
Annual interest rate | 5% | |
Annual service and maintenance costs | 6% | |
Annual system operation time | 8760 hours, without stopping | |
Supply airflow | 10.000 m³/h | |
Exhaust airflow | 10.000 m³/h | |
Room temperature | 22°C | |
Relative humidity all year round no more than | 30% | |
Outdoor air parameters in Moscow | ||
Winter | T = −25°C, φ = 83% | |
Summer | T = 26°C, φ = 55,9% | |
Energy costs in Moscow | ||
Electricity | 0,11 €/kWh | |
Heating | 0,03 €/kWh | |
Cooling | 0,05 €/kWh | |
Emission CO₂ | 0,017 €/kg | |
Price change factors | ||
Investment/service/operation | 3% | |
Energy consumption | 4% | |
A detailed overview of costs for 15 years operation time period is presented in Annex.
The presented LCC analysis compares, from the technical-economic aspect, two realistic methods for dehumidification of air in space, sorption and condensation.
The method for dehumidification with by means of a sorption rotor is characterized by significantly higher investment costs, but during operation it has a distinct advantage in reduced consumption of electricity and cooling energy, to the extent that the investment pays off after 8 months from the start of operation.
The LCC analysis calculation has been done for a pharmaceutical plant in close environment of Moscow, Russia, the main input data were presented in Table 2 and comparative chart for both system on Figure 14.

Figure 13. Components considered in the LCC calculation.

Figure 14. Comparative chart of LCC costs.
[1] BranislavTodorović, Klimatizacija, SMEITS, Beograd, 1998.
[2] DST-SG, catalogues and brochures of sorption rotor producer.
[3] VDI 2067-1, Economic efficiency of building installations. Fundamentals and economic calculation, 2010.
[4] DIN V 18599-3, Energy efficiency of buildings – Energy need for air conditioning, 2007.
[5] Chapter 22 of the ASHRAE Handbook-Fundamentals – Desiccant dehumidification.
[6] Сотников А.Г., Процессы, аппараты и системыкондиционированиявоздуха и вентиляции - Том 1, Sankt-Peterburg 2005.
Annex. Recapitulation table with a detailed presentation of costs.