Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
Energy
labelling enables customers to make informed choices based on the energy
consumption of energy-related products. This entails several benefits: reduces
energy demand and saves customers money on energy bills, contributes to
innovation and investment in energy efficiency, and supports industries which
develop and produce the most energy efficient products.
However, a
lack of ambitious requirements and standardised/reliable data for heating and
cooling technologies will lead to a risk that the cost effective and energy
saving potential will not be fully utilized and that the consumers will lose
their confidence in the energy labelling and other product information
provided by suppliers.
The
technologies considered in this study are: air conditioners, liquid chilling
packages and hydronic heat pumps, rooftop and variable refrigerant flow units.
Comfort air
conditioners (ACs) consist of a reversible heat pump that can be used for both
heating and cooling the air in a room. This type of heating and cooling
technology has gained increasing market penetration in recent years and thus,
it has been included in the ecodesign (2009/125/EC) and
energy labelling (2010/30/EU) European directives (implemented through
regulations No 206/2012 and No 626/2011) to contribute with a large amount of
energy savings in the European Union within the next 10 to 20 years. The
products evaluated in this work have a capacity that varies between 2 kW
and 15 kW [1].
Liquid
chilling packages and hydronic heat pumps (LCP-HP) consist in electrically
driven reversible heat pumps used for heating and refrigeration. Like air
conditioners, LCP- HP units may be air-cooled or liquid cooled, but instead of
heating and/or cooling air, they transfer heat to liquid water. The units
considered in this work have a capacity up to 1500 kW (water-cooled) and
600 kW (air-cooled) [2].
Rooftop
(RT) units consist of a blower, heating or cooling elements, filter racks or
chambers, sound attenuators and dampers. They are used to condition and
circulate air as part of a heating, ventilation and air condition (HVAC)
system. Rooftops are designed for outdoor use, as it names indicates, typically
the roof. The units considered in this work have a rated capacity up to 200 kW
[3]. They can be air-to-air or water-to-air rooftop units.
Finally,
variable flow refrigerant (VFR) units is a more recent HVAC technology (1982).
A typical unit consist of one or several outdoor units – with the compressor
and condenser, several indoor units –evaporator, refrigerant piping running
between the outdoor and indoor units. These types of systems modulate the flow
of refrigerant according to exact demands of one or several areas and are
especially suited for large buildings with several rooms – commercial
buildings, offices, schools, etc. In this study, only single module outdoor
units used for cooling-only, heating-only and reversible units are considered.
They can be air- or water- sourced. The units considered in this work have a
rated capacity between 7.2 and 61.6 kW [4].
To assess
the energy efficiency progress in heating and cooling European market,
statistical analyses were made on reliable performance rating data of an
independent database over a period of three years. The data studied is
third-party certified, i.e. it proceeds from tests run at independent
laboratories. The rating data studied includes:
·
Coefficient
of Performance (COP) and Energy Efficiency Ratio (EER): For all systems
considered in this study the COP – energy efficiency in heating mode – and EER
– energy efficiency in cooling mode – are defined as the ratio between the
thermal energy delivered and electrical power absorbed by the unit at reference
design conditions [1; 2; 3; 4].
·
Seasonal
Coefficient of Performance (SCOP) and Seasonal Energy Efficiency Ratio (SEER):
The calculation of SCOP and SEER is in accordance with EN14511:2013,
EN14825:2013 and the [6].
·
Energy
classes:
o AC: The energy classification for air conditioners is defined in the European Commision Regulation (EU) No 626/2011 supplementing the Directive 2010/30/EU [5]. See Annexes Table 7.
o LCP-HP: The energy classification for LCP-HP is defined in the Eurovent Certita Certification Rating Standard [2].
o RT: The energy classification for RT systems is defined in the Eurovent Certita Certification Rating Standard [3].
Figure 1 and Figure 2 reflect the effects of the entry
into force of the ecodesign regulation requirements illustrated by the
evolution of energy classes (introduced in Jan.2013 for AC units). Non-ducted
AC units are classified with 10 different energy classes, from the best, A+++,
to the worse, G. This sample includes more than 6500 AC units between the years
2014 and 2016. The share of non-ducted
AC units with high energy efficiencies (classes A+, A++ and A+++) is
larger than 50% and has smoothly increased along the years in both heating (Figure 1) and cooling mode (Figure 2). There are no units in the market
labelled with classes lower than D.
The
progress illustrated in Figure 1 and Figure 2 mirrors the positive effects of the
regulations. However, in the recent revision of the European Commission of the
Energy Labelling directive (2010/30/EU) [7] it was identified the need to
update the energy labelling framework to improve its effectiveness. Customers
compare labels across different product groups (for example, between ACs and
dishwashers), and not all have the same number of classes, i.e. some vary from
A to G (7 classes) while others vary from class A+++ to class G (10 classes,
case of AC units). This leads to some confusion making some customers believe
that more efficient products could exist or, in the opposite case, that a class
A product in a product group where classes vary, from A+++ to G, is very
efficient. In the new revision, the Commission considers that the
classification using letters from A to G has shown to be more effective for customers
and intends to uniform this across products groups (except space and water
heaters). For all other products, all class A+++ will be assigned class A,
class A++ will be class B and so forth from Jan. 2019 [8].
Figure 1. Seasonal Cooling Energy Efficiency – seasonal energy efficiency ratio (SEER) transformation of non-ducted AC units between 2014 and 2016.
Figure 2. Seasonal Heating Energy Efficiency – seasonal
coefficient of performance (SCOP) transformation of non-ducted AC units between
2014 and 2016.
Today, the
energy class of AC units is determined through the calculation of the seasonal
energy efficiency ratio (SEER) and seasonal coefficient of performance (SCOP)
of the unit. Compared to the previous requirements, before 2013, based on the
energy efficiency ratio (EER) and the coefficient of performance (COP) a single
standard operation condition, the SCOP and SEER are calculated based on
measurements at six different ambient conditions (known as points A, B, C, D, E
and F). They represent the fluctuating demand in residential buildings.
Additionally, the new method takes into account the residual electric energy
demand during standby and off-mode periods. Altogether, this gives a more
realistic picture of the phase of use of AC for consumers.
The
regulations demand the manufacturers to self-declare the performance data.
These new requirements and its complexity stimulate manufacturers to be more
knowledgeable about their products and discourages free-riders. Yet, empirical
data from the last three years show that not all manufacturers are able to
declare accurate performances (Figure 3). When compared to its performance
data tested in independent labs, the share of non-conform declared ratings was
above 30% and has significantly increased. This mismatch between declared and
tested values will over and above have a negative impact on the confidence of
end-use consumers and investors in this technology and certainly, jeopardize
its potential to reduce energy demand and increase the energy efficiency in
buildings. This emphasizes the importance of third party independent testing
performed by market surveillance authorities and independent certification
organisations. These organisations and their activity ensure the reliability of
values declared and thus, promote energy efficiency and end-user confidence.
Figure 3. Failure rate of tested non-ducted AC units in the period 2014-2016
according to Eurovent Certita Certification testing campaigns.
Since
January 2013, the EU regulation No 206/2012 requires minimum levels of energy
efficiency and sound power for all electric AC units with a rated capacity up
to 12 kW for cooling or heating (if the unit has no cooling function). The
minimum requirements depend on the rated capacity (<6 kW and 6-12 kW)
and, since January 2014, also on the global warming potential (GWP) of the
refrigerant (GWP > 150 or GWP ≤ 150), the working
fluid of the unit.
Figure 4shows the SCOP values of the products analysed in this study. All units
seem to comply with the ecodesign minimum (SCOP ≥ 3.8) [5]. The
units with larger
capacity (>12 kW) have SCOP values less spread than smaller capacities
units. Together with this, it is evident that smaller capacity units can reach
SCOP values much higher (max. = 6.2) than the minimum requirements imposed
today.
Figure 4. SCOP values dispersion for each of
the non-ducted AC unit type according to its rated heating capacity (Ph). See Table 6 in Annexes for unit type.
Nonetheless,
it is should be highlighted that the average SCOP has evolved in a very
conservative way during the last three years. Table 1 outlines the SCOP transformation of
non-ducted AC units between 2014 and 2016. The Split Reversible units (…/S/R)
represent the greatest progress with maximum of 0.96% SCOP increase between
2015 and 2016. Together with the high SCOP values, the facts suggest that a
readjustment of the minimum requirements of the current regulation is
recommended in the future. Rated capacities of AC units with a cooling capacity
larger than 12 kW (AC2 in Figure 4) are plotted to exemplify what can
be expected from larger units. It seems that their seasonal energy efficiency
in heating mode is analogous to AC1 units.
Table 1. Summary of average and std. deviation SCOP values for each non-ducted
AC unit type.
Unit
Type | SCOP Mean (x̄) | SCOP Std. deviation (s) | Δ | Δ | ||||
Year | 2014 | 2015 | 2016 | 2014 | 2015 | 2016 | ||
AC1/A/M/R | 3.96 | 3.97 | 4.00 | 0.24 | 0.22 | 0.23 | +0.25 | +0.76 |
AC1/A/S/R | 4.04 | 4.06 | 4.10 | 0.30 | 0.32 | 0.32 | +0.46 | +0.96 |
AC2/A/S/R | – | – | 4.01 | – | – | 0.01 | – | – |
Figure 5 shows the SEER values of the
products analysed in this study. As it happens for SCOP, the larger
capacity (>12 kW) units have SCOP values less spread than units with
smaller capacities.
Figure 5. SEER values dispersion for each of the non-ducted AC unit type
according to its rated cooling capacity (Pc). See Table 6 in Annexes for unit type.
Table 2 outlines the SEER transformation of
non-ducted AC units between 2014 and 2016. The SEER has evolved in an
indisputable way for both split (…/S/R) and multisplit reversible (…/M/R)
units. Given the existence of high SEER values, the question of the
suitableness of the minimum requirements pops-up once more. In distinction to
reversible units (…/R), the only cooling mode (…/C) units exhibit a
deterioration of the seasonal energy efficiency ratio. Some of only cooling
units have tested rated capacities below the EU minimum requirements
(SEER≥4.3) [5]. This might be caused by the decreasing interest in units
that only deliver cooling in buildings applications and therefore,
manufacturers abandon their development.
Table 2. Summary of average and std. deviation SEER values for each non-ducted
AC unit type.
Unit
Type | SCOP Mean(x̄) | SCOP Std. deviation (s) | Δ | Δ | ||||
Year | 2014 | 2015 | 2016 | 2014 | 2015 | 2016 | ||
AC1/A/M/C | – | 6.36 | 6.27 | – | 0.66 | 0.41 | – | -1.42 |
AC1/A/M/R | 5.85 | 5.88 | 6.18 | 0.51 | 0.51 | 0.86 | +0.51 | +5.10 |
AC1/A/S/C | 5.43 | 5.19 | 5.10 | 0.95 | 1.20 | 1.35 | -4.42 | -1.73 |
AC1/A/S/R | 6.08 | 6.12 | 6.24 | 0.87 | 0.90 | 0.91 | +0.66 | +1.96 |
AC2/A/S/R | – | – | 5.92 | – | – | 0.24 | – | – |
Finally,
under the ecodesign requirements a bonus is proposed to guide the market in the
direction of the use of refrigerants with low global warming potential (GWP)
falls short of expectation. The bonus consists in imposing lower minimum energy
efficiency for AC units using low-GWP refrigerants (GWP < 150).
The introduction of low GWP refrigerants represents certain technological
challenges with respect to energy efficiency of AC units due to thermodynamic
characteristics of new refrigerants but great benefits in terms of reduction of
global warming gas emissions, in the case of leakage. According to this study (Figure 6) among over 6500 non-ducted AC
products, low-GWP are not present in the market. The R410A refrigerant (GWP = 2088)
is by far the dominating refrigerant used in the market of AC units in Europe
while R32 (GWP = 675) has been gaining moderate importance. Perhaps,
more stringent ecodesign minimum requirements for AC units using conventional
refrigerants could also steer the market for the use of low GWP refrigerants.
Figure 6. Evolution of refrigerants used in non-ducted AC units.
The COP of
LCP-HP units in low temperature heating mode sorted by unit type are plotted
against its capacity in Figure 7. Air source packaged reversible
units (LCP35/A/P/R) tend to perform worse than any type of unit. Otherwise, the
COP values of LCP-HP units seem to exhibit no significant statistical dependence
between energy efficiency (COP) and its capacity.
The maximum
average COP among LCP-HP units in low temperature (35°C) heating mode was 5.59
– in water based packaged (LCP-HP35/W/P/C) units, while the minimum was 3.89 in
air based packaged reversible units (LCP-HP35/A/P/R). See Table 3.
Table 3. Summary of average and std. deviation COP and EER values for each
LCP-HP unit type.
Unit Type | COP | COP Std. | EER | EER Std. |
LCP35/A/P/R | 3.89 | 0.28 | 3.43 | 0.42 |
LCP35/A/S/R | 4.34 | 0.31 | 3.38 | 0.33 |
LCP35/W/P/C | 5.43 | 0.11 | 3.58 | 0.47 |
LCP35/W/P/R | 5.32 | 0.35 | 6.80 | 0.80 |
LCP-HP35/A/P/H | 4.21 | 0.16 | 5.64 | 0.48 |
LCP-HP35/W/P/H | 5.59 | 0.43 | - | - |
LCP55/A/P/R | 2.51 | 0.20 | - | - |
LCP55/A/S/R | 2.83 | 0.21 | - | - |
LCP55/W/P/C | 3.41 | 0 | - | - |
LCP55/W/P/R | 3.33 | 0.18 | - | - |
LCP-HP55/A/P/H | 3.2 | 0.37 | - | - |
LCP-HP55/W/P/H | 3.69 | 0.15 | - | - |
In high
temperature (55°C), as shown in Figure 8, the maximum average COP was
reached water based packaged LCP-HP units (LCP-HP55/W/P/H), 3.69 and the
minimum average 2.51 with air based packaged reversible units (LCP55/A/P/R). The
different types of LCP-HP units show to be clustered in different COP value
levels. This indicates that, particularly in high temperature heating mode, the
different types of units should be considered independently with regards to
minimum energy performance requirements.
Figure 7. COP values dispersion of the LCP-HP type low heating mode (35°C) units
according to its rated heating capacity (Ph). See Table 8 in Annexes for unit type.
Figure 8. COP values dispersion of LCP-HP unit in high heating mode (55°C) units
according to its rated heating capacity (Ph). See Table 8 in Annexes for unit type.
Figure 9 shows the EER values of LCP-HP units during the period 2014–2016. The maximum average EER among LCP-HP units in low temperature heating mode was 6.80 – in the case of water based packaged reversible units (LCP35/W/P/R), while the minimum was 3.38 in air based split reversible units (LCP-HP35/A/S/R). See Table 3.
Figure 9. EER values dispersion LCP-HP units according to its rated cooling
capacity (Pc). See Table 8 in Annexes for unit type.
LCP-HP
units are not yet considered under the energy labelling regulation. Thus, no
study on the seasonal energy efficiency (SCOP and SEER). However, the Eurovent
Certita Certification program [2], defines energy classes on the basis of the
COP and EER values [2]. Results of the market transformation between 2014 and
2016 can be found in the following couple of figures (Figure 10 and Figure 11). These results echo the stagnation
of the LCP-HP market. In the last three years, there are no signs of
significant positive evolution with respect to COP and EER values.
Figure 10. Coefficient of performance (COP) –transformation of LCP-HP between
2014 and 2016.
Figure 11. Energy Efficiency Ratio (EER) –transformation of LCP-HP between 2014
and 2016.
Figure 12 shows that RT present no clear
dependence between COP and unit rated capacity. In addition, the latter figure
reveals two clear clusters corresponding to water-based units with higher COP
values than air-based units.
Figure 12. COP values dispersion for each of the RT unit type in heating mode
according to its rated heating capacity. See Table 9 in Annexes for unit type.
Figure 13 shows that RT present no clear
dependence between COP and the rated capacity of the unit in cooling mode,
either. In addition, the latter figure reveals two clear clusters corresponding
to water-based units with higher EER values than air-based units, both cooling
only mode and reversible type.
Figure 13. EER values dispersion for each of the RT unit type in cooling mode
according to its rated cooling capacity (Pc). See Table 9 in Annexes for unit type.
Table 4 sums up average COP and EER values found for three different types of RT units (see types in Table 9). The water based packaged reversible systems (RT/W/P/R) present COP values 1.3 times higher than air heated units (RT/A/P/C and RT/A/P/R) in heating mode. The standard deviation values indicate a slight potential for positive effects to incite for energy performance improvement for heating applications.
The performance of water cooled RT units in cooling mode is also up to 1.4 times higher than air cooled packaged reversible units (RT/A/P/R). The standard deviation values indicate a slight potential for positive effects to incite for energy performance improvement in cooling mode.
Table 4. Summary of average and std. deviation COP and EER values for each RT
unit type.
COP Mean | COP Std. deviation | EER Mean | EER Std. deviation | |
RT/A/P/C | – | – | 2.87 | 0.23 |
RT/A/P/R | 3.24 | 0.28 | 2.80 | 0.28 |
RT/W/P/R | 4.31 | 0.19 | 3.94 | 0.30 |
As LCP-HP
units, RT are not considered under the energy labelling regulation. Thus, no
study on the seasonal energy efficiency (SCOP and SEER). However, the Eurovent
Certita Certification program [3], defines energy classes on the basis of the COP
and EER values. Results of the market transformation between 2014 and 2016 can
be found in the following couple of figures (Figure 14 and Figure 15) for air and water based RT
systems. These results echo the stagnation of the RT market. Except with
respect to water-based systems, in the last three years, there are signs of
positive evolution on EER values. From 2014 to 2016, 19% passed from lower
energy classes to class A.
Figure 14. Coefficient of performance (COP) –transformation of RT for air and
water based units between 2014 and 2016.
Figure 15. Energy Efficiency Ratio (EER) –transformation of RT for air and water
based units between 2014 and 2016.
Figure 16 shows the COP values of VRF units
in heating mode sorted by unit type against its capacity. It is shown that water-
and air-sourced systems seem to have comparable performances. The evident
vertical lines corresponding to different heating capacities are defined by the
market.
Figure 16. COP values dispersion for each of the VRF unit type in heating mode
according to its rated heating capacity (Ph) See Table 10 in Annexes for unit type.
Figure 17 shows the EER values of VRF units
in cooling mode sorted by unit type against its capacity. Water-sourced units
present higher energy efficiency that air-sourced in cooling mode, contrasting
with what could be seen in heating mode, where these two types of units seem to
show comparable performances (Figure 16). This could be a result of
free-cooling. However, it is ambitious to conclude that this is a trend as
there are only three samples of water-sourced units available in this dataset.
Figure 17. EER values dispersion for each of the VRF unit type in heating mode
according to its rated heating capacity (Pc). See Table 10 in Annexes for unit type.
The maximum average COP among VRF units in heating mode was 4.53 –water based units (VRF/W/R), while the minimum was 4.22 in air based units (VRF/A/R). Table 5 summarizes the mean and standard deviation of COP and EER for each unit type in the last three years period (2014-2016).
Air based types present a larger standard deviation than water based. Yet, this might be due to the smaller numbers of water based samples. Thus, the potential for policy effect should be the same for air- and water- sources VRF units.
Table 5. Summary of average and std. deviation COP and EER values for each VRF
unit type.
Unit
Type | COP Mean | COP Std. | EER Mean | EER Std. |
VRF/A/R | 4.22 | 0.48 | 3.77 | 0.47 |
VRF/W/R | 4.53 | 0.10 | 5.52 | 0.28 |
VRF units
are not considered under the energy labelling regulation or any certification
program. Thus, no study on the seasonal energy efficiency (SCOP and SEER) or
nominal conditions efficiency (COP and EER) were performed.
This study
is based on accurate data of the performance of heating and cooling
technologies tested in independent laboratories. The technologies considered in
this study are: air conditioners, liquid chilling packages and hydronic heat
pumps, rooftop and variable refrigerant flow units.
The statistical
analyses performed and its results give an outlook of the technological
progress in European heating and cooling market during the period of 2014 and
2016. The facts presented prove the positive effect of energy labelling
implementation on energy efficiency improvement and confirm the importance of
standardised/legit data for heating and cooling technologies. Furthermore, the
facts strongly recommend the revision of the ecodesign requirements on the
minimum energy efficiency in the future revision of the regulation in the
matter of AC units. A review of the regulation No 206/2012 supplementing the
Directive 2010/30/EU with regard to ecodesign requirements of AC products is
planned. The Commission shall review the regulation No 206/2012 no later than 5
years from the date of entry into force.
With
respect to the other technologies (liquid chilling packages and hydronic heat
pumps, rooftops and variable flow refrigerant) studied in this work and its
future application with regards to energy efficiency improvement, it is
suggested that these systems should be discriminated by water and air-based
units when defining minimum requirements. In addition, packaged and split
systems also present distinguished performances.
In this
study, the AC units are classified according to their capacity:
·
AC1:
Comfort Air Conditioners and Heat Pumps rated up to 12 kW;
·
AC2:
Comfort Air Conditioners rated from over 12 kW up to but not including 45 kW
cooling capacity.
Furthermore, they are also classified according to its heat source, system and mounting types. AC units reject heat from the room to water (water cooled unit) or air (air/air units) in cooling mode and, if reversible, they can also absorb heat from the water or air to the room in heating mode. Table 6condenses the AC units classification used in this study.
Table 6. Non-ducted air conditioners (AC) classification.
Programme | Code | Heat rejection | Code | System | Code | Operation | Code | Mounting | Code |
Comfort Air
Conditioners up to 12 kW | AC1 | Air cooled | A | Split | S | Cooling only | C | High wall | W |
Floor mounted | L | ||||||||
Multisplit | M | Cassette | C | ||||||
Comfort Air
Conditioners from 12 up to 45 kW | AC2 | Water cooled | W | Reverse cycle | R | Ceiling suspended | S | ||
Packaged | P | Built-in horizontal | B | ||||||
Built-in vertical | V | ||||||||
Window | Wi |
Table 7 Energy Classification for Air
Conditioners except double ducts and single ducts.
Energy Efficiency Class | SEER | SCOP |
A+++ | SEER ≥ 8.50 | SCOP ≥ 5.10 |
A++ | 6.10 ≤ SEER ≤ 8.50 | 4.60 ≤ SCOP ≤ 5.10 |
A+ | 5.60 ≤ SEER ≤ 6.10 | 4.00 ≤ SCOP ≤ 4.60 |
A | 5.10 ≤ SEER ≤ 5.60 | 3.40 ≤ SCOP ≤ 4.00 |
B | 4.60 ≤ SEER ≤ 5.10 | 3.10 ≤ SCOP ≤ 3.40 |
C | 4.10 ≤ SEER ≤ 4.60 | 2.80 ≤ SCOP ≤ 3.10 |
D | 3.60 ≤ SEER ≤ 4.10 | 2.50 ≤ SCOP ≤ 2.80 |
E | 3.10 ≤ SEER ≤ 3.60 | 2.20 ≤ SCOP ≤ 2.50 |
F | 2.60 ≤ SEER ≤ 3.10 | 1.90 ≤ SCOP ≤ 2.20 |
G | SEER < 2.60 | SCOP < 1.90 |
The table below sums all the classes of LCP-HP units studied as classified by ECC [2].
Table 8. Classes of LCP-HP units.
Programme | Code | Heat rejection | Code | System | Code | Operation | Code | Duct | Code | Compressor | Code |
Liquid Chilling Packages | LCP | Air cooled | A | Packaged | P | Cooling only | C | Ducted | D | Centrifucal | C |
Water cooled | W | Split | S | Reverse cycle | R | Non Ducted | N | Other | O |
The table
below sums all the classes of RT units studied as classified by ECC [3].
Table 9. Classes of RT units.
Programme | Code | Heat rejection | Code | System | Code | Operation | Code |
Rooftop | RT | Air | A | Packaged | P | Cooling only | C |
Water | W | Reversible cycle | R |
The
following table below sums all the classes of VRF units studied as classified
by ECC [4].
Table 10. Classes of VRF units.
Programme | Code | Heat rejection | Code | Operation | Code |
Variable Refrigerant Flow | VRF | Air | A | Cooling only | C |
Water | W | Reversible cycle | R |
[1] ECC, Eurovent Certita Certification. RS 6/C/011-2016. [Online] [Cited: 07 10 2017.] http://www.eurovent-certification.com/en/Certification_Programmes/Programme_Descriptions.php?lg=en&rub=03&srub=01&select_prog=AC.
[2] ECC, Eurovent Certitita
Certification. RS
6/C/003-2017. [Online] [Cited: 07 10 2017.] http://www.eurovent-certification.com/en/Certification_Programmes/Programme_Descriptions.php?lg=en&rub=03&srub=01&select_prog=LCP-HP.
[3] ECC, Eurovent Certita
Certification. RS
6/C/007-2017. [En ligne] [Citation:
10 08 2017.] http://www.eurovent-certification.com/en/Certification_Programmes/Programme_Descriptions.php?n&rub=03&srub=01&select_prog=RT.
[4] RS 6/C/008-2016. [En ligne] [Citation: 10 08 2017.] http://www.eurovent-certification.com/en/Certification_Programmes/Programme_Descriptions.php?n&rub=03&srub=01&select_prog=VRF.
[5] Commission Delegated Regulation (EU) No 626/2011 of 4 May 2011. Commission, European. 2011. http://eur-lex.europa.eu/legal-content/en/ALL/?uri=CELEX:32011R0626.
[6] Commission Regulation (EU) No 206/2012. Commission,
European. 2012. http://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX%3A32012R0206.
[7] Energy Labelling Directive 2010/30/EU. Commission,
European. 2010. http://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX:32010L0030.
[8] Regulation (EU) 2017/1369. Commission,
European. 2017. http://eur-lex.europa.eu/eli/reg/2017/1369/oj.
[9] ECC, Eurovent Certitita Certification. [En ligne] [Citation: 07 08 2017.] http://www.eurovent-certification.com/en/Certification_Programmes/Programme_Descriptions.php?lg=en&rub=03&srub=01&select_prog=LCP-HP.
[10] ECC, Eurovent Certita Certification. [En ligne] [Citation: 07 08 2017.] http://www.eurovent-certification.com/en/Certification_Programmes/Programme_Descriptions.php?n&rub=03&srub=01&select_prog=RT.
[11] [En ligne] [Citation: 07 08 2017.] http://www.eurovent-certification.com/en/Certification_Programmes/Programme_Descriptions.php?n&rub=03&srub=01&select_prog=VRF.
Follow us on social media accounts to stay up to date with REHVA actualities
0