Anders NielsenApplication Manager, Grundfos A/S, anders@grundfos.com
| Charles W. HansenPlant Manager, Bjerringbro District Heating, cwh@bjerringbro-varme.dk |

The Energy
Central is the result of a cooperation between Grundfos and the local district
heating company. [Photo: Anders Nielsen]
Earlier
this year, Grundfos headquarters and the local district heating company
inaugurated a joint system to store the surplus heat from the Grundfos factories
in obsolete groundwater boreholes, and use it in the district heating network
when needed.
The synergy
between the cooling demand in Grundfos' production plants and the heat demand
of Bjerringbro district heating company has virtually eliminated energy waste.
The remarkable reduction of energy consumption, CO2 emission and
operational costs now benefit both companies and the district heating customers
in the area.
As part of
the agreement, a new energy central with state-of-the-art cooling compressors
and heating pumps has been established.
The new
setup is based on three elements:
1. Exploitation of surplus heat from cooling in
the factories.
2. Indirect storage of heat in an underground
aquifer.
3. Heat pumps supply additional heat, when
required
Using small, individual refrigeration
compressors to cool down machines in production facilities is a very
inefficient, but nevertheless very common method. To make matters worse, the heat energy developed
in the process is virtually always wasted.
With the
new shared Energy Central, Grundfos productions facilities are cooled by cold
water from the District heating network. And when the cold water needs to be
colder, three large cooling compressors with a total cooling capacity of 2.85
MW and thermal power of 3.65 MW handle the job from a central facility.

Cooling
compressors.
During the
heating season, the cold water used to cool the machines at Grundfos, becomes
hot in the process, and along with the excess heat from the cooling compressors
in the energy central, the heat is recycled and sent directly to the district
heating network.
During summer, when the heating demand is minimal, the surplus heat is stored in underground energy storage - a so-called ATES-stock (Aquifer Thermal Energy Storage) located 80 metres underground.
During the four summer months, a total cooling output of 3 500 MWh is accumulated. And more than 80% of the stored energy during summer will be supplied to the district heating network during the heating season. In fact, the energy central covers more than 15% of the town’s annual heat requirement, of which 1/3 comes from the hot water storage.
| ||||||||||||||||||
| ||||||||||||||||||
Flow chart of Bjerringbro district heating and cooling network which supplies Grundfos production plants with ground water thermal storage, district heating network and heat pumps (in the energy central in the figure) for additional heating and cooling (compressors in the figure next page). The water used for cooling in the Grundfos factories is 6-12°C and 18°C when returned to the central. The temperature of the water is raised to 46/67°C with heat pumps and supplied to the district heating network. COP for heat pumps for heating is 4.60. |
Pressure
drops across valves in a heating system are costly and waste energy. This
system however, is frequency controlled and designed for completely open
valves. Accordingly, all thermal adjustments are carried out, by speed
controlled pumps. As a result, pressure
drop across the valves have been completely eliminated and replaced by massive
energy savings.
The ATES system will reduce Grundfos’ energy consumption for cooling by up to 90%. Combined with significantly reduced heating costs, the result is cheaper heating for the citizens and massive energy savings for Grundfos and the district heating plant.
In fact, the
carbon emission will be reduced by some 3,700 tonnes a year, equivalent to 1.5
tonnes per household connected to the heating plant.
In total, Grundfos and Bjerringbro district heating company have invested 4.5 mill. euro in the new system. Without this joint investment, two separate systems would have been the solution. Compared to these reference systems, annual savings of 400 000 euro was initially expected, but because the system seems to be more efficient than estimated, the payback time will most likely be shorter than the projected 11.25 years.
Economics of the investment | |
Annual cooling output of groundwater cooling – 4 summer months Groundwater cooling covers cooling of all factories. | 3 500 MWh |
Annual heat production of the cooling machines | 13 400 MWh |
Annual cooling output of cooling machines – 8 months | 10 500 MWh |
Total investment | 4.5 mill. Euro |
Estimated annual savings | 400 000 Euro |
Total annual reduction in carbon emissions | 3 700 ton |
With the
new setup Bjerringbro district heating company seizes the opportunity to store
energy and become less dependent on natural gas. As a result, the plant will emit
less C02 and be able to offer more sustainable heating supply even lower
price.
Many European countries aim to be free from the use of fossil fuels in the near future, and this type of system is a big step in that direction. The system is able to store solar heat and thus, in principle, low fossil heat as it runs only on electricity. In the future, this may be supplied by wind turbines or any other renewable source.
According to Lars Hummelmose of the Danish
Board of District Heating, this solution will hopefully inspire others to explore local environmental friendly
energy opportunities. He sees many elements of the project that can be used
globally, especially in countries that already have district heating, but also
in countries that are facing a transition away from nuclear power.