Philomena M. Bluyssen |
Prof.dr., Chair Indoor environment, Faculty of Architecture and the Built Environment, Delft University of Technology, Delft, The Netherlandsp.m.bluyssen@tudelft.nl |
Even though the guidelines for indoor
environmental quality are met, problems can occur. To cope with this descrepancy, recently, a new research model was introduced
to determine requirements (to prevent negative effects) and preferences (to
stimulate positive experiences) for (re)designing healthy and comfortable
buildings [1]. To fill and validate this model for children of primary
schools, a field study and a series of lab studies were held. The field study
was reported in Part 1 [2], while the SenseLab
studies with 335 children from 7 primary schools, are reported here. Primary
school children from previous studied schools were invited to take part in a
series of tests in a semi-laboratory environment (the SenseLab),
to investigate preferences, needs and responses to single components (sound,
thermal, light and air) and interactions of different environmental
configurations more in depth.
The SenseLab comprises of four test chambers (one for each IEQ factor: air, light, acoustics and thermal aspects) and the Experience room (a room for integral perception) [3]. 335 children from seven different primary schools visited the SenseLab at 10 days in the spring of 2018. Maximum three groups per day were formed: group 1 started in the Experience room (maximum 16 children), group 2 in the test chambers (maximum four children per test chamber) and group 3 in the Science Centre where the SenseLab is located. After 35 minutes, group 1 went to the test chambers, group 2 to the Science Centre and group 3 to the Experience room. In the Experience room an exposure study [4]; and a workshop [5] was held, while in each of the test chambers, a test was performed that relates respectively to thermal [6], air (smell) [7], lighting [8] and acoustical quality [9].
To test the main, cross-modal and interaction effects of 36 different combinations of environmental conditions on the evaluation of temperature, noise, light and smell by the children [4], a four-way factorial design (Figure 1 shows the combination ‘All acoustical panel’s and with ‘soft light on’) was applied:
· With ‘all’ versus ‘fewer’ acoustical panels: creating a different interior, view outdoors and acoustical quality.
· Two ventilation principles: mixing and displacement ventilation with a ventilation rate of 600 m³/h to provide 30–40 m³/h per person at 21 degrees Celsius.
· Three types of led-lighting: direct, indirect and soft light (setting 100%).
· Three types of background sound: no sound, traffic and children talking, both at 60 dB(A).
The results showed a clear influence of ‘fewer’ acoustical panels on children’s’ evaluation of smell, draught and light. More acoustical panels had a positive effect on the children’s assessment of sound. Sound type, especially ‘children talking’, affected the assessment of both sound and smell.

Figure 1. Set-up in Experience room (with acoustical panels and with soft light on).
To conceptualize design solutions by primary school children to solve IEQ-problems in their classrooms, children participated in a workshop, comprising of two parts [5]. In Part 1, the children were asked to choose an IEQ-problem in their own classroom that they are bothered with, while in Part 2, they were asked to imagine they are an inventor or scientist in 2040 with all resources available and to make a design for the future. Noise-related problems were most frequently reported (58%), followed by temperature (53%), air (22%), and light (16%). Girls reported more problems than boys. 47% of the children proposed solutions related to more than one IEQ-problem. Solutions ranged from existing solutions, such as headphones to protect against noise to far-fetched solutions for example send noisy children away by means of a rocket [5].
A three-way factorial randomized design was used to test the effect of different colours of walls and floor on the thermal comfort and draught feeling in a winter situation (sunlight coming in: heat) and in a summer situation (opening window: draught) [6]. The different classroom situations (colours of walls: red, blue or white; and floor: green, grey or blue) (combination white walls and blue floor is shown in Figure 2), were created with Virtual Reality in combination with a construction lamp (simulating the heat of the sun) and a fan (simulating the draught of fresh air). A statistical relevant relationship between feeling of draught and feeling of temperature was found, as well as a significant difference in temperature feeling for different floor colours when the wall colour was red in the winter situation.

Figure 2. Virtual classroom with blue flooring and white walls.
The aim was to expose children to different sources of smell (container 1: perfume; container 2: mint leaves; container 3: carpet/MDF/vinyl; container 4: crayons; in Figure 3), and to evaluate and identify those sources at individual level with their noses [7]. The possible effect of plants on the reduction and/or production of smells was tested in the CLIMPAQ (number 5 in Figure 3). Children found the smell in general more acceptable, when they recognized the smell. In general, children did not like the smell of the building/furnishing materials and in most cases they could not identify the source of smell. The effect of (passive) plants on the perception of smells showed no effect.

Figure 3. Pictures of air test chamber set-up.
Children assessed six school desks table tops (brown, yellow and grey wood and normal, matt and reflective white) (Figure 4), under three different light conditions: energizing (650 lux; 12000 K), calming (300 lux; 2900 K), and focusing (1000 lux; 6500 K) [8]; using a two-way randomized design. For all surfaces, the calming light was perceived as the worst and the energizing light as the best (except for the brown wood surface). For the wooden-like surfaces these differences were statistically significant. The children preferred the brown wood under focusing light the best and the brown wood under calming light the worst. For energizing light, grey wood scored the best, while for focusing light, brown wood.
a |
|
b |
|
Figure 4. a. Set-up light experiment b. Six
types of surfaces: from top left: brown wood, white matt, yellow wood, normal white,
reflective white, grey wood). | |
The effect of reverberation time (RT) on
children’s cognitive performance (phonological processing), noise evaluation
and emotional attitude was studied [9]. Two series of listening tests and
evaluations were performed in chamber A (untreated: RT=0.33 seconds) and
chamber B (acoustically treated: RT=0.07 seconds) respectively (see Figure 5),
while at the same time one of seven background sounds (45 dB or 60 dB
traffic noise, 45 dB or 60 dB children talking, 45 dB or 60 dB
music, or no sound) were randomly played. The positive effect of the acoustical
treatment was demonstrated by the statistically significant difference of children’s
sound perceptions between the acoustically treated chamber and the untreated
chamber. However, especially with the ‘children’s talk’ as the background
sound, overtreatment seemed to have adverse effects on children’s performance.
Children preferred the
acoustically treated environmentwhen there was a background
sound.

Figure 5. Treated and untreated chamber.
From the exposure studies and the workshop held in the Experience room, the following can be said:
· Interaction effects of different IEQ-factors seem to take place at human level.
· Sound type, especially ‘children talking’ affected the assessment of both sound and smell, indicating that children are perhaps pre-conditioned in their response by hearing children talk.
· Children were very able to provide problems and solutions for IEQ-problems at different levels (building, classroom, desk, child etc.).
· Girls reported more problems than boys, which is possibly related to a better recollection of negative feelings towards those problems in their classrooms.
The tests in the different test chambers (thermal, air, light and sound) showed that:
· When the wall colour was red in the winter situation, a significant difference in temperature feeling for different floor colours was found.
· The smell was in general assessed more acceptable, when the children recognized the smell.
· Different surfaces most likely require different types of lighting, and vice versa.
· When there was a background sound, the acoustically (over)treated environment was preferred by the children.
Both the field (reported in [2]) and the SenseLab studies with the primary school children were an attempt to fill and validate the newly introduced research model [1]. The outcome of both studies confirmed the need for this model, and the need for more studies to determine requirements (to prevent negative effects) and preferences (to stimulate positive experiences) per scenario (e.g. schools, homes, offices) and situation (for example traditional and non-traditional). Interactions at environment and human level need to be explored, as well as patterns of stressors for different profiles of occupants.
This study was sponsored by the fellowship
of Philomena Bluyssen provided by the Delft
University of Technology under the chair of Indoor Environment. Dadi Zhang, Marco Ortiz, Stanley Kurvers,
Annemarie Eijkelenboom, Arno Freeke,
Arend-Jan Krooneman, and
Tatiana Armijos Moya arethanked
for their contribution to the lab studies.
[1] Bluyssen PM (2019) Towards an integrated analysis of the indoor environmental factors and its effects on occupants Intell. Build. Int. doi.org/1080/17508975.2019.1599318.
[2] Bluyssen PM, (2020) Understanding the indoor environment and its effects, Part 1: Field study of 21 primary schools, REHVA Journal 2020-02.
[3] Bluyssen PM, van Zeist F, Kurvers
S, Tenpierik M, Pont S, Wolters B, van Hulst L, Meertins D (2018) The creation of Senselab:
A laboratory for testing and experiencing single and combinations of indoor
environmental conditions Intell. Build. Int. 10(1) 5-18.
[4] Bluyssen PM, Zhang D, Kim DH, Eijkelenboom A, Ortiz M (2019) First SenseLab studies with primary school children: exposure to different environmental configurations in the Experience room, Intelligent Buildings International, DOI:10.1080/17508975.2019.1661220.
[5] Bluyssen PM, Kim DH, Eijkelenboom
A., Ortiz M. (2019) Workshop with 335 primary school
children in The Netherlands: What is needed to improve the IEQ in their
classrooms? Intelligent Buildings International, DOI:
10.1080/17508975.2019.1682493.
[6] Bluyssen PM, Zhang D, Krooneman A-J, Freeke A. (2019) The effect of wall and floor colouring on temperature and draught feeling of primary school children, E3S Web Conf., 111 (2019) 02032, CLIMA2019, May 25-29 2019, Bucharest, Romania.
[7] Armijos Moya T and Bluyssen PM (2019) Appraisal and identification of different sources of smell by primary school children in the air quality test chamber of the SenseLab, Intelligent Buildings International, DOI: 10.1080/17508975.2019.1682493.
[8] Ortiz MA, Zhang D, Bluyssen
PM. (2019) Table top surface preference of school
children under different lighting conditions tested in the SenseLab,
E3S Web
Conf., 111 (2019) 02040, CLIMA 2019, May 25-29 2019, Bucharest, Romania.
[9] Zhang D, Tenpierik MJ, Bluyssen PM (2019) The effect of acoustical treatment on primary school children’s performance, sound perception, and influence assessment. E3S Web Conf., 111 (2019) 02046, CLIMA 2019, May 25-29 2019, Bucharest, Romania.