Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
This
article was first published in IKZplus IKZ-Klima
3/2019 in Germany.
Thomas HartmannProf. Dr.-Ing., ITG Dresden Institute for
Building Systems Engineering – Research and Application, Dresden, Germanye-mail hartmann@itg-dresden.de | Bernd KleinDipl.-Ing., University of Stuttgart, IGE Prüfstelle HLK, Testing Centre at the Institute of
Building Energy, Stuttgart, Germanye-mail bernd.klein@hlk-stuttgart.de | Christine KnausDipl.-Ing., ITG Dresden Institute for Building
Systems Engineering – Research and Application, Dresden, Germanye-mail knaus@itg-dresden.de |
Paul MathisDipl. Ing., RWTH Aachen University, E.ON Energy Research Center, Institute for Energy
Efficient Buildings and Indoor Climate, Aachen, Germanye-mail pmathis@eonerc.rwth-aachen.de | Dirk MüllerProf. Dr.-Ing., RWTH Aachen University, E.ON Energy Research Center, Institute for Energy
Efficient Buildings and Indoor Climate, Aachen, Germanye-mail dmueller@eonerc.rwth-aachen.de | Tim RöderM. Sc., RWTH Aachen University, E.ON Energy Research Center, Institute for Energy
Efficient Buildings and Indoor Climate, Aachen, Germanye-mail troeder@eonerc.rwth-aachen.de |
Mechanical
ventilation is considered to play an important role in achieving the
energy-saving targets for new construction and refurbishment of existing
residential buildings, particularly in view of the possibilities for heat
recovery and demand-based operation. In addition to the well-known ventilation
units with continuous volume flow, decentralized alternating systems are
increasingly being offered on the market, which are often also referred to as
push-pull units. For heat recovery, heat storages are used with air passing them
unsteadily in alternating manner (Figure 1).
Figure 1.
Functional principle of decentralized alternating ventilation units.
In the
extract air cycle, a storage mass is charged with the energy of the warm
internal air. In the following supply air cycle, this energy is released again
into the inflowing external air. Due to the necessary flow reverse, axial fans
are typically used in these units. In order to achieve balanced air flows in
relation to the room, at least two air flows are necessary, which work
alternately in opposite directions. The two air flows can either be integrated
in one casing (1 compact unit) or realized by two separate units which are
coupled on the control side (2 single devices). In the second case, the devices
can also be placed in different rooms.
In the case
of alternating devices, there were still uncertainties as to how this concept
should be evaluated in comparison to continuously operating devices due to a
lack of science-based results. This applies to aspects such as ventilation
efficiency, wind pressure susceptibility and the determination of energy
parameters. These aspects were investigated in the publicly funded project “EwWalt – EnergetischeBewertungdezentralerEinrichtungenfür die kontrollierteWohnraumlüftungmitalternierenderBetriebsweise” (Energetic assessment of decentralized
facilities for controlled ventilation with alternating operation). Under the
leadership of RWTH Aachen University and with the project partners HLK Stuttgart
and ITG Dresden, simulation investigations were carried out about indoor air
flow effects, test methods for determining the characteristic values for the
energetic evaluation were further developed and proposals for implementation in
the standards were formulated.
CFD studies (Computational Fluid Dynamics) were carried out within the EwWalt project to compare the room air flows from the
ventilation side, which are caused by decentralized alternating or continuous
devices. With these calculations, it is possible to forecast the air flows that
occur and, for example, to evaluate how long the air will stay in the building.
These simulation methods were used in the EwWalt
project to analyse the air exchange efficiency for all rooms in two different
residential constellations (apartment & single-family house, see Figure 2). A small
value for the air exchange efficiency, for example, indicates existing short-circuit
flows.
Figure 2.
Floor plan and exemplary device constellation of the examined apartment.
In order to achieve a broad informative value of the results, several
parameter variations were carried out. On the one hand, the local position of
the ventilation units in the living area was varied; on the other hand, the
ventilation volume flows for partial load behaviour were reduced. It was also
investigated to what extent wind pressure on the building facade or an active
exhaust air system in the building influences the operation of the ventilation
units.
Since many different aspects like ventilation openings inside the building
and wind pressure effect the volume flow rates which can be delivered by the
ventilation devices, the so-called imbalance first had to be evaluated. For
this purpose, the examined buildings were conceived as a duct network in a
second simulation study, in which all ventilation components were modelled as
flow resistances. This pressure-volume flow model calculates the final volume
flows at all ventilation units, which are caused by disturbances such as wind
pressure and ventilation system for bathrooms without windows. It was developed
within the Modelica modelling language and coupled
with the CFD model for the interior flow (Figure 3). The values for the
effectively conveyed volume flows from the duct network simulation could thus
be used as boundary conditions in the flow simulation.
Figure 3. Interface between pressure-volume flow
simulation and flow simulation.
The results coming from the duct network simulation showed that, for
example, if the ventilation units were placed unfavourably across corners,
relatively large pressure differences would be present at the ventilation
units. The axial fans installed primarily in alternating ventilation units have
flat pressure-volume flow characteristics, which means that even a slight
pressure fluctuation has a strong influence on the volume flow conveyed. In
partial load conditions and in case of strong wind, the volume flow can decrease
to zero, which has a considerable influence on the heat recovery rate.
In contrast, the following CFD simulations under the various conditions all
showed similar behaviour for ventilation effectiveness. Thus, a mixing
ventilation characteristic with the typical air exchange efficiency of 0.5 was
available in the individual rooms, almost independent of geometry, thermal
conditions, volume flow and imbalance. Here, alternating ventilation units did
not differ from continuously operated ones. Previous doubts that areas could be
found in alternating operation – especially in corridors – that would not be
supplied with fresh air by premature reversal of the ventilation direction
could thus be eliminated.
A great
challenge during the test is the unsteady mode of operation during heat
recovery. Therefore, it is not possible to use the methods known from continuously
operating devices to determine characteristic values such as heat recovery,
balance or air volume flow. For this reason, the air volume flow of continuous
operation, which can be measured using a conventional method, has been used for
simplification reasons up to now. The reduction of the mean volumetric flow due
to the start-up and shut-down processes during the switching is neglected. In
the EwWalt project a method was developed to measure
the mean air volume flow also in alternating operation with comparable
accuracy. The volume flow of the two strands is recorded over time using a
dynamic pressure method (Figure 4). An average volume flow in alternating operation can be determined
from the measured curve. Comparative measurements have shown that in this case
the average volume flow in alternating operation was approx. 85% of the volume
flow in continuous operation. This method can also be used to determine the
imbalance in alternating operation. This is a precondition for correct
measurement of heat recovery.
Figure 4. Example of volume flow curve measured in
alternating operation.
Two methods
are currently used to measure heat recovery. One method is described in EN 13141-8
Ventilation for buildings - Performance testing of
components/products for residential ventilation - Part 8: Performance testing
of non-ducted mechanical supply and exhaust ventilation units (including heat
recovery)for mechanical ventilation systems
intended for a single room: 2014 (direct method), the second method is
used for DIBt (DeutschesInstitutfürBautechnik
– German institute of building technology) approval (purge air method). Both
methods were examined in detail in the EwWalt
project. For the direct method, the comparison measurements showed an increased
measurement uncertainty of more than 8% due to the inhomogeneous temperature
distribution of the air leaving the device (Figure 5).
Figure 5. Qualitative visualization of the temperature
distribution at the outlet of the device.
This
uncertainty is prevented in the purge air process by homogenizing the air by
mixing and turbulence before temperature measurement. A previously carried out
inter-laboratory test of the DIBt resulted in a
comparable exactness with this procedure as with the procedures for
continuously working devices. The purge air method was further developed on the
basis of the previously measured average volume flow to eliminate systematic
disadvantages for compact units. With the help of the disbalance measured in
alternating operation, the result of the thermal test can now also be corrected
in analogy to the measurement of the continuous devices. During the comparison
measurements, further parameters such as the purge air volume flow and the
speed were optimized, so that the accuracy of the process could be further
improved. A complete description of the purge air process provided the basis
for its inclusion in the revision of the standard EN 13141-8 which is
currently ongoing.
The EwWalt research project was able to answer some of the most
urgent questions on the classification and evaluation of decentralized
alternating residential ventilation devices.
The
recently achieved scientific results are based on investigations of the
function of alternating ventilation devices based on numerical flow
simulations. It was found that in all cases there is mixed ventilation
practically independent of the room design. About the imbalance of the
ventilation units and consequently also the effects of interference pressures
(e.g. due to wind) on heat recovery, a correlation with the steepness of the
unit characteristic curve could be demonstrated.
Parallel to
the simulation, methods for the experimental evaluation of alternating
ventilation devices were developed. With the developed method for air flow
measurement in alternating operation it is possible for the first time to
measure the effective air volume flow relevant for the design as well as the
imbalance in alternating operation. For the determination of heat recovery, the
direct method described in EN 13141-8 and the purge air method used for DIBt approval were analysed and compared in detail. Test
boundary conditions are defined for the methods to improve the measurement
uncertainty and comparability of the results.
From the
results, useful characteristic values for standardization were identified and
proposed for standardization work, e.g:
·
a
description of the purge air procedure for testing alternating ventilation
units,
·
a
detailed representation of a standard-compliant design of alternating
ventilation units about the positioning of the components and determination of
the volume flows for typical constellations,
·
an
evaluation algorithm including characteristics for dual use of air,
·
a
normative concept for the consideration of start-up processes during
alternating operation,
·
an
algorithm for considering wind pressure stability as a function of climate data
in the efficiency of heat recovery, and
·
further
information on current standardization.
In the
framework of the project, further topics essential for the well-founded
evaluation of alternating ventilation units, such as moisture recovery, wind
susceptibility or comfort evaluation, have been identified which should become
the subject of further research activities.
The
research project (SWD-10.08.18.7-16.32) has been financed by the research
initiative “Future Building” of the German Federal Ministry of Environment,
Nature Conservation, Building and Nuclear Safety as a joint project with FGK e.V. (Professional Institute of Air Conditioning in
Buildings – registered association).
Follow us on social media accounts to stay up to date with REHVA actualities
0