Buildings have a significant contribution in the overall energy consumption in the EuropeanUnion (“EU”) by about 40%. For this reason, the EU has issued specific directives to member states related to the Energy Performance of Buildings and the use of renewable energy in buildings. Cyprus has embedded into national law the aforementioned directives, by taking various measures, such as issuing relevant decrees. The latest decrees by the Cypriot Ministry of Energy, Commerce, Industry and Tourism (“MCIT”), came into effect on 11 December 2013, according to which the new maximum specified heat transmission coefficients (“U-values”) for the building envelope are as follows: Umax external walls/ columns/ beams = 0.72 W/m²K, Umax external exposed floors/ roofs = 0.63 W/m²K, Umax floors above spaces without air-conditioning = 2.00 W/m²K, Umax external openings = 3.23 W/m²K, Umean max. = 1.30 W/m²K.
Compliance with the decrees issued by MCIT is both essential and crucial. That is why this study examines whether the minimum requirements regarding theU-values for the building envelope, as well as the average U-value, of the new residential buildingsin Cyprus are according to the decrees issued by the MCIT, both as they were declared in the buildings’ Energy Performance Certificates (“EPCs”), and as they were built on site.
The present
study focuses on the U-values of 22 new residential
buildings, located in the southern part of Cyprus (see Figure 1). During the study, photographs of
the examined buildings during construction phase and documents from suppliers
regarding the U-values of specific elements were collected, site visits and
inspections took place in order to gather information regarding their real
construction, and communications with architects, constructors, and tenants,
where possible, were conducted in order to verify the as built situation of the
examined construction elements that were declared in the EPCs. Moreover, a
calculation of their U-values was conducted taking account of the as built
situation in order to check whether the buildings were built as designed,
specified and declared regarding those specific elements.

Figure 1. Study conducted in the southern
part of Cyprus.
Non-compliance with the input data in the
EPC of a building leads to wrong reporting, which in most cases means that the
reported performance is better than the actual performance. Reported U-values
may vary from actual U-values due to various reasons. For example during EPC
calculation the qualified building energy assessors (QE) may be applying same
U-values for construction elements with different U-values, or during
construction there may be use of different products with worse U-values than
the ones specified during the EPC calculation, or there may be mistakes
or omissions of building elements during construction which lead to a different
U-value than the one stated, or there may be missing or unclear
definition regarding input data (e.g. windows, doors). Also, in Cyprus,
although there is a control framework regarding the calculations in the EPCs in
order to submit to authorities for building permit, there is no control
framework on site, which means that there is no procedure to control energy performance issues related to
the quality of the works.
In the 22 new residential buildings, which
were examined in the present study, there are deviations between reported and
actual U-values, which sometimes are not so important, for example during
calculation a construction element like the coat cement being omitted, but
which sometimes are very important, for example there may be no reliable input
data, or a construction element like part of an exposed slab or a single glazed
window may not be taken into account, or there may be changes during
construction without the required EPC revision (see Figure 2).[1]
|
|
Figure 2.
Causes for deviations between calculated in EPC U-values and in actual
U-values. |
The study also showed that only 54.5% of the examined new residential buildings fully comply with the new requirements regarding maximum U-values and maximum average U-Value, whereas in the cases that they do not comply, there are specific construction elements that do not comply, which are the exposed floor slabs and the external openings. As for the pattern of causes for non-compliance, the study revealed that in most cases the causes are either lack of knowledge which results in construction elements not to be taken into account, or changes during construction without the required amendment of the EPCs and check from the relevant authorities, or application of the same U-values for construction elements with different U-values by the QE for simplification.
![]()
QUALICHeCK
responds to the challenges related to compliance of Energy Performance
Certificate (EPC) declarations and the quality of the building works. Find out
more at http://qualicheck-platform.eu.
The
QUALICHeCK project is co-funded by the Intelligent Energy Europe Programme of
the European Union. The sole responsibility for the content of this article
lies with the author(s). It does not necessarily reflect the opinion of the
European Union. Neither the EASME nor the European Commission are responsible
for any use that may be made of the information contained therein.
[1]Important note:Requested information was not provided by some QE and the main reason, as was reported by them, was that thereported in EPCs U-values vary from actual U-values due to either lack of a supervising engineer on site, or alterations made during construction without the required revision of the EPC due to time/budget reasons, or engineers giving wrong and/or deficient information to QE due to lack of knowledge or appreciation of the value of EPC.