Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
“The article
was first published in German in “Wohnungslüftung in Deutschland” in TAB
6/2013, p. 38–44”
Ronny MaiDipl.-Ing.ILK Institute of Air
Handling and Refrigeration, Dresden | Thomas HartmannProf. Dr.-Ing.ITG Dresden Institute
for Building Systems Engineering - Research and Application |
To facilitate
the further development of the German energy saving regulations, the standard DIN V 18599
has been revised and released in 2011. One of the main innovations is the balancing
for cooling of residential buildings in part 6. The described cooling
systems of residential buildings are classified according to Figure 1.
The focus
is on technical solutions, which are realized in connection with heating or
ventilation systems. Typical solutions are e. g. use of heat pumps in cooling
mode, but also the passive cooling (including ground heat exchangers or fan
assisted night ventilation). Of course, conventional cooling systems, such as
compression refrigeration machine and split- / multisplit-systems are mapped.
Figure 1. Alternatives for cooling of residential buildings according to DIN V 18599-6: 2011.
A major
difference to cooling in non-residential building represents the often restricted
performance of the cooling systems of residential buildings. For this a part load
factor fc,part and a
precooling factor fc.limitare
introduced. The part load factor describes the case, that not the entire used
area of the building is cooled:
with
fc,part part load factor
AN,c cooled used area (according to design)
AN used area
The precooling
factor takes into account, that not all cooling systems for residential buildings
for a complete coverage of energy need for cooling being interpreted. This can be caused
by limitation of cold generation (e.g. ground heat exchanger or fan-assisted
night ventilation) or by a limitation of cold control and emission in the room
or cold distribution (e. g. air cooling systems or floor cooling):
fc,limit precooling factor
fc,limit,g precooling factor by limitation of cold generation
fc,limit,ced precooling factor by limitation of cold control and emission in the room or cold distribution
The purpose
of precooling systems is to reduce the room temperature without guaranteed
conditions (such as compliance with Category A according to [EN ISO 7730]
irrespective of the cooling loads). The resulting thermal conditions in the room
can be exemplarily illustrated on the vertical temperature gradient (Figure 2). A cooling is done, however, with the aim of achieving defined comfort
conditions even at higher loads and must have corresponding performance reserves.
Figure 2. Vertical temperature gradient as a
function of the cooling system (examples).
A precooling (examples of active cooling systems in Table 1) can be the result of a limited cooling
capacity (e.g. cold generation by free cooling or cooling by radiators as
cooling coil in the room).
Table 1. Maximum cooling capacity of selected systems for active cooling according
to DIN V 18599-6.
Control Emission Distribution | Generation | |||
Outdoor air – water – heat pump | Exhaust air – supply air – heat pump | Compression refrigeration machine | Room air conditioning systems | |
Ceiling cooling | 20 W/m² | – | 45 W/m² | – |
Floor cooling | 20 W/m² | – | 20 W/m² | – |
Radiator as cooling coil | 2.5 W/m² | – | 2.5 W/m² | – |
Fan coil | 20 W/m² | – | 45 W/m² | – |
Ventilation system | – | 5 W/m² | 5 W/m² | – |
Split / multisplit system | – | – | – | 45 W/m² |
As a result you get a precooling factor in dependency of
· cold generation,
· cold control and emission in the room,
· cold distribution,
· building type and
· level of heat insulation.
Examples
for the precooling factors in a new single-family house show Table 2 for active cooling and Table 3 for passive cooling according to DIN V 18599-6.
If the
precooling factor reached a value of 1, a full cooling can be realized with the
system, the energy need for cooling meets completely. With precooling factors
less than 1, the energy need for cooling can be partly covered.
Table 2. Precooling factor fc,limit of selected systems for active cooling according to DIN V 18599-6 – new single-family house.
Emission Distribution | Generation | |||
Outdoor air – water – | Exhaust air – | Compression refrigeration machine | Room air conditioning
systems | |
Ceiling cooling | 1.00 | – | 1.00 | – |
Floor cooling | 0.98 | – | 0.98 | – |
Radiator as cooling coil | 0.36 | – | 0.36 | – |
Fan coil | 1.00 | – | 1.00 | – |
Ventilation system | – | 0.60 | 0.60 | – |
Split / multisplit system | – | – | – | 1.00 |
Table 3. Precooling factor fc,limit of selected systems for passive cooling according to DIN V 18599-6 – new single-family house.
Control Emission Distribution | Generation | |||
Brine – water – | Fan assisted night ventilation | Ground heat exchanger (without
bypass) | Night ventilation and ground heat exchanger | |
Ceiling cooling | 0.73 | – | ||
Floor cooling | 0.73 | |||
Radiator as cooling coil | 0.36 | |||
Fan coil | 0.73 | |||
Ventilation system | 0.60 | 0.10 | 0.44 | 0.51 |
Split / multisplit system | – | – | – | – |
The generator
cooling output is determined in accordance with part load and precooling effects
of the cooling system as well as heat gains during control and emission in the
room, distribution and storage:
with
Qrc,b energy need for cooling
fc,part part
load factor
fc,limit precooling factor
Qrc,ce control
and emission heat gains for cooling
Qrc,d distribution
heat gains for cooling
Qrc,s storage heat
gains for cooling
This
results in the annual final energy demand depending on the type of cold generation.
For compression refrigeration machines or heat pumps in cooling mode applies:
with
Qrc,f,electr,a annual final energy demand for cold generation (electricity input)
Qrc,outg,a annual generatorcooling output
EER energy efficiency ratio
PLVav mean part load value
Table 4using the example of new single-family house with default values to show
the resulting seasonal energy efficiency ratio (SEER = EER * PLVav).
Table 4. Seasonal energy efficiency ratio
SEER of selected systems for active cooling according to DIN V 18599-6
6 – new single-family house.
Control | Generation | |||||
Outdoor air – | Exhaust air – | Compression refrigeration machine | Room air conditioning systems | |||
Outgoing temperature cooling | Split | Multi-split | ||||
6°C | 16°C | |||||
On / Off | 2.11 | 2.55 | 2.18 | 2.95 | 1.90 | 1.40 |
Inverter controlled | 3.10 | – | – | – | 2.83 | 2.77 |
Digital scroll | – | – | 2.37 | 3.19 | – | – |
Similarly
for the annual final energy demand for cold generation (heat input) of thermal refrigeration machines:
Qrc,outg,therm,a annual final energy demand for cold generation (heat input)
Qrc,outg,a annual generatorcooling output
z nominal heat capacity ratio
PLVav mean part load value
For the assessment of the efficiency of
different technologies it was necessary to have information about the trend of
a cooling load of a refrigeration period time. These calculations were carried
out in accordance to different structural building properties, to reflect the
influence of different building age classes. Therefore a classification according
to the building age respectively the insulation standard was done (Table 5).
Table 5. Classification according to the residential buildings age.
Class of residential building | Old building (low insulation
standard) | Old building (ordinary
insulation standard) | New building (high insulation
standard) |
Built year | to 1995 | Since 1996 | New building |
Insulation standard | – | German | German |
U-value external wall | 1.0 W/m²K | 0.5 W/m²K | 0.28 W/m²K |
U-value external window | 2.5 W/m²K | 1.8 W/m²K | 1.3 W/m²K |
U-value roof, top floor ceilings | 0.8 W/m²K | 0.3 W/m²K | 0.2 W/m²K |
U-value wall or ceiling covered unheated rooms / ground covered walls | 1.0 W/m²K | 0.5 W/m²K | 0.35 W/m²K |
For each residential building class beyond the
influence of typical parameters like thermal storage capacity, share of window
area, building orientation, type of shading system was studied and divided in 3
categories of buildings (Table 6), in which for all variants the
thermal heat protection in summer is maintained.
Table 6. Categorization of typical parameters for the cooling demand.
Building | Category 1 | Category 2 (standard) | Category 3 |
Thermal storage capacity | Thermal mass class S | Thermal mass class M | Thermal mass class L |
Share of window area | 10% of ground floor, | 20% of ground floor, | 30% of ground floor, |
Building orientation | Main window area | Main window area | Main window area |
Window
type | Double glazing g = 0.8 | Heat protection | Solar protection |
Type of shading system | Internal glare protection activated only in case of direct solar radiation | External solar protection activated only in case of direct solar radiation | External solar protection activated from an amount of 200 W/m² |
As a result it could be shown, that a differentiation
of building age is necessary in the standardization process.
In addition to the building properties the kind
of building usage is responsible for the trend of the cooling load. In this
context the usage-specific internal thermal gains for different rooms of a
residential building (living room, bedroom, bath, kitchen) from EN ISO 13791
were used and a load profile for a children’s room and humidification effects
in all profiles were added. Based on the room profiles averaged flat-profiles
were derived for single-family houses (EFH) and multi-family houses (MFH),
which correlate in the daily total amount with the values for the internal heat
sources of DIN V 18599-10 (45 Wh/m²d for
single family houses and 90 Wh/m²d for multi-family houses). The determined
usage profiles were validated using measured data for 10 different residential
buildings and showed a good agreement in this field.
Taking into account the boundary conditions described a lot of cooling load profiles were determined for the single- and multi-family houses. Figure 3 shows the frequency distribution of the cooling hours in residential rooms of single-family houses in comparison to the complete flat as an exemplary for the building Category 2.
Figure 3. Frequency distribution of the cooling hours in different rooms of existing
single-family houses with ordinary insulation standard (German “WSchV 1995”,
building Category 2).
All living rooms show a similar frequency distribution
of the cooling hours like the complete flat. As a result of the investigations
it was found that there is no need for a differentiation between different
rooms of a flat. Therefore residential buildings also in the cooling case can be calculated with the existing single-zone
model.
According to Figure 3 the maximum frequency of the
cooling hours occurs at very low cooling load. Thus cooling systems with a low
cooling capacity could reach comfortable room temperatures in this part load
range.
In the standardization process the maximum
value of the cooling load in the load profile corresponds to the maximum required
cooling capacity. If the installed system can‘t deliver the complete required cooling
capacity it is defined as a “part cooling system”. This capacity deficit could
be a consequence of a limited cooling capacity of the generation and
distribution system (e.g. an air based Free Cooling system with a ground heat
exchanger) or of the control and emission system (e.g. cold water flowed floor
heating).
The efficiency of a chiller is usually
described through the energy efficiency ratio EER. The nominal cooling capacity
is required only in few hours of the year. According to Figure 3 cold generation systems in
residential buildings work the most time in the part load range. The reduction
of the cooling capacity comes from an integrated capacity control system, which
can be designed as a continuously control (e.g. variable speed control) or a
staged system (e.g. ON-OFF operation). The more efficient this capacity control
system works, the more efficient the complete cooling system is.
To map this effect in the normative value
method, the part load value was established. Through multiplication with the
nominal energy efficiency ratio EER, the seasonal energy efficiency ratio SEER
of a chiller can be calculated. The SEER value characterizes the relation
between the annual net energy demand for cooling and the necessary required final
energy demand. A cooling system with high energy efficiency (low final energy
demand) must have a high nominal energy efficiency ratio EER and additionally a
high part load value PLV.
A
variety of part load values for different system boundary conditions and
various kinds of building usages contains the German standard DIN V 18599-7:
2011 in annex A for non-residential buildings. Taking into account a possible
capacity limitation of the residential buildings control and emission and
distribution systems and based on the typical load profiles for residential
buildings (Figure 3) part load values PLV for active cooling
systems in residential buildings were determined for the first time. Figure 4 shows the part load values PLV of a
reversible outdoor air – water heat pump in the cooling mode exemplary for
existing single-family houses with an ordinary insulation standard (German ”WSchV 1995”).
Figure 4. Part load value PLV of a reversible outdoor air – water heat pump in
existing single-family house with ordinary insulation standard (German “WSchV 1995”,
building Category 2).
In general the inverter-controlled heat pump is more energy efficient than the ON-OFF-controlled heat pump because it has higher part load values in cooling mode.
If the specific cooling capacity of the control and emission system decreases fewer than 20 W/m² the cooling capacity of the heat pump must be reduced. This correlates with a reduction of the energy efficiency. At the same time the precooling factor decreases fewer than the value of 1.0. For that the cooling capacity limitation of the control and emission system is responsible, because not in the whole cooling period the required cooling capacity could be transferred into the room. Figure 5 shows the trend of the precooling factor in dependence of the cooling capacity limitation of the control and emission system exemplary for existing single-family houses with different insulation standards.
Figure 5. Precooling factor in dependence of the cooling capacity limitation of the control and emission system (building Category 2).
The precooling factor describes the relationship between the provided cooling energy of the installed cooling system and the required overall cooling energy demand as an area-weighted average of all rooms in a single family house. This factor tends to be slightly higher in good insulated buildings than in low insulated old buildings.
At all systems decreases the transferred cooling energy rate if the control and emission limitation increases. At air based ventilation systems with a cooling capacity of maximum 5 W/m² only the half of the required annual cooling energy demand may be provided.
Reversible heat pump sale shows, that cooling
of residential buildings in Germany leaving the niche in recent years. As
reasons, increased user requirements for the comfort, the discussion of the
climate change or the subjective feeling of very hot summer in the recent past
can be named.
Nevertheless, in Germany no general trend for
cooling of residential buildings should be noted. Structural measures for the
summer heat protection in addition to moderate weather conditions are the
reason for preferring compensation of cooling
loads to using technical systems. However, in new residential buildings can
originate cooling loads by approximately 30 W/m². These are always more
frequently at least proportionally covered by technical systems that take over
most other functions (heating, ventilation) in the building.
With current German standard DIN V 18599:
2011 cooling for residential building is part of the framework of the energy
saving regulation (EnEV) for the first time in Germany. Attention is paid to
the peculiarities in comparison with air conditioning of non-residential buildings.
Due to the typical cooling of residential
buildings, which often is realized as an additional feature of existing
equipment (e.g. in combination with heat pumps or ventilation), a new
definition of the cooling target arises.
In DIN V 18599-6: 2011 precooling and
part cooling effects are described and quantified to enable comparison of
cooling systems both from the perspective of the energy balance and thermal
comfort. The focus is consequently on typical residential cooling systems
without neglecting the conventional refrigeration. The energetic balance method
provides the opportunity to create an adequate cooling effect with efficient
technologies usually without major additional investments in residential
buildings and to localize at the same time inefficient systems in advance.
ReferencesEN ISO 13791:2004. EN ISO 7730:2005 DIN V 18599:2011-12 Part
2: Net energy demand for heating and cooling of building zones Part
6: Final energy demand of ventilation systems and air heating systems for residential
buildings Part
7: Final energy demand of air-handling and air-conditioning systems for non-residential
buildings Part 10: Boundary conditions of use, climatic data EnEV 2009 Verordnung
über energiesparenden Wärmeschutz und energiesparende WSchV 1995Wärmeschutzverordnung (WärmeschutzV) in der Fassung der Bekanntmachung vom 16. August 1994. German heat protection regulations in the version of the announcement of August 16, 1994 |
Follow us on social media accounts to stay up to date with REHVA actualities
0