Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
|
|
Burhan YorukIstanbul Technical University, | Ahmet ArisoyIstanbul Technical University, |
When a
cooling based climate is considered, evaporative cooling of outer walls during summer can be a very valuable
tool for reducing cooling energy from outer skin of the buildings. There are some
solutions in the literature based on this principle. However, applying such an
evaporative layer on the inner surfaces of the outer walls is a novel approach.
At this stage only the idea has been evaluated.
A case
study, in which the target is reducing cooling energy (heat gains) from outer
walls for energy conservation has been conducted. Cooling inner surfaces of the
outer walls reduces heat gain from the outer walls and more importantly
increases the thermal comfort indoors in summer conditions by decreasing the
wall temperatures.
Simulation
results show that this
system is more successful comparing to the thermal insulation in Mediterranean
climate. Depending on the design parameters the peak heat gain through the
outer walls can be compensated by the system without any additional insulation
layer. Even in some favourable conditions an additional cooling effect can be
achieved besides avoiding heat gains from outer walls.
The
definition of energy efficiency measures and packages are strictly related to
the climate, considering both temperature and humidity. Therefore, for hot and
dry regions, specific solutions are certainly required. In particular,
Mediterranean climate is characterized by a dominant cooling demand and varying
outdoor conditions along the day.
Behaviour
of outer walls plays an important role on heat gains and heat losses of the
building. Thermal insulation of walls is known as an important measure to
reduce static heat loss of buildings for cold and mild climates. However,
increasing thermal insulation thickness plays a reverse effect on heat gains
due to dynamically changing outdoor conditions for hot climates [1]. Instead of increasing thermal insulation
thickness, evaporative cooling of outer walls can be used reducing cooling
energy from outer skin of a building in such climates.
An
evaporative layer to be applied on the inner surfaces of outer walls has been
designed to reduce the cooling energy of buildings in Mediterranean region in
this study. This can be considered as a new approach.
This work
presents a case study. A building in Mediterranean region has been considered as
an air conditioning system that keeps indoor temperatures at the required
level. The target is reducing cooling energy (heat gains) from outer walls for
energy conservation. The proposed heat absorbing layer basically consists of
two plates with a gap between them and it is applied on the inner side of the
outer walls. Indoor air passes through this gap from bottom to top, across all
the length of the wall. Back plate is actually a moist pad and evaporation of
water from this pad creates a cooled wall surface. Cooling inner surfaces of
the outer walls reduces heat gain from the outer walls and, more importantly,
increases the thermal comfort indoors in summer conditions.
A dynamic
computer model has been developed to simulate the system. This model can consider
the effects of thermal mass of the wall too.
It is shown
that this system is successful in Mediterranean climate. Depending on the
design parameters, the heat gain through the outer walls can be compensated by
the system without any additional insulation layer. Even in some favourable
conditions an additional cooling can be achieved. This layer is also effective
during the winter conditions. In winter season, the layer is used in dry state
and it reduces the heat loses.
A standard
building in Izmir-Turkey is considered as the reference case in this study.
Izmir is selected as the representative of the Mediterranean climate. The building
is a two storey residential house with 512 m²
total floor area. Total outer wall area is 314 m² and only 211 m² of
this wall can be covered by the proposed layer. Density of 5 cm thick
concrete external walls is 1,600 kg/m³. Thermal mass is an important
parameter effecting on thermal performance of the building skin and this value
has been parametrically studied in this paper. 5 cm thick thermal
insulation is necessary, in this case, to remain within the limits of the
standard. All other external and internal heat gains/losses have not been taken
into consideration in this study.
It is
assumed that there is an ideal HVAC system which controls indoor temperatures
ideally. Cooling set point temperature is 24°C for summer period. Heating set
point temperature is 21°C during the
winter period. Total ventilation air rate is 1 013 m³/h which
corresponds to 0.66 air change per hour.
This
approach is based on a modular evaporative layer to be applied on the inner
surface of the outer walls. This layer is to be attached to the wall surfaces
tightly by screws and it should be leak-proof. The drawing of a module is seen
in (Figure 1). These modules can be connected to
each other and all the outer wall inner surfaces can be covered with these
elements. Frame of the module is steel and the panels of the module can be
either plastic or sheet steel. There is a porous pad attached to the back-side
panel of the module, there is a gap for air flow between this pad and the front
side panel of the module. The pad is made of synthetic fibers and it
is wetted by the water dripping nozzles at the top. Gap dimensions and air flow
rate have been defined by the help of the developed computer program. Room air
is introduced to the gap from bottom of the module and this air picks up the
evaporated water from wetted pad. Collected moist air at the top of the gap is
exhausted to the outdoor by the help of a fan. This air circulation system can
also be part of the mechanical ventilation system of the building. In this
system, no moist air is introduced in indoors.

Figure 1.
Drawing of the designed evaporative module.
Two
different cases have been studied as wetted pad in summer and dry pad in winter
to evaluate the year-round performance of the proposed layer. Hourly
temperature and humidity variations and the resultant heat gain/loss values
have been solved for these cases. Using the model results, optimized
dimensions, air flow rates and water feeding rates have been determined.
Effects of wall thermal inertia have been investigated, performance of the
proposed system have been evaluated.
The
optimized air flow gap/clearance is 0.01 m and optimized air flow velocity
is 0.8 m/s. Indoor air temperature (and the air temperature at the
entrance of the layer) is 24°C and the humidity ratio of air is 0.0093 kg/kg
for summer season. This humidity ratio corresponds to 50% relative humidity.
Indoor air temperature (and the air temperature at the entrance of the layer)
is 21°C and the humidity ratio of air is 0.0078 kg/kg for winter season.
Hourly changing outdoor temperature and solar radiations on the outer surfaces
of the wall in each direction have been considered as boundary conditions.
Hourly weather data of the typical year has been taken from International
Weather for Energy Calculations Database [2].
In Case A,
the pad is kept wet by supplying water from top. With the help of evaporation,
inside wall surface temperatures can be kept below the room temperature. In
these conditions, besides preventing heat gain from outer walls, an additional
cooling effect is seen. A heat loss occurs from indoor air. Low inner surface
temperatures also help improving comfort conditions due to radiative heat
transfer between cooled wall and the human body. Mean leaving air temperature
at the middle of the wall for the first week of July in a typical year is 25.3°C
which is very close to the room air. Meanwhile, specific humidity increases
from 9.3 g/kg to 17.6 g/kg in exhaust air. Leaving air specific
humidity corresponds to approximately 70% relative humidity value. This humid
and cool air can be used in a conventional heat recovery unit to reduce the
temperature of incoming hot ventilation air.
Heat gains
through cooling months are given in Table 1. Negative values indicate heat loss
(additional cooling) and positive values indicate heat gain. Besides preventing
heat gains from outer walls, additional cooling created by the evaporative
layer along five cooling months, is 16,294 kWh. However, without applying
this evaporative layer, total heat gain from same bare walls was 43,925 kWh.
Thermal insulation can reduce the heat gain to a certain extent in summer
months, but additional cooling effect cannot be created by only a thermal
insulation. It seems adding such a layer inside the walls, causes much better
performance than the thermal insulation for hot and dry regions and in
dynamically changing outdoor conditions.
Table 1.
Monthly heat gains of the building only from the outer walls [kWh].
EvapWall | Bare Wall | With Isolation | |
May | −4587 | 4516 | 983 |
Jun | −2838 | 9885 | 2189 |
Jul | −2512 | 11637 | 2593 |
Agu | −2827 | 10452 | 2325 |
Sep | −3530 | 7435 | 1663 |
Heat loss
should be reduced from the outer walls in winter. November, December, January
and February are four winter months. The common solution for this is applying
thick thermal insulation to the outer walls. Without any thermal insulation,
mean inner surface temperature of bare wall is 16°C in a typical January week.
In (Case B)
the pad is kept dry but the air flow continues. It is assumed that indoor
temperature is kept constant at 21°C by the heating system in winter. Inside
wall surface temperatures can be increased by the flowing warm room air in the
layer gap. These elevated inner surface temperatures reduce the heat loss and
also help improving comfort conditions. The mean temperature of air is 19.1°C
in the gap and the mean temperature difference between the room and the layer
is about 2ºC. In winter conditions, this proposed dry layer can be considered
as a heat recovery unit. Air flow rate is also the same as in the summer case
and correspond to the ventilation air rate (total 1,013 m³/h). There could
be a conventional heat recovery unit in the system, in this case, this layer
and heat recovery unit work in parallel.
Heat loss
through winter months are given in Table 2. Total heating energy for 4 winter
months is 15,779 kWh. Without applying this dry evaporative layer, total
heat loss from same bare walls is 25,413 kWh. This reduction is big enough
to consider.
Table 2.
Monthly heat losses of the building only from the outer walls [kWh].
DRY | Bare | Isolation | |
Jan | −4572 | −7352 | −1652 |
Feb | −4011 | −6465 | −1443 |
Nov | −2494 | −4020 | −854 |
Dec | −4701 | −7576 | −1672 |
Thermal
insulation is the most effective solution in winter. However, without any
thermal insulation EvapWall decreases heat losses
almost half compared to the bare wall.
Considering
both summer and winter performances of the proposed layer, annual energy need
for the building and the outer wall have been calculated. This performance
value has been compared with the bare wall and the 5 cm
thick insulation covered wall. Evaporative layer will work wet during the five
summer months and will work dry during the 4 winter months. Building energy
simulation has been carried out by using Energy-Plus software for bare wall and
the insulated wall. Temperature set points are again 21 for four winter months
and 24°C for the rest of the year with air conditioning system that operates 24
hours. Results are given in Table 3. Negative sign
for EvapWall indicates additional cooling effect. All
other figures are considered as load and there is no sign of differentiation
for heat gain or loss in the table. March, April and October can be considered
as intermediate season. Both cooling and heating are required during these
months. However, outer walls in each case more or less perform as a cooling
element and reduce total mechanical cooling load in these months.
Table 3.
Total monthly heat (energy) lost/gain only from outer walls [kWh].
| Insulated wall | Bare wall | EvapWall | |||
Month↓ | Heat loss/gain by the wall (kWh) | Total energy requirement of the system (heating or cooling) (kWh) | Heat loss/gain by the wall (kWh) | Total energy requirement of the system (heating or cooling) (kWh) | Heat loss/gain by
the wall (kWh) | Total energy requirement of the system (heating or cooling) (kWh) |
January | 1652 | 6800 | 7352 | 12500 | 4572 | 9720 |
February | 1443 | 6735 | 6465 | 11757 | 4011 | 9303 |
March | 1430 | 4196 | 6178 | 8944 | 3804 | 6570 |
April | 660 | 2700 | 3038 | 5078 | 1849 | 3889 |
May | 983 | 4919 | 4516 | 8452 | −4587 | 0 |
June | 2189 | 8011 | 9885 | 15707 | −2838 | 2984 |
July | 2593 | 8025 | 11637 | 17069 | −2512 | 2920 |
August | 2325 | 10452 | 10452 | 18579 | −2827 | 5300 |
September | 1663 | 5493 | 7435 | 11265 | −3530 | 300 |
October | 127 | 3226 | 618 | 3717 | 373 | 3472 |
November | 854 | 5803 | 4020 | 8969 | 2494 | 7443 |
December | 1672 | 6450 | 7576 | 12354 | 4701 | 9479 |
Annual | 72810 | 134391 | 61380 | |||
According to these results, applying evaporative layer is the best solution for İzmir. The 5 cm thick thermal insulation reduces annual building energy requirement from 134,391 kWh to 72,810 kWh. Saving of energy is about 61,581 kWh annually. However, in case of proposed evaporative layer, annual energy saving is higher comparing the thermal insulation. The proposed layer reduces annual building energy requirement from 134,391 kWh to 61,380 kWh and saving of energy is about 73,012 kWh annually. It seems that this proposed system is advantageous for hot and dry climates.
Thermal mass of the wall highly influences the
performance of the outer wall. When outdoor whether conditions change daily and heat loss and gain
occurs in the same day, thermal mass of the wall becomes important. Increasing
thermal mass improves the thermal performance in dynamic climate conditions.
This is especially effective during intermediate seasons. Wall thickness has
been doubled in this case study and all the calculations were repeated for the EvapWall case. Calculated heat loss values are given in Table 4. Because these values are always heat loss, the sign is negative. This
monthly negative value should be as low as possible in winter and as much as
possible in summer. In case of thick wall, heat loss decreases in winter and
cooling effect increases in summer. This means increasing thermal mass acts
positively in a year-round performance of the wall.
Table 4.
Comparison of thermal mass on wall thermal performance. Monthly heat loss of
outer walls [kWh.]
EvapWall Heavyweight heat loss | EvapWall Lightweight heat loss | |
Jan | −4572 | −5779 |
Feb | −4011 | −5050 |
Mar | −8040 | −8253 |
Apr | −6795 | −6614 |
May | −4587 | −3496 |
Jun | −2838 | −1258 |
Jul | −2512 | −734 |
Agu | −2827 | −1145 |
Sep | −3530 | −2194 |
Oct | −6194 | −5699 |
Nov | −2494 | −3153, |
Dec | −4701 | −5941, |
Evaporative
layer to be applied inside surfaces of outer walls in Mediterranean climate is
a novel approach. This novel element has been designed and its performance has
been investigated in this study.
Simulation
results indicate that this layer prevents heat gain from outer walls and
provides additional cooling during summer period in İzmir conditions.
This layer
can also be used in winter conditions as dry.
The other
benefit of this layer is improving thermal comfort conditions of the indoor
environment.
It has been shown that evaporative layer is the best solution for İzmir. In case of proposed evaporative layer, annual energy saving is higher comparing to the thermal insulation. The proposed layer reduces annual building energy requirement from 134,391 kWh to 61,380 kWh and the saving of energy is about 73,012 kWh annually.
[1] Stazi, F., Bonfigli, C., Tomassoni, E., Di Perna, C., & Munafò, P.,
2015. The effect of high thermal insulation on high thermal mass: Is the
dynamic behavior of traditional envelopes in Mediterranean climates still
possible? Energy and Buildings, 88, 367-383.
[2] ASHRAE, 2001. International Weather for Energy Calculations (IWEC Weather Files) User Manual and CD-ROM. Atlanta USA.
Follow us on social media accounts to stay up to date with REHVA actualities
0