Stay Informed
Follow us on social media accounts to stay up to date with REHVA actualities
|
|
Jae-Han LimPh.D., ASHRAE member, | Kwang-Woo KimArch.D., Fellow ASHRAE and |
In recent years, radiant heating and
cooling systems have seen considerable use not only in residential buildings
but also in commercial buildings because of their many advantages including
higher comfort level, lower noise level and greater possibility of integration
to the architectural design in comparison with other HVAC systems. In particular,
these systems have gained attention as heating and cooling systems with a high
possibility of utilizing renewable energy sources because they can provide
heating at a low temperature of hot water and cooling at a high temperature of
cold water. Nowadays many countries in Europe, USA and Asia have developed and
applied separate components such as pipes, prefabricated panels, manifolds and
controller to new and existing building construction. Generally a few product
standards had been adopted for the international trade of related products at
that time. For that reason, CEN had been working on developing related
standards for determining the heating and cooling capacity and finally
developed EN 15377 (refer to Figure
1). However, there was no single and comprehensive
international standard for the design of radiant heating and cooling system. Therefore
it was imperative that design standards that maximize the advantages of radiant
heating and cooling systems should be developed. So the ISO Standards need
to deal with the determination of the heating and cooling capacity, system
construction, commissioning and operation all together. And this work could be
done by supplementing above mentioned EN 15377. Furthermore, for the
development of new ISO Standards, some regional characteristics needed to
be considered. For example, some particular floor structures used in each
country should be categorized to include the all types of radiant heating and
cooling system in use. And different comfort criteria which has been preferred
traditionally (e.g. maximum floor surface temperature) should be considered
accordingly during design process.

Figure 1. Structure of European standards
about radiant heating and cooling system design.
The scope of ISO 11855 is the radiant heating
and cooling systems that perform heating and cooling in new construction and
the retrofit of existing buildings. Most of HVAC systems undergoes the life
cycle as shown in Figure 2. To ensure the system performance, technical standards should be applied
to each step of the life cycle.

Figure 2. Life cycle of general HVAC
system design.
To establish the basic design principles,
the design process and conditions were firstly addressed. So it was imperative
that the established systems should be able to perform in accordance with
occupants’ comfort. And the process regarding the determination of the heating
and cooling capacity and system construction (heat supply, hydronic
distribution systems, panels and control systems) must be provided to make it
possible to secure the same performance even when the designers are different. As
for the performance of radiant heating and cooling systems, energy consumption
throughout the building’s life cycle must be taken into consideration. ISO Standards
for determining the energy performance of radiant heating and cooling systems should
be developed by providing methods for conducting dynamic analysis during design
process. It is also imperative that standards be developed to make possible
energy reduction, prolongation of the life cycle of heating and cooling
equipment, and operation of radiant heating and cooling systems according to
their design.
After the review of current EN Standards
and discussions on references and the world-wide experts’ opinions, 8 parts of ISO Standard
structure was firstly proposed as shown in Figure 3. At the development stage,
these standards were assigned to ISO 11855 series, and the structure of
standards was changed into 6 parts accordingly. Experts agreed that ISO 11855
would deal with the embedded surface heating and cooling system that directly
controls heat exchange within the space, and does not include the system
equipment itself, such as heat source, distribution system and controller. The ISO 11855
series addresses an embedded system that is integrated with the building
structure. Therefore, the panel system with open air gap, which is not
integrated with the building structure, is not covered by this series.
The objective of the ISO 11855 series
is to provide criteria to effectively design embedded systems. To do this, it
presents comfort criteria for the space served by embedded systems, heat output
calculation, dimensioning, dynamic analysis, installation, operation, and
control method of embedded systems.

(a) Resolution 122 in TC 205 plenary
meeting, Paris, 2006

(b) EN 15377

(c) EN 1264

(d) ASHRAE Handbook, Systems and Equipment

(e) Opinions from world-wide experts
Figure 3. Basic structure of ISO 11855
considering the current EN Standards and other references.
Part 1 of these standards specifies the
comfort criteria which should be considered in designing embedded radiant
heating and cooling systems, since the main objective of the radiant heating
and cooling system is to satisfy thermal comfort of the occupants. Part 2
provides steady-state calculation methods for determination of the heating and
cooling capacity. Part 3 specifies design and dimensioning methods of radiant
heating and cooling systems to ensure the heating and cooling capacity. Part 4
provides dimensioning and calculation method to design TABS (Thermo Active
Building Systems) for energy-saving purposes, since radiant heating and cooling
systems can reduce energy consumption and heat source size by using renewable
energy. Part 5 addresses the installation process for the system to operate as
intended. Part 6 shows proper control methods of the radiant heating and
cooling systems to ensure the maximum performance when the system is being
actually operated in a building.
Occupant’s thermal comfort would be the
primary objective that any HVAC system pursues. Radiant heating and cooling
systems can be used as primary or hybrid systems which are combined with an air
system and provide unique and cost-effective approaches dealing with numerous
conditions affecting human thermal comfort. Radiant heating and cooling systems
can be used to directly provide heat to humans as well as to spaces. As long as
the occupants are radiantly heated in a radiant heating system, the same
comfort level can be maintained with a lower air temperature in comparison to a
convective heating system. For radiant cooling systems, maintaining the same
comfort level with a higher air temperature in comparison to convective cooling
is possible. Therefore, compared with conventional heating and cooling systems,
it is possible to reduce the energy loss due to ventilation, and infiltration
while maintaining the same comfort level.
Thermal comfort can be defined as the psychological
condition that expresses satisfaction with the thermal environment. Therefore,
thermal comfort would be evaluated by asking all the occupants if they are
satisfied with their thermal environment. However, in order to design and
control radiant heating and cooling systems, it is necessary to predict the
thermal comfort in a room without resorting to a polling result. To provide an
acceptable thermal environment to the occupants, the requirements for general
thermal comfort, e.g. predicted mean vote (PMV), operative temperature (OT),
and local thermal comfort (surface temperature, vertical air temperature
differences, radiant temperature asymmetry, draft, etc.) shall be taken into
account. In radiant systems, floor, walls and ceilings can be used as the heat
transfer surface for heating and cooling. For this reason, special care shall
be paid to the surface temperature limit of the floor and wall with which the
occupants can have direct contact.
The floor temperature has a direct impact
on the comfort of the feet or buttocks. In ISO 7730, the floor temperature
range of 19°C to 29°C is recommended in the space with sedentary and/or
standing occupants wearing normal shoes. This is a limiting factor when
deciding the capacity of floor heating and cooling systems. For heating, the
maximum temperature is 29°C and for cooling, the minimum temperature is 19°C.
However, this temperature range of 19°C to 29°C might be changed by the factor
of whether the occupants wear shoes or not, or whether they usually sit on the
floor or stand up in the occupied zone. Thus, the range of the surface
temperature can be different depending on lifestyle habits. For this reason, it
is recommended to follow the widely accepted standards of each country when
deciding on the optimum range of floor surface temperature. For an electric
heating system, an electrically-heated floor may cause discomfort and even skin
burn if occupants have prolonged contact with the floor. This is due to the
constant supply of heat from an electrical heating source, whereas, for a water
based heating system, the increase in surface temperature is limited by the
water temperature. Therefore it is important to control the electrical heating
source in order to keep the floor surface temperature under the lower limit of
discomfort and skin burn. For wall heating, the maximum recommended surface
temperature is in the range of 35°C to 50°C. The maximum temperature depends on
factors such as whether occupants may easily have contact with the surface or
whether buildings are used for more sensitive persons such as children or the
elderly. When a skin temperature is 42°C to 45°C, there is a risk of burns and
pain. The losses to the rear walls and its influence on neighboring spaces
should be taken into account.
ISO 11855-2 specifies procedures and
conditions to enable the heat flow in water based surface heating and cooling
systems to be determined relative to the medium differential temperature for
systems. The determination of thermal performance of water based surface
heating and cooling systems and their conformity to this part of ISO 11855
are carried out by calculation in accordance with design documents and the model.
This should enable a uniform assessment and calculation of water based surface
heating and cooling systems. The surface temperature and the temperature
uniformity of the heated/cooled surface, nominal heat flow density between
water and space, the associated nominal medium differential temperature, and
the field of characteristic curves for the relationship between heat flow
density and the determining variables are given as the result. Based on the
calculated average surface temperature at given combinations of medium (water)
temperature and space temperature, it is possible to determine the steady state
heating and cooling capacity.
ISO 11855-2 includes a general method
based on Finite Difference or Finite Element Methods and simplified calculation
methods depending on position of pipes and type of building structure. Two
types of simplified calculation methods can be applied according to ISO 11855-2.
One method is based on a single power function product of all relevant
parameters developed from the finite element method (FEM), and another method
is based on calculation of equivalent thermal resistance between the heating or
cooling medium temperature and the surface temperature (or room temperature). A
given system construction can only be calculated with one of the simplified
methods. The correct method to apply depends on the type of system, A to G (depending
on position of pipes, concrete or wooden construction) and the boundary
conditions.
The ISO 11855 series is applicable to
water based embedded surface heating and cooling systems in residential,
commercial and industrial buildings. The methods apply to systems integrated
into the wall, floor or ceiling construction without any open air gaps. It does
not apply to panel systems with open air gaps which are not integrated into the
building structure. The ISO 11855 series also applies, as appropriate, to
the use of fluids other than water as a heating or cooling medium. The ISO 11855
series is not applicable for testing of systems. The methods do not apply to
heated or chilled ceiling panels or beams.
ISO 11855-3 introduces the design and
dimensioning of floor heating, ceiling heating, wall heating, floor cooling,
ceiling cooling and wall cooling respectively. Basically the design and
dimensioning methods for radiant floor heating and cooling were described. And
wall and ceiling radiant heating and cooling can also be applied to the same
procedure except for determination of limit curves because of physiological
limitations concerning the surface temperatures of ceiling heating systems.
Floor heating system design requires
determining heating surface area, type, pipe size, pipe spacing, supply temperature
of the heating medium, and design heating medium flow rate. The design steps for
floor heating system are as follows:
·
Step 1: Calculate the design
heating load QN. The design heating load QN shall not
include the adjacent heat losses. This step should be conducted in accordance
with standards for heating load calculation, e.g. EN 12831, based on an
index such as operative temperature (OT) (see ISO 11855-1).
·
Step 2: Determine the area of
the heating surface AF, excluding any area covered by immovable objects
or objects fixed to the building structure.
·
Step 3: Establish a maximum
permissible surface temperature in accordance with ISO 11855-1.
·
Step 4: Determine the design
heat flux qdes. For floor heating systems including a peripheral
area, the design heat flux of peripheral area qdes,R and the design
heat flux of occupied area qdes,A shall be calculated respectively
on the area of the peripheral heating surface AR and on the area of
the occupied heating surface AA.
·
Step 5: For the design of the
floor heating systems, determine the room used for design with the maximum
design heat flux qmax = qdes.
·
Step 6: Determine the floor
heating system such as the pipe spacing and the covering type, and design
heating medium differential temperature ΔθH,des based on
the maximum design heat flux qmax and the maximum surface
temperature θF,max from the field of characteristic curves.
·
Step 7: If the design heat flux
qdes cannot be obtained by any pipe spacing for the room used for
the design, it is recommended to include a peripheral area and/or to provide
supplementary heating equipment. In this case, the maximum design heat flux qmax
for the embedded system may now occur in another room. The amount of heat
output of supplementary heating equipment Qout is determined by the
following equation:
·
Step 8: Determine the backside
thermal resistance of insulating layer Rλ,ins and the design
heating medium flow rate.
·
Step 9: Estimate the total
length of heating circuit.
If intermittent operation is common, the
characteristics of the increase of the heat flow and the surface temperature
and the time to reach the allowable conditions in rooms just after switching on
the system shall be considered.
Floor cooling system design requires
determining cooling surface area, type, pipe size, pipe spacing, supply
temperature of the cooling medium, and design cooling medium flow rate. The
design steps are as follows.
·
Step 1: Calculate the design
sensible cooling load QN,s. The design sensible cooling load QN,s
does not include the adjacent heat gains. This step shall be conducted in
accordance with standards for cooling load calculation, e.g. EN 15243,
based on an index such as operative temperature (OT).
·
Step 2: Determine the minimum
supply air quantity needed for dehumidifying.
·
Step 3: Calculate latent
cooling available from supply air and also calculate sensible cooling available
from supply air.
·
Step 4: Determine remaining
sensible cooling load to be satisfied by radiant system. Also designate or
calculate the relative humidity and dew point, because cooling system shall
operate within a temperature range above the dew point, which shall be
specified depending on the respective climate conditions of the country.
·
Step 5: Determine the area of
the cooling surface AF, excluding any area covered by immovable
objects or objects fixed to the building structure.
·
Step 6: Establish a minimum
permissible surface temperature in accordance with ISO 11855-1 in
consideration of the dew point.
·
Step 7: Determine the design
heat flux qdes. For floor cooling systems including a peripheral
area, the design heat flux of peripheral area qdes,R and the design
heat flux of occupied area qdes,A shall be calculated respectively
on the area of the peripheral cooling surface AR and on the area of
the occupied cooling surface AA.
·
Step 8: For the design of the
floor cooling systems, determine the room used for design with the maximum
design heat flux qmax = qdes.
·
Step 9: Determine the floor
cooling system such as the pipe spacing and the covering type, and design
cooling medium differential temperature ΔθH,des based on
the maximum design heat flux qmax and the minimum surface
temperature θF,min from the field of characteristic curves.
·
Step 10: If the design heat
flux qdes cannot be obtained by any pipe spacing for the room used
for the design, it is recommended to provide supplementary cooling equipment.
In this case, the maximum design heat flux qmax for the embedded
system may now occur in another room.
·
Step 11: Determine the backside
thermal resistance of insulating layer Rλ,ins and the design
cooling medium flow rate.
·
Step 12: Estimate the total
length of cooling circuit.
ISO 11855-4 allows the calculation of
peak cooling capacity of Thermo Active Building Systems (TABS), based on heat
gains such as solar gains, internal heat gains and ventilation, and the
calculation of the cooling power demand on the water side to size the cooling
system as regards the chiller size, fluid flow rate, etc. ISO 11855-4
defines a detailed method aimed at the calculation of heating and cooling
capacity in non-steady state conditions. A Thermally Active Surface (TAS) is an
embedded water based surface heating and cooling system, where the pipe is
embedded in the central concrete core of a building construction. The building
constructions embedding the pipe are usually the horizontal ones. As a
consequence, floors and ceilings are usually referred to as active surfaces.
Looking at a typical structure of the TAS, heat is removed by a cooling system
(for instance, a chiller), connected to pipes embedded in the slab. Thermally
active surfaces exploit the high thermal inertia of the slab in order to
perform the peak-shaving. The peak-shaving is to reduce the peak in the
required cooling power, as it is possible to cool the structures of the
building during a period while the occupants are absent (during night time, in
office premises). This way the energy consumption can be reduced and the lower
night time electricity rate can be used. At the same time a reduction in the
size of heating/cooling system components (including the chiller) is possible.
TABS may be used both with natural and
mechanical ventilation (depending on weather conditions). Mechanical ventilation
with dehumidifying may be required depending on external climate and indoor
humidity production. The required peak cooling power needed for dehumidifying
the air during day time is sufficient to cool the slab during night time. As
regards the design of TABS, the planner needs to know if the capacity at a
given water temperature is sufficient to keep the room temperature within a
given comfort range. Moreover, the planner needs also to know the heat flow on
the water side to be able to dimension the heat distribution system and the
chiller/boiler.
When using TABS, the indoor temperature
changes moderately during the day and the aim of a good TABS design is to
maintain internal conditions within the comfort range, i.e. −0,5 < PMV < 0,5,
during the day, according to ISO 7730. Some detailed building system
calculation models have been developed to determine the heat exchanges under
unsteady state conditions in a single room, the thermal and hygrometric balance
of the room air, prediction of comfort conditions, check of condensation on
surfaces, availability of control strategies and calculation of the incoming
solar radiation. The use of such detailed calculation models is, however,
limited due to the high amount of time needed for the simulations. The
development of a more user friendly tool is required. Such a tool is provided
in this part of ISO 11855, and allows the simulation of TAS.
ISO 11855-5 establishes guidelines on
the installation of embedded radiant heating and cooling systems. It specifies
uniform requirements for the design and construction of heating and cooling
floors, ceiling and wall structures to ensure that the heating/cooling systems
are suited to the particular application. The requirements specified by this
part of ISO 11855 are applicable only to the components of the
heating/cooling systems and the elements which are part of the heating/cooling
surface and are installed for the heating/cooling systems.
ISO 11855-6 describes the control of
hydronic systems to enable all embedded systems to perform as simulated. The
design documents shall include specifications for the control system. The
control system shall be capable of varying heating or cooling outputs as well
as maintaining predetermined room or surface temperatures. The control system
shall, if specified, protect buildings and equipment against frost and moisture
damage where necessary (when normal comfort temperature level is not required)
and prevent condensation from occurring. The design of the control system shall
take into account the building, its intended use and the effective functioning
of the embedded system, efficient use of energy and avoid conditioning the
building at full design conditions when not required.
Due to the high impact that fast varying
heat gains (e.g. sunshine through windows) may have on the room temperature, it
is necessary that the radiant system control to compensate this by reducing or
increasing the temperature difference between room and heated/cooled surface
and partly on the difference between room and the average temperature output.
For the low temperature heating and high temperature cooling systems, the
“self-regulating effect” is significant. The “self-regulating” depends on the
average water temperature in the panels. It means that fast change of operative
temperature will equally change heat exchange and result in influence of total
heat exchange. This impact is bigger for systems with surface temperatures
close to room temperature because the change of one degree represents a higher
percentage based on a small temperature difference than on a high temperature
difference. The self-regulating effect of low temperature heating and high
temperature cooling systems supports the control equipment (e.g. individual
room temperature control) in maintaining a stable thermal environment providing
comfort to persons in the room.
Water based radiant heating and cooling
systems need hydronic balancing. The components shall be adjusted in order to
ensure the required flow rates. Under dynamic conditions, e.g. during the
heating up/cooling down period, it must be ensured that the hydraulic
interaction between the different circuits is small (the flow rates in
different circuits shall not be greater than the design flow rates). Depending
on the situation of the heating/cooling system, the panel distribution system
shall be equipped with facilities for degassing and sludge separation.
The control modes of embedded systems are
based on three system levels:
1) Local (room) control, where the energy supplied to a room is
controlled
2) Zone control normally consisting of several spaces (rooms)
3) Central control where energy supplied to the whole building is
controlled by a central system
The control system classification is based
on performance level:
1) Manual: The energy supply to the conditioned space is only
controlled by a manually operated device
2) Automatic: A suitable system or device automatically controls
energy to the conditioned spaces
3) Timing: Function of energy supplied to a conditioned space is
shut off or reduced during scheduled periods, e.g. night setback (not
necessarily applicable for cooling)
4) Advanced timing: Function of energy supply to the conditioned
space is shut-off or reduced during scheduled periods, e.g. daytime with more
expensive electricity tariff. Re-starting of the energy supply is optimized
based on various considerations, including reduction of energy use (not
applicable in commercial buildings).
In general, HVAC systems have been designed
as all-air HVAC systems in European countries. Radiant heating and cooling
systems can be integrated with general HVAC system by separating the tasks of
ventilation and thermal space conditioning. By using the primary air
distribution to fulfill the ventilation requirements and the secondary water
distribution system to thermally condition the space, the amount of air circulation
through buildings can be reduced significantly, because the ventilation air can
be supplied by outside fresh air without affecting the recirculation of air. To
secure the performance of radiant heating and cooling system, there must be
standards for processes and conditions that determine the heating and cooling
capacity of radiant heating and cooling systems. The purpose of ISO 11855
lies above all in enabling the radiant heating and cooling systems to perform
in accordance with occupants’ comfort by providing standards for determining
the heating and cooling capacity of radiant heating and cooling systems. These standards
may be seen as integrated design standards that make possible the effective
design of the entire system by providing standards regarding heat emission
calculation, panel design, and system construction.
The authors would like to acknowledge the contributions of the other
experts in the team that is responsible for the preparation of the ISO 11855
in the ISO working group to which the preparation of these standards has been
assigned.
ISO 11855-1 Building environment
design — Design, dimensioning, installation and control of embedded radiant
heating and cooling systems —Part 1: Definition, symbols, and comfort criteria.
ISO 11855-2 Building environment
design — Design, dimensioning, installation and control of embedded radiant
heating and cooling systems — Part 2: Determination of the design and heating
and cooling capacity.
ISO 11855-3 Building environment
design — Design, dimensioning, installation and control of embedded radiant
heating and cooling systems —Part 3: Design and dimensioning.
ISO 11855-4 Building environment
design — Design, dimensioning, installation and control of embedded radiant
heating and cooling systems —Part 4: Dimensioning and calculation of the
dynamic heating and cooling capacity of Thermo Active Building Systems (TABS).
ISO 11855-5 Building environment
design — Design, dimensioning, installation and control of embedded radiant
heating and cooling systems —Part 5: Installation.
ISO 11855-6 Building environment
design — Design, dimensioning, installation and control of embedded radiant
heating and cooling systems —Part 6: Control.
Follow us on social media accounts to stay up to date with REHVA actualities
0